English (GB)

17

37

360

Device changed 
(same type)

Option board changed for one 
previously inserted in the same slot. 
The board's parameter settings are 
saved.

Device is ready for use. Old 
parameter settings will be used.

38

370

Device changed 
(same type)

Option board added. The option 
board was previously inserted in the 
same slot. The board's parameter 
settings are saved.

Device is ready for use. Old 
parameter settings will be used.

39

380

Device removed

Option board removed from slot.

Device no longer available.

40

390

Device unknown

Unknown device connected (power 
unit/option board)

Device no longer available.

41

400

IGBT temperature

IGBT temperature (unit temperature 
+ I

2

T) is too high.

Check loading.
Check motor size.
Make identification run.

44

430

Device changed 
(different type)

Option board changed or Power unit 
changed. No parameter settings are 
saved.

Set the option board parameters 
again if option board was 
changed. Set converter 
parameters again if power unit 
was changed.

45

440

Device changed 
(different type)

Option board added. The option 
board was not previously present in 
the same slot. No parameter settings 
are saved.

Set the option board parameters 
again.

46

662

Real Time Clock

RTC battery voltage level is low and 
the battery should be changed.

Replace the battery.

47

663

Software updated

Software of the drive has been 
updated (either the whole software 
package or application).

No actions needed.

50

1050

AI low fault

At least one of the available 
analogue input signals has gone 
below 50 % of the defined minimum 
signal range.
Control cable is broken or loose.
Signal source has failed.

Change the failed parts.
Check the analog input circuit.
Check that parameter AI1 signal 
range is set correctly.

51

1051

External Fault

Fault activated by digital input.

Check the digital input or the 
device connected to it.
Check the parameter settings.

52

1052
1352

Keypad 
communication 
fault

The connection between the control 
keypad and frequency converter is 
broken

Check keypad connection and 
possible keypad cable

53

1053

Fieldbus 
communication 
fault

The data connection between the 
fieldbus master and fieldbus board is 
broken

Check installation and fieldbus 
master.

54

1654

Slot D fault

Defective option board or slot

Check board and slot.

1754

Slot E fault

57

1057

Identification

Identification run has failed.

Check that motor is connected 
to the drive.
Ensure that there is no load on 
the motor shaft. 
Ensure that the start command 
will not be removed before 
completion of identification run.

Fault 

code

Fault

ID

Fault name

Possible cause

Remedy

Содержание RSI Series

Страница 1: ...RSI 1 5 37 kW Installation and operating instructions GRUNDFOS INSTRUCTIONS...

Страница 2: ...ctions Installation and operation must comply with local regulations and accepted codes of good practice Advanced IO http net grundfos com Appl ccmsservices public literature filedata Grundfosliteratu...

Страница 3: ...5 5 5 kW TM06 6526 1813 E W W2 L1 L L2 H H2 H1 Frame Size Product Net weight kg E mm W mm W2 mm L mm L1 mm L2 mm H mm H1 mm H2 mm Frame A 8 8 5 9 143 5 191 0 297 0 293 0 315 0 188 0 197 0 214 0 Frame...

Страница 4: ...W2 H H2 H1 L1 L L2 Frame Size Product Net weight kg E mm W mm W2 mm L mm L1 mm L2 mm H mm H1 mm H2 mm Frame B 14 9 6 1 180 0 233 0 349 0 345 2 368 0 204 0 214 0 231 0 Frame Size Package Gross weight...

Страница 5: ...W2 H H2 H1 L1 L L2 Frame Size Product Net weight kg E mm W mm W2 mm L mm L1 mm L2 mm H mm H1 mm H2 mm Frame C 31 5 8 2 322 0 350 0 385 0 382 5 500 0 230 0 236 0 254 0 Frame Size Package Gross weight...

Страница 6: ...age VAC 220 380 Enclosure class IP66 IP66 Power kW Product number Electrical Data Frame size Max P2 kW Rated Output Current A 1 5 99090622 1 5 8 A 2 2 99090633 2 2 11 A 3 0 99090634 3 0 12 5 A 4 0 990...

Страница 7: ...he control panel and select min Frequency Caution To ensure a good convective cooling effect install the inverter vertically with at least 10 cm free space at the top and bottom To be installed indoor...

Страница 8: ...Can be isolated from ground see chap 12 24Vout 24V aux voltage 13 GND I O ground 14 DI4 Digital input 4 15 DI5 Digital input 5 16 DI6 Digital input 6 17 CM Common for DI1 DI6 18 AO1 Analogue output v...

Страница 9: ...every 1500 m increase in altitude Note Adjust control parameters according to the steps indicated in this manual before the first start TM05 4446 2412 Digital display control panel Operating keys The...

Страница 10: ...ntrol panel and edit parameter values Down key Navigate control panel and edit parameter values Right key Navigate control panel and edit parameter values Left key Navigate control panel and edit para...

Страница 11: ...lay Directions Notes Select Language Select Start up Wizard Verify or adjust the rated motor voltage Verify or adjust the rated frequency Verify or adjust the nominal speed Verify or adjust the rated...

Страница 12: ...Select pump type or Other and adjust parameters Select solar modules or other and adjust Vmp maximum power voltage Select the number of solar modules Select if sinus filter is used or not Display Dir...

Страница 13: ...req Reference Target frequency 50 Acceleration time Initial ramp time 3 Deceleration time Final ramp time 3 PV modules type Solar panel type sw260 Module MP Voltage Vmp Maximum power point voltage 31...

Страница 14: ...n time longer Use brake chopper or brake resistor available as options Activate overvoltage controller Check input voltage 11 Overvoltage software fault 3 20 Earth fault hardware fault Current measure...

Страница 15: ...o you 609 Memory access has failed For example retain variables could not be restored 610 Necessary device properties cannot be read 614 Configuration error 647 Software error Update software Should t...

Страница 16: ...ure Motor is overloaded Decrease motor load If no motor overload exists check the temperature model parameters 17 160 Motor underload Motor is underloaded Check load 19 180 Power overload short time s...

Страница 17: ...l Time Clock RTC battery voltage level is low and the battery should be changed Replace the battery 47 663 Software updated Software of the drive has been updated either the whole software package or...

Страница 18: ...limit Carry out the needed maintenance and reset counter 69 1310 Fieldbus mapping error Non existing ID number is used for mapping values to Fieldbus Process Data Out Check parameters in Fieldbus Dat...

Страница 19: ...ched the alarm limit Find the cause of temperature raise Check the temperature sensor and connections Check that the temperature input is hardwired if no sensor is connected See option board manual fo...

Страница 20: ...circuit Insulation tests must not be performed on a single terminal Use a 500 V mega ohm meter to conduct the test 2 When conducting an insulation test on the motor dismantle the connection between mo...

Страница 21: ...on environment 2 Radiator 3 Fan 1 Good ventilation in installation environment 2 Radiator air duct not blocked 3 Fan should be running smoothly if equipped Inverter cabinet 1 Vibration 2 Temperature r...

Страница 22: ...ong period of time It is thus necessary to start up the equipment every two years to restore the performance of the capacitor and inspect the inverter function at the same time The voltage must be inc...

Страница 23: ...23...

Страница 24: ...Tallinn Tel 372 606 1690 Fax 372 606 1691 Finland OY GRUNDFOS Pumput AB Trukkikuja 1 FI 01360 Vantaa Phone 358 0 207 889 500 Telefax 358 0 207 889 550 France Pompes GRUNDFOS Distribution S A Parc d A...

Страница 25: ...5020 1426 sk grundfos com Slovenia GRUNDFOS LJUBLJANA d o o Lesko kova 9e 1122 Ljubljana Phone 386 0 1 568 06 10 Telefax 386 0 1 568 06 19 E mail tehnika si grundfos com South Africa GRUNDFOS PTY LTD...

Страница 26: ...4145 0516 ECM 1184037 The name Grundfos the Grundfos logo and be think innovate are registered trademarks owned by Grundfos Holding A S or Grundfos A S Denmark All rights reserved worldwide Copyright...

Отзывы: