0-5 V
•
0-10 V
•
0-20 mA
•
4-20 mA.
Sensor range, minimum value
Set the minimum value of the connected sensor.
Sensor range, maximum value
Set the maximum value of the connected sensor.
Related information
6.6.1 Setting two sensors for differential measurement
6.6.1 Setting two sensors for differential measurement
Two analog sensors must be installed and connected electrically to measure a parameter at two different locations in a system.
The pressure, temperature and flow parameters can be used for differential measurement.
•
Set the analog inputs according to the measured parameter:
Parameter
Sensor 1, measured parameter
Sensor 2, measured parameter
Pressure, option 1
Inlet pressure
Discharge press.
Pressure, option 2
Press. 1, external
Press. 2, external
Flow
Pump flow
Flow, external
Temperature
Temperature 1
Temperature 2
If you want to use the
Con. diff. press.
,
Con. diff. temp.
or
Const. flow rate
control modes, you must configure both sensors
as
Feedback sensor
.
Related information
6.7 "Pt100/1000 inputs"
The inputs and outputs available depend on the functional module fitted in the motor.
Functional module
Pt100/1000 input 1
(Terminals 17, 18)
Pt100/1000 input 2
(Terminals 18, 19)
FM 100 (basic)
-
-
FM 200 (standard)
-
-
FM 300 (advanced)
•
•
In order to set the Pt100/1000 input for a feedback sensor, we recommend that you do this via the
"Assisted pump setup"
menu. If you wish
to set a Pt100/1000 input for other purposes, you can do this manually.
Function
You can set the inputs to these functions:
•
Not active
•
Feedback sensor
The sensor is used for the selected control mode.
•
Setpoint influence
The input signal is used for influencing the setpoint.
•
Other function
The sensor input is used for measurement or monitoring.
Measured parameter
Select one of the below parameters to be measured in the system by the sensor connected to the input.
TT
TT
TT
DTT
4
3
1
2
TM064012
42
English (GB)