English (GB)

12

9.2 Fitting the sleeve

1. Fold the sleeve and insert it into the hole (from the outside of 

the pit).

2. Unfold the sleeve so that it lies evenly in the hole.

3. LM50/100 sleeves: Pull the sleeve outwards until its collar 

touches the inside of the pit all around the hole.
L965 sleeves: Pull the sleeve outwards until its collar touches 
the inside of the pit at the positions 3 and 9 o’clock. 
See fig. 20.

4. Lubricate the inside of the sleeve with a water-based lubricant.

5. Chamfer the pipe and press it home.

LM50/100 sleeves: Push the inlet pipe through the sleeve. 
See fig. 18.

Fig. 18 Pipe with LM50/100 sleeve, seen from side

L965 sleeves: Push the inlet pipe into the sleeve and against the 
stop. See fig. 19.

Fig. 19 Pipe with L965 sleeve, seen from side

Fig. 20 Pipe with L965 sleeve, seen from top

9.3 Installation of pump

Some versions come without the pump installed. For installation 
and start-up of the pump, see the installation and operating 
instructions of the pump.

9.4 Pipework with flange connections

9.5 Fitting the chain

In the case of pumps on auto coupling, we recommend to fit the 
chain in the foremost lifting eye of the lifting bracket. The number 
of lifting eyes depends on the pump.

Fig. 21 Chain fitted to pump

10. Pump control

When installing the level switches, the following points should be 
observed: 

To prevent air intake and vibrations in the pump, the stop level 
switch must be fitted in such a way that the pump is stopped 
before air is sucked into the pump.

In the case of 1-pump operation, the start level switch should 
be installed in such a way that the pump is started at the 
required level; however, the pump must always be started 
before the liquid level reaches the lower edge of the bottom 
inlet pipe. 

In the case of 2-pump operation, the start level switches 
should be installed in such a way that pump 2 is started before 
the liquid level reaches the lower edge of the bottom inlet pipe 
to the pit, and so that pump 1 is started correspondingly 
earlier.

The high-level alarm switch should always be installed about 
10 cm above the start level switch; however, the alarm must 
always be given before the liquid level reaches the inlet pipe. 

For further settings, see the installation and operating instructions 
for the pump controller selected.

10.1 Start and stop levels

The effective volume of the pump pit must be so large that the 
number of starts does not exceed the maximum permissible 
number. See the installation and operating instructions of the 
pump.

10.2 Installation of level controller

See the installation and operating instructions of the controller.

Note

As it must be possible to pull the pump up 
through the pit, the inlet pipe must not project 
beyond the sleeve by more than 5 cm.

TM

03 37

09 08

06

T

M

03

 37

08

 08

0

6

TM

03

 37

68

 10

06

Caution

Lower the pump carefully into the pit in order to 
avoid damage to pump and pit.

Pit side

Max. 5 cm

Pit side

Pit side

Note

If the pit is to be installed at a temperature below 
0 °C, slacken all bolts of the flange and retighten 
them when the pit has been installed. 
This prevents stress in the pipes.

T

M

02

 93

41

 24

0

4

Warning

The lifting equipment used for lifting the pump 
must be rated for the weight of the pump and 
approved according to local regulations.

Содержание PUST04

Страница 1: ...t be led into the pit See also the installation and operating instructions of the pump 3 1 4 Density Maximum 1 1 tons m3 1 Symbols used in this document 6 2 General description 6 3 Applications 6 3 1...

Страница 2: ...inless steel AISI 304 Prepared for pump type KP Unilift KP Unilift CC AP35 Unilift AP12 40 Unilift AP35 AP50 Unilift AP12 50 Unilift AP50 APB Unilift AP35B Unilift AP50B DPEF DP 0 6 1 5 kW EF DPSE DP...

Страница 3: ...B 8 TM02 9364 2404 TM02 9363 2404 Fig 3 Pit with free standing pump Fig 4 Pit with pump on auto coupling TM02 9366 2404 TM02 9365 2404 Fig 5 Pit with pump on wall mounted auto coupling Fig 6 Pit with...

Страница 4: ...viest standard pit weighing approximately 1000 kg 7 Sizing The pit volume depends on the wastewater flow rate and the pump performance If the liquid in the pit is static during long periods sediments...

Страница 5: ...The backfill must meet the same requirements as those for the bedding layer The backfilling must be carried out so that the pit is not damaged or deformed The backfill must be compacted in layers of m...

Страница 6: ...cutting edge of the hole saw by at least 23 mm The position of the hole is not an issue See fig 17 Fig 17 Drillilng from the inside Caution If the hole for the pit is drilled pay special attention to...

Страница 7: ...he start level switch should be installed in such a way that the pump is started at the required level however the pump must always be started before the liquid level reaches the lower edge of the bot...

Страница 8: ...lse generators for the pressure switches of the controller and function by means of pneumatic pressure changes The pressure changes when the liquid level in a pickup changes The air bells are connecte...

Страница 9: ...oduct or parts of it must be disposed of in an environmentally sound way 1 Use the public or private waste collection service 2 If this is not possible contact the nearest Grundfos company or service...

Отзывы: