8
English (US)
8. Mechanical installation
8.1 Location
The pump is suitable for indoor and outdoor
installation. It is resistant to sunlight.
8.2 Foundation
Mount the pump on the base plate with horizontal
suction port and vertical discharge port.
The pump must be installed horizontally.
The maximum permissible inclination angle is ± 18 °.
See fig.
Fig. 2
Horizontal installation of MQ
To prevent movement and vibrations, the pump and
base plate can be secured to a solid foundation by
means of the bolt holes in the base plate.
For pipework connection, see section
The bolt holes are covered by a thin plastic layer that
must be knocked out before use. See fig.
.
Fig. 3
Knocking out the plastic layer in bolt
hole
Fig. 4
Base plate
Note
For outdoor installation, the pump
must be fitted with a protective cover
(accessory). See section
and
.
Caution
Should the unlikely event of an internal
leakage occur, pumped liquid will be
drained out from the base and/or end
cover instead of damaging the pump.
Install the pump in such a way that no
undesirable collateral damage can
arise.
TM
01
96
91
26
00
Max. ± 18 °
TM
05 515
6 341
2
T
M
01
96
92
26
00
1
1
.4 c
m
19.0 cm
Содержание MQ 3-35
Страница 1: ...GRUNDFOS INSTRUCTIONS MQ Installation and operating instructions US C ...
Страница 2: ...2 ...
Страница 56: ...56 Appendix Appendix 1 Exploded view TM02 8410 4812 ...
Страница 58: ...58 ...