page 22
6
INTERFACING MIXIT TO THE BMS USING ANALOGUE SIGNALS
In the case of retrofit where no BACnet or Modbus interfaces are available MIXIT can be controlled via
analogue signals. The complete terminal overview is given in the MIXIT installation and operating instructions
that can be downloaded at
https://product-selection.grundfos.com/
, search for MIXIT, click on a MIXIT
product and browse to documentation. The most relevant are listed in Table 8.
Action
Input
Notes
Relevant MIXIT application
Set start
Pull DI5 low
Input has internal pull up
all applications
Set stop
Pull DI5 up
Input has internal pull up
all applications
Set setpoint
CI01
Configure range and type in
Grundfos GO
all applications
Temperature control
enabled
Relay 2
all applications
Fault
Relay 1
all applications
Boiler setpoint
CIO3
Voltage 0-10 corresponds to
0-100 deg. C.
all applications
Set overheat risk
Pull DI4 up
Input has internal pull down
underfloor heating
Remove overheat risk
Pull DI4
down
Input has internal pull down
underfloor heating
Set frost risk
Pull DI4 up
Input has internal pull down
heating coil
Remove frost risk
Pull DI4
down
Input has internal pull down
heating coil
Air sensor input
CI02
Configure range and type in
Grundfos GO
heating coil
Table 8: Most relevant datapoints associated with the underfloor and radiator heating applications.