Analog inputs
5.2 Outputs
Digital outputs
Transducer supply
Identification of phase sequence
5.3 Terminals
Digital inputs
Thermal switch / PTC inputs (5 V)
Voltage category
II
Insulation voltage
50 V
(to system earth)
Insulation test voltage
700 VDC
Input band width
10 Hz, second order
filter
Mains frequency
suppression
50-60 Hz
Voltage input:
Voltage range
0-10 V
2-10 V
Input resistance
250 k
Ω
Input resolution
40 mV
Gain error at 25°C
0.4%
Gain error during operation
(rms)
60 ppm/°C
Current input:
Current range
0-20 mA
4-20 mA
Input resistance
250
Ω
Input resolution
80 µA
Gain error at 25°C
0.4%
Gain error during operation
(rms)
75 ppm/°C
Filter times:
Integration time
100 ms
Reading interval
400 ms
Voltage category
III
Insulation voltage
400 V (to all other
terminals)
Insulation test voltage
4 kVAC
Insulation between
two channels
2.6 kVAC
Max. load
400 VAC, 2 A, AC-15/
24 VDC, 2 A, DC-15
Min. load
5 V/10 mA
Max. load power AC/DC
400 VA/48 W
Contact type
NO (normally open
contact)
Output voltage without
load
22 V
Output voltage at 25 mA
20 V
Max. current per channel
25 mA
Voltage category
III
Insulation voltage
when using the FB 101
480 VAC
(to system earth)
Insulation test voltage
4 kVAC
Voltage range
85-480 VAC
Input resistance
100 M
Ω
Terminal designation Description
DI1
Digital input
DI2
Digital input
DI3
Digital input
DI4
Digital input
DI5
Digital input
6 x 0 V
Common zero point
Terminal designation Description
T6 (pump 1)
PTC 1
T7 (pump 1)
PTC 2
T (pump 1)
0 V for T6 and T7
T6 (pump 2)
PTC 1
T7 (pump 2)
PTC 2
T (pump 2)
0 V for T6 and T7