E
ngli
sh (
G
B)
20
3
PE
Earth
Earth
Supply voltage to the IO 111
-
GND for supply
voltage
0 VDC
24 VAC ± 10 %
+
Plus for supply
voltage
24 VAC ± 10 %
24 VDC ± 10 %
5
A
RS485 A
Bus input
RS485 communication connection
(9600 baud)
Y
RS485 GND
0 V
B
RS485 B
Bus input
9
I1
Earth
Earth
The insulation resistance between
stator windings and earth is measured.
The measurement is only correct when
the motor is stopped.
Measurement voltage: 10 VDC.
I2
Not connected
-
I3
Terminal for
measurement of
stator insulation
resistance
CAT II 600 V
10
P1
Terminal for
sensors in the
pump
Sensor input
Thermal switch or PTC sensor
according to DIN 44081 and 44082.
P1 to P5 are used for the connection of
sensors in the pump. All sensors in
contact with phase voltage must be
double insulated according to
EN 61010-1.
P2
Terminal for
supply voltage
to sensors in
the pump
15 V
P3
Terminal for
sensors in the
pump
Sensor input
P4
Terminal for
supply voltage
to sensors in
the pump
15 V
P5
Terminal for
sensors in the
pump
Sensor input
Pos.
Terminal
Description
Data
Function
Diagram
+
A
Y
B
L1
L2
L3
I3
I1
P1..P5
Grundfos.bk Page 20 Tuesday, January 25, 2011 12:56 PM
Содержание IO 111
Страница 2: ...Grundfos bk Page 2 Tuesday January 25 2011 12 56 PM...
Страница 116: ...RU 116 1 3 1 4 1 5 1 6 VDE 1 7 1 8 1 9 3 Grundfos bk Page 116 Tuesday January 25 2011 12 56 PM...
Страница 145: ...145 Grundfos bk Page 145 Tuesday January 25 2011 12 56 PM...
Страница 146: ...146 Grundfos bk Page 146 Tuesday January 25 2011 12 56 PM...