17
English (US)
Pos.
Terminal
Description
Data
Diagram
1
L
Connection to phase conductor
1 x 100-240 VAC ± 10 %, 50/60 Hz
N
Connection to neutral conductor
PE
Connection to protective earth
2
A1
RS-485 A
GENIbus (internal)
Fix the screen with a cable clamp.
Y1
RS-485 GND
B1
RS-485 B
Functional earth
3
Connection to external fieldbus, see installation and operating instructions for the CIM module.
4
30
PTC 1
Input for PTC sensor or thermal switch.
31
GND, PTC
32
PTC 2
33
GND, PTC
34
PTC 3
5
50
+ 24 V
Supply to sensor.
Short-circuit-protected 30 mA.
51
AI1
Input for analog signal.
0-20 / 4-20 mA or 0-10 V.
53
+ 24 V
Supply to sensor.
Short-circuit-protected 30 mA.
54
AI2
Input for analog signal.
0-20 / 4-20 mA or 0-10 V.
55
GND
All terminals (except mains terminals) must only be connected to voltages not exceeding 16 V
rms
and 22.6 V
peak
or 35 VDC.
6
77
Relay 1
Relay contact for starting and stopping
mains-operated pumps.
79
Relay 2
80
Common
80
Common
81
Relay 3
7
70
Relay 1
C
71
Relay 1
NO
72
Relay 1
NC
73
Relay 2
C
74
Relay 2
NO
75
Relay 2
NC
8
10
DI1
Digital input
11
GND
12
DI2
All terminals (except mains terminals) must only be connected to voltages not exceeding 16 V
rms
and 22.6 V
peak
or 35 VDC.
9
GENIbus
Service connection
L
N
CU
L
N
P
A
Y
B
CU E-pump
A1
Y1
B1
34
33
32
31
30
PTC 1
CU 323
PTC 3
PTC 2
54
53
50
51
55
1
2
CU 323
CU 323
81
77
79
80
80
74
73
72
70
71
75
CU 323
12
11
10
CU 323