6.5 Connecting the IO connections
WARNING
Electric shock
Death or serious personal injury
‐
The IO connections of the GiM CIU
unit must be connected to SELV or
SELV-E circuits only.
A screened cable must be used and it
must be connected to an earth clamp
inside the unit.
1. Connect the input and output terminals according
to the drawing.
AI/DI_1
GND
AI/DI_2
GND
AI/DI_3
GND
Pt100/1000
24VDC_EXT_1 (Max. 50 mA)
24VDC_EXT_2 (Max. 50 mA)
24VDC_EXT_3 (Max. 50 mA)
DI
GND
DO_NO (Max. 30 V/500 mA)
DO_COM (Max. 30 V/500 mA)
MODBUS_D1
MODBUS_GND
MODBUS_D0
GENIbus_A
GENIbus_Y
GENIbus_B
TM076438
Wiring diagram
Options for configuration of connections
Electrical signals
DI
AI/DI 1
AI/DI 2
AI/DI 3
Pt100(0)
Digital input
x
Analog input, 0 - 20 mA
x
x
x
Analog input, 4 - 20 mA
x
x
x
Analog input, 0 - 10 V
x
x
x
Analog input, 0 - 5 V
x
x
x
Analog input, 0.5 - 3.5 V
x
x
x
Pt100
x
Pt1000
x
Related information
6.2 Connecting the power supply
6.6 Connecting to a Modbus network
12
English (GB)
Содержание GiM CIU
Страница 2: ......
Страница 132: ...8 维修产品 该模块无法维修 联系格兰富 如果模块出现故障 必须更换模块 8 1 清洁产品 只能用干净的干布或沾有肥皂水的湿布清洁产品 132 中文 CN ...