Service and maintenance
Warning
•
Maintenance and inspection must be performed by a qualified electrician. Do not dismantle the pump controller when it is running.
•
The pump controller must be powered off at least 5 minutes before conducting maintenance and inspection.
•
It is absolutely forbidden for unauthorised persons to repair the pump controller as this can cause personal injury or equipment damage.
Any service performed on the pump controller by unqualified staff will void the warranty.
9.1
Routine inspection
To ensure the pump controller runs stably, carry out an annual inspection.
Warning
The inspection must be performed by trained and qualified technical staff.
Disconnect the power supply to the pump controller before starting inspection.
Inspection frequency
Inspection issue
Inspection item
Criteria or requirement
Routine
1)
Regular
2)
✓
Running environment
1. Temperature.
2. Humidity.
3. Gas.
4. Dust.
1. Temperature < 50 °C.
2. Humidity < 90 %, no
condensation.
3. No flammable, explosive gas.
4. Non-corrosive environment.
✓
Cooling system
1. Installation
environment.
1. Good ventilation in installation
environment.
✓
Inverter cabinet
1. Vibration.
2. Temperature rise.
3. Noise.
4. Leads, terminals
1. A vibration that appears steady
and normal
2. Normal temperature.
3. No abnormal noise.
4. Leads and terminals fastened
properly.
✓
Motor
1. Vibration.
2. Temperature rise.
3. Noise.
1. Steady running.
2. Normal temperature.
3. No abnormal noise.
✓
Input and output parameters
1. Input voltage.
2. Output current.
1. Input voltage within limit.
2. Output current under the rated
value.
1.
Every 1000 running hours.
2.
Every month
9.2
Storage and warranty
9.2.1
Storage
If the product is stored for a long time after purchasing,
comply with the following requirements:
1. Avoid placing the pump controller in high-temperature or
humid areas or areas with vibration and metal dust. Ensure
ventilation.
2. The performance of the capacitor inside the pump
controller can be reduced if the equipment is not used for a
long period of time. It is thus necessary to start up the
equipment every two years to restore the performance of
the capacitor and inspect the pump controller function at
the same time. The voltage must be increased gradually
through a DC power supply with power-on time being not
less than 5 hours.
9.2.2
Warranty
The following situations are not covered by the warranty:
• Faults caused by failure to comply with this manual or
standard specifications.
• Faults caused by self
-repairing and modification without
permission.
• Faults caused by poor storage and maintenance.
• Faults caused by abnormal use of the
pump controller.
• Damage caused by fire, salt corrosion, gas
corrosion,
earthquake, storm, flooding, lightning, abnormal voltage or
another force majeure situation.
10
Disposal
This product or parts of it must be disposed of in an
environmentally sound way:
1. Use the public or private waste collection service.
2. If this is not possible, contact the nearest Grundfos
company or service workshop.