Short terminals 1,2,3. Connect common liquid level probe in terminal no. 4 which is 

placed at the bottom of the tank touching the surface. Connect the lower liquid 

level probe in terminal no. 5 (this should be ideally at the level where the pump is 

desired to run). Connect the upper liquid level probe in terminal no. 6 (this should 

be ideally at the level where the pump is desired to stop ie. Tank should be full).

 

 

Start Condition: 

If the water level in the OH tank falls below the lower liquid level 

probe, the pump starts. LCD screen displays RUN indicating pump is running.

 

Stop Condition: 

If the water level in the OH tank rises above the upper liquid level 

probe, the pump stops. LCD screen displays FULL, indicating OH tank is full.

 

 

 
 
 
 
 

(i)

 

Using 2 float switches – for pump start & stop and overflow alarm (level-2)

 

 

 
 

 
 
 
 

 

(h)

 

Using 1 float switch - for pump start & stop

 

Connect common of Float switch to terminal 1, connect NO point of Float switch 

to terminal 2. Short terminals 2,3. Kindly ensure terminals 4,5,6 are open.

 

Start condition: 

If the water level in the pit/tank rises and the float switch is in up 

position, the pump starts. LCD screen displays RUN indicating pump is running.

 

Stop condition: 

If the water level in the pit/tank decreases and the float switch in 

down position, the pump stops. LCD screen displays NO WATER, indicating there is 

no liquid level in pit/tank.

 

Connect common of Float Switch A to terminal 1, connect NO point of Float 

switch A to terminal 2. Short terminals 2,3

 

Connect common of Float Switch B to terminal 4, connect NO point of Float 

switch B to terminal 6. Kindly ensure terminal 5 is open.

 

Start condition: 

If the water level in the pit/tank rises and the float switch is in 

up position, the pump starts. LCD screen displays RUN indicating that the pump 

is running.

 

Stop condition: 

If the water level in the pit/tank decreases and the float switch 

in down position, the pump stops. LCD screen displays NO WATER, indicating 

there is no liquid level in pit/tank.

 

Alarm condition: 

If the water level in the pit/tank rises even further despite 

pump running and Float switch (Level-2) is in up position, there is an audio-visu- 

al alarm. LCD screen displays OVERFLOW indicating that liquid level in the 

pit/tank has reached Overflow level.

 

Drainage / De-watering

 

Содержание DPC 1-1 CSCR

Страница 1: ...CR For Single Phase Pumps 0 37 2 2 kW For more information contact us The name Grundfos the Grundfos logo and we think innovate are registered trademarks owned by Grundfos Holding A S or Grundfos A S...

Страница 2: ...controller Installation 6 Controller components 6 LCD screen 6 Terminals 8 DIP switch settings 9 PARAMETER CALIBRATION AND ERASING 9 Calibration 9 Erasing 10 CONNECTIONS CONTROLS DEVICES AND APPLICAT...

Страница 3: ...time of dry run 6 sec or this can be set manually Recovery time of over load 30 min Recovery time of under over voltage 5 min Recovery time of dry run 30 min or this can be set manually Trip voltage...

Страница 4: ...following tools You also can choose the right tools according to your own experience INSTALLATION CONTROLLER COMPONENTS LCD Screen Voltage v M Minute Second S H Hour Ampere A The parameter configurati...

Страница 5: ...paired and installed back Setting of parameters calibration of unit according to the connected load X X X X X X b Control terminals for connecting probes or float switches Press the MODE key to switch...

Страница 6: ...will start flashing on the LCD screen For re calibration follow the instruction as given in CALIBRATION section ERASING NOTE For all applications connect the NO contact of float switch in down positi...

Страница 7: ...ys RUN indicating pump is running Stop Condition If the water level in the OH tank rises and Float switch in OH tank is in up position the pump stops LCD screen displays FULL indicating OH tank is ful...

Страница 8: ...r level in the pit tank rises and the float switch is in up position the pump starts LCD screen displays RUN indicating pump is running Stop condition If the water level in the pit tank decreases and...

Страница 9: ...LCD screen displays NO WATER that means there is no water in the source tank and can lead to a dry run situation If the Pressure in the line is equal to or above the cut out pressure setting on the p...

Страница 10: ...signal from sensor float switch or pressure switch The controller can memorize hours the pump has run so it is very convenient for the pump users to analyse pump running condition and perform maintena...

Страница 11: ...istance like mine water tower across railway road and bridge etc users can adopt RS485 extender Technical Parameters The following chart shows main technical parameters of communication between the pu...

Страница 12: ...and 5 minutes respectively Liquid level in the borewell or lower tank is below pump intake pump stop running Liquid level in the lower water tank water well is below lower sensor probe float switch in...

Страница 13: ...ated voltage pump is in over voltage protection state Check the power supply at source Control unit will attempt to restart the pump every 5 minutes until line voltage is restored to normal Flashing o...

Страница 14: ...Note Float Pressure Switch should be ordered separately Abbreviation 1 OH Overhead 2 UG Underground 3 NO Normally Open 4 DOL Direct online start 5 COM Common 26...

Отзывы: