Press and hold STOP key and then press STORE key, the product makes a “Beep” 

sound and displays run hours of the pump since the pump was last calibrated.

 

 

 

 

Press the 

 MODE  

key to switch to manual mode. Once the unit is in 

 MANUAL  

mode, press the 

 START  

key to run pump, press the 

 STOP  

key to stop pump.

 

 

NOTE: In manual state, the unit doesn’t receive signal from float switch 

or pressure switch.

 

 

 

Press STOP key to exist the run hours display screen.

 

 

 

 

Press the 

 MODE 

key to switch to auto mode. Once the unit is in 

 AUTO  

mode, 

the pump will start or stop according to the signal from sensor, float switch or 

pressure switch.

 

 

 

The controller can memorize hours the pump has run, so it is very convenient for 

the pump users to analyse pump running condition and perform maintenance.

 

Press MODE key to switch to manual state, make sure the pump is not running.

 

 

The controller can memorize the last  f i ve failures of pump, so it is very convenient 

for the pump users to analyse the pump running conditions and fault trend.

 

 

Press the MODE key to switch to manual state, make sure the pump is not running 

and LCD screen displays as below:

 

 

Press and hold the STOP key and MODE key together, the controller makes a “Beep” 

sound and the product displays last  f i ve fault records.

 

AUTO MODE:

 

BASIC OPERATION

 

Displaying Run Hours of The Pump:

 

 

MANUAL MODE:

 

Содержание DPC 1-1 CSCR

Страница 1: ...CR For Single Phase Pumps 0 37 2 2 kW For more information contact us The name Grundfos the Grundfos logo and we think innovate are registered trademarks owned by Grundfos Holding A S or Grundfos A S...

Страница 2: ...controller Installation 6 Controller components 6 LCD screen 6 Terminals 8 DIP switch settings 9 PARAMETER CALIBRATION AND ERASING 9 Calibration 9 Erasing 10 CONNECTIONS CONTROLS DEVICES AND APPLICAT...

Страница 3: ...time of dry run 6 sec or this can be set manually Recovery time of over load 30 min Recovery time of under over voltage 5 min Recovery time of dry run 30 min or this can be set manually Trip voltage...

Страница 4: ...following tools You also can choose the right tools according to your own experience INSTALLATION CONTROLLER COMPONENTS LCD Screen Voltage v M Minute Second S H Hour Ampere A The parameter configurati...

Страница 5: ...paired and installed back Setting of parameters calibration of unit according to the connected load X X X X X X b Control terminals for connecting probes or float switches Press the MODE key to switch...

Страница 6: ...will start flashing on the LCD screen For re calibration follow the instruction as given in CALIBRATION section ERASING NOTE For all applications connect the NO contact of float switch in down positi...

Страница 7: ...ys RUN indicating pump is running Stop Condition If the water level in the OH tank rises and Float switch in OH tank is in up position the pump stops LCD screen displays FULL indicating OH tank is ful...

Страница 8: ...r level in the pit tank rises and the float switch is in up position the pump starts LCD screen displays RUN indicating pump is running Stop condition If the water level in the pit tank decreases and...

Страница 9: ...LCD screen displays NO WATER that means there is no water in the source tank and can lead to a dry run situation If the Pressure in the line is equal to or above the cut out pressure setting on the p...

Страница 10: ...signal from sensor float switch or pressure switch The controller can memorize hours the pump has run so it is very convenient for the pump users to analyse pump running condition and perform maintena...

Страница 11: ...istance like mine water tower across railway road and bridge etc users can adopt RS485 extender Technical Parameters The following chart shows main technical parameters of communication between the pu...

Страница 12: ...and 5 minutes respectively Liquid level in the borewell or lower tank is below pump intake pump stop running Liquid level in the lower water tank water well is below lower sensor probe float switch in...

Страница 13: ...ated voltage pump is in over voltage protection state Check the power supply at source Control unit will attempt to restart the pump every 5 minutes until line voltage is restored to normal Flashing o...

Страница 14: ...Note Float Pressure Switch should be ordered separately Abbreviation 1 OH Overhead 2 UG Underground 3 NO Normally Open 4 DOL Direct online start 5 COM Common 26...

Отзывы: