8.3.12 SCADA settings
The SCADA system is set in this display.
The user must select the individual alarms and warnings that are to
be sent to the SCADA system (SCADA callback). See section about
system alarms.
SCADA callback
The SCADA callback must be enabled in this display.
SCADA callback test
A test can be performed to ensure that the SCADA callback
function works as intended. It can be carried out on site using CU
362 or remotely via PC Tool. CU 362 sends out a test message and
the SCADA system acknowledges it.
Incoming calls
This function is used to protect the connection to the SCADA
system. The user can enter a SCADA system password for
communication with CU 362.
A password must have four digits.
Path:
Settings > Communication settings > SCADA settings
4-3-8_SCADA_SETTINGS_105
SCADA settings
Related information
8.3.3 CIM 250/260 (Modbus and SMS via GSM/GPRS)
8.3.13 Interlock settings
The interlock function is set in this display.
The function can be divided into two areas:
•
Incoming interlock
•
Outgoing interlock.
Incoming interlock
This function ensures that the operating pit is stopped if the next pit
is full. Incoming interlock requires SMS authentication.
Outgoing interlock
This function is used when the operating pit is full. When the pit is
full, up to three downstream pits can be stopped. This prevents an
overflow in this pit.
To enable outgoing interlock, the following criteria must be fulfilled:
•
The pit level is higher than the alarm level.
•
The alarm for alarm level is triggered.
The outgoing interlock is disabled only when the pit level has fallen
to the lowest stop level.
Example
Select or ignore incoming interlock.
Incoming interlock:
•
Ignore incoming interlock.
Outgoing interlock:
•
Interlock, pit 1
•
Interlock, pit 2
•
Interlock, pit 3.
Path:
Settings > Communication settings > Interlock settings
4-3-9_INTERLOCK_SETTINGS_106
Interlock settings
Interlock, pit 1
Outgoing interlock for "Pit 1" is set in this display.
The user must enable an outgoing interlock and enter the telephone
number of the pumping station to be stopped.
Installation name
The user can rename "Pit 1" to the actual installation name. This
makes it easier to identify the pumping station.
Phone number
The user can enter the telephone number of the pumping
station under the installation name.
PIN code enabled
The user can enable the PIN code function. "Pit 1" is thus code-
protected. The PIN code is sent with the SMS interlock message to
stop "Pit 1".
Example:
"Pit 1" must receive a PIN code with an SMS interlock
message. This PIN code must correspond to the code of "Pit 1",
otherwise the command will not be received.
Interlock timeout
An interlock is valid for a specific time period. When the time period
has passed, a new SMS interlock message is sent to stop the
pumping station.
Example
Enable outgoing interlock.
Installation name:
•
Pit 1.
Phone number:
•
+4512345678.
PIN code enabled:
•
PIN code.
Interlock timeout:
•
The interlock is disabled after 20 minutes.
It is important that the receiving pumping station has the
same configuration.
The time limit ensures that the pumping station is not
staying in this condition. Only a communication failure can
cause an indefinite stop.
Path:
Settings > Communication settings > Interlock settings >
Interlock, pit 1
55
English (GB)