Description
Factory settings
Own settings
Start ↔ stop delay
2 s
After-run delay
2 s
After-run delay, high level
2 s
Analog level sensor
AI1 (CU 362)
Level, pressure
4-20 mA
Min. value: 0 m
Max. value: 5 m
10.3 Level
Description
Factory settings
Own settings
Overflow level
4.95 m
High level
4.75 m
Alarm level
3.5 m
Start level 2
2.0 m
Start level 1
1.75 m
Stop level 1
0.5 m
Stop level 2
0.5 m
Dry-running level
0.25 m
Foam-draining level
0.15 m
10.4 CU 362 configuration
Description
Factory settings
Own settings
Units and frequency
SI
Password, Operation menu
Disabled
Password, Settings menu
Disabled
Display language
English
10.5 SMS configuration
Description
Factory settings
Own settings
SMS phone number 1
+45 12345678
SMS phone number 2
+45 12345678
SMS phone number 3
+45 12345678
Send alarm SMS to
Primary SMS number
Acknowledgement deadline
10 minutes
SMS heartbeat message
Monday to Sunday at 12:30
SMS authentication, method
Via PIN code
SMS authentication, PIN code
1234
10.6 SCADA configuration
Description
Factory settings
Own settings
SCADA callback
Disabled
SCADA phone number
+45 12345678
Number of retries
3
Incoming calls, PIN code enabled
Disabled
Incoming calls, PIN code
1234
10.7 System alarms
Description
Factory settings
Own settings
Overflow
-
High level
-
Alarm level
-
Dry running
-
69