English (GB)
6
5.4 Maximum operating pressure
on page
shows the maximum inlet pressure. However,
the actual inlet pr maximum pump pressure (at no flow)
must always be lower than the values stated in
on
page
The pumps are pressure-tested at a pressure of 1.5 times the
values stated in
on page
.
5.5 Minimum flow rate
Due to the risk of overheating, do not use the pump at flows
below the minimum flow rate.
The curves below show the minimum flow rate as a percentage of
the rated flow rate in relation to the liquid temperature.
Fig. 4
Minimum flow rate
5.6 Electrical data
See motor nameplate.
5.7 Frequency of starts and stops
5.8 Dimensions and weights
Dimensions: See
on page
.
Weights:
See label on the packing.
5.9 Sound pressure level
See
on page
6. Installation
The pump must be secured to a horizontal, plane and solid
foundation by bolts through the holes in the base plate.
When installing the pump, follow the procedure below in order to
avoid damaging the pump.
T
M
02
82
90
49
03
Caution
The pump must not run against a closed discharge
valve.
Motor size
[kW]
Maximum number of starts per hour
≤
2.2
250
3-4
100
5.5 - 11
50
18.5 - 22
40
Step
Action
1
T
M
02
00
13
38
00
Arrows on the pump base show
the direction of flow of liquid
through the pump.
2
T
M
00
2
2
5
6
33
93
These pieces of information are
stated in
on page
• port-to-port lengths
• dimensions of the base
• pipework connections
• diameter and position of
foundation bolts.
40
50
60
70
80
90 100 110 120 t [°C]
0
10
20
30
Qmin
[%]
2
1
2
1
L
L
B
4 x ø
B
3
TM
01
12
41
40
97
The pump can be installed
vertically or horizontally.
However, the motor must
neither fall below the horizontal
plane nor be installed upside
down.
Ensure that an adequate supply
of cool air reaches the motor
cooling fan.
Motors above 4 kW must be
supported.
3a
TM
05
77
05
10
13
(Additional support for ships'
use)
To minimize pump vibrations,
additional support brackets can
be mounted. The brackets can
be fitted from the motor or the
motor stool to the bulkhead of
the ship. Mount the bracket in
horizontal position. To minimize
further vibration mount the
bracket at an angle of 30-40 ° to
the wall.
4
TM
02
01
1
6
3
8
0
0
To minimise possible noise from
the pump, we advise you to fit
expansion joints on either side
of the pump. The foundation/
installation must be carried out
as described in section
.
Fit isolating valves on either
side of the pump to avoid
draining the system if the pump
needs to be removed for
cleaning, repair or replacement.
Always protect the pump
against backflow by means of a
non-return valve (foot valve).
5
T
M
0
2
0
114
380
0
Install the pipes so that airlocks
do not occur, especially on the
suction side of the pump.
6
TM
02 01
15
38
00
Fit a vacuum valve close to the
pump if the installation has one
of these characteristics:
• The discharge pipe slopes
downwards away from the
pump.
• There is a risk of siphon
effect.
• Protection against backflow of
unclean liquids is needed.
Step
Action
Содержание CRT
Страница 1: ...CRT Installation and operating instructions GRUNDFOS INSTRUCTIONS ...
Страница 2: ...2 ...
Страница 141: ...141 ...
Страница 142: ...142 ...