Eng
lish (US)
34
10.6 Other technical data
EMC (electromagnetic compatibility)
Standard used: EN 61800-3.
The table below indicates the emission category of the motor.
C1: Fulfills the requirements for residential areas.
C3: Fulfills the requirements for industrial areas.
*
C1, if equipped with an external Grundfos EMC filter.
Immunity: Fulfills the requirements for industrial areas.
Contact Grundfos for further information.
Enclosure class
Standard: IP55 (IEC 34-5).
Optional: IP66 (IEC 34-5).
Insulation class
F (IEC 85).
Standby power consumption
5-10 W.
Cable entries
The cable entries are fitted with blind plugs from the factory.
Cable glands are not provided.
Torques
Motor
Hp (kW)
Emission category
1450-2000 min
-1
2900-4000 min
-1
4000-5900 min
-1
0.33 (0.25)
C1
C1
1/2 (0.37)
C1
C1
3/4 (0.55)
C1
C1
1 (0.75)
C1
C1
1 1/2 (1.1)
C1
C1
2 (1.5)
C1
C1
3 (2.2)
C1
C1
5 (4)
C1
C1
7 1/2 (5.5)
C3/C1*
C1
10 (7.5)
C3/C1*
C3/C1*
15 (11)
-
C3/C1*
Motor
Hp (kW)
Supply voltage
Number and size of
cable entries
1/2 - 2
(0.37 - 1.5)
1 x 200-240 V, 50/60 Hz
3 x 200-240 V, 60 Hz
3 x 440-480 V, 50/60 Hz
4 x NPT 1/2"
4 x NPT 1/2"
4 x NPT 1/2"
3
(2.2)
3 x 200-240 V, 60 Hz
3 x 440-480 V, 50/60 Hz
5 x NPT 1/2"
4 x NPT 1/2"
5
(4)
3 x 200-240 V, 60 Hz
3 x 440-480 V, 50/60 Hz
5 x NPT 1/2"
5 x NPT 1/2"
7 1/2
(5.5)
3 x 200-240 V, 60 Hz
3 x 440-480 V, 50/60 Hz
1 x NPT3/4" +
5 x NPT1/2"
5 x NPT 1/2"
10 - 15
(7.5 -11)
3 x 440-480 V, 50/60 Hz
1 x NPT3/4" +
5 x NPT1/2"
Terminal
Thread size
Maximum torque
[ft lb (Nm)]
L1, L2, L3, L, N
M4
1.3 (1.8)
NC, C1, C2, NO
M2.5
0.4 (0.5)
1-26 and A, Y, B
M2
0.4 (0.5)