This control mode requires either a factory-fitted or external
differential-pressure sensor or two external pressure sensors as
shown in the examples below:
Fig. 37
Constant differential pressure
8.1.5 Constant curve
The pump can be set to operate according to a constant curve,
like an uncontrolled pump. See fig. 38.
The desired speed can be set in % of maximum speed in the
range from 25 to 100 % (110 %).
Fig. 38
Constant curve
8.1.6
Analog inputs
Available inputs depending on the functional module fitted in the
pump:
To set up an analog input, make the settings below.
Function
The analog inputs can be set to these functions:
•
Not active
•
Feedback sensor
•
Ext. setpoint infl.
See section
•
Other function
.
Measured parameter
Select one of the parameters, i.e. the parameter to be measured
in the system by the sensor connected to the actual analog input.
Unit
Available measuring units:
Electrical signal
Select signal type (0.5 - 3.5 V, 0-5 V, 0-10 V, 0-20 mA or 4-20
mA).
Sensor range, min. value
Set the min. value of the connected sensor.
Sensor range, max. value
Set the max. value of the connected sensor.
8.1.7
Pt100/1000 inputs
Available inputs depending on the functional module fitted in the
pump:
Function
The Pt100/1000 inputs can be set to these functions:
•
Not active
•
Feedback sensor
•
Ext. setpoint infl.
See section
•
Other function
.
Measured parameter
Select one of the parameters, i.e. the parameter to be measured
in the system.
Examples
• Factory-fitted differential-pressure sensor.
• One external differential-pressure sensor.
• Two external pressure sensors.
TM
05
7
957
17
13
p
p
p
p
p
H
Q
Function (terminal)
FM 300
(advanced)
Analog input 1, setup
(4)
●
Analog input 2, setup
(7)
●
Analog input 3, setup
(14)
●
Parameter
Possible units
Pressure
bar, m, kPa, psi, ft
Pump flow
m
3
/h, l/s, yd
3
/h, gpm
Liquid temp.
°C, °F
Other parameter
%
Function (terminal)
FM 300
(advanced)
Pt100/1000 input 1, setup
(17 and 18)
●
Pt100/1000 input 2, setup
(18 and 19)
●