English (GB)
40
Setting range
• Pump speed
• number of pumps
• filling pressure
• maximum filling time
• warning or alarm + stop
• ramp time for the pressure build-up phase.
Setting via control panel
• Settings > Secondary functions > Stop function >
Soft pressure build-up.
1. Select and set:
• Speed
• Number of pumps
• Filling pressure
• Max. time.
2. Select: Warning / Alarm + stop.
3. Set: Ramp time.
4. Select: Enabled.
Factory setting
The function is disabled.
8.7.25 Emergency run (4.3.5)
Fig. 71
Emergency run
Description
This function is used in booster applications. When this function
has been enabled, the pumps will keep running regardless of
warnings or alarms. The pumps will run according to a setpoint
set specifically for this function.
Setting range
• Setting of digital input (
• Setting of digital output (
8.7.31 Digital outputs (4.3.9)
).
• Setting of setpoint for emergency run.
Setting via control panel
• Settings > Secondary functions > Stop function > Emergency
run > Go to setting of digital input.
1. Select digital input.
2. Select: Emergency run.
3.
x 2.
4. Select: Go to setting of digital output.
5. Select digital output.
6. Select: Emergency run.
7.
x 2.
8. Set: Setpoint, emergency run.
8.7.26 Digital inputs (4.3.7)
Fig. 72
Digital inputs
Description
It is possible to set the digital inputs of the CU 352. Each input,
except DI1, can be activated and related to a certain function.
As standard, the system has three digital inputs. If the system
incorporates an IO 351B module (option), the number of digital
inputs is 12.
All digital inputs are shown so that their physical position in the
system can be identified.
Example
DI1 (IO 351-41), [10]:
For further information on the connection of various digital inputs,
see the wiring diagram supplied with the control cabinet.
Setting range
Setting via control panel
• Settings > Secondary functions > Stop function > Digital
inputs.
Caution
In case of sensor fault, both main and standby
pumps will run at 100 % speed!
Note
When this function has been set as described above,
it can also be enabled via display
.
DI1:
Digital input No 1
(IO 351-41):
IO 351, GENIbus number 41
[10]:
Terminal No 10
Note
DI1 (CU 352) cannot be selected.