4
CONTENTS
Page
Delivery
General description
Applications
Function
Installation
Connections
Lifting station
Dimensions 6
Connection of inlet and discharge hoses
Electrical connection
Start-up
Checking the function
Maintenance and service
Cleaning the Conlift
Contaminated lifting station or components 11
Components 12
Service kit
Accessories
Fault finding chart
Technical data
10.1 Other technical data
Disposal
1. Delivery
The Grundfos Conlift is delivered in a cardboard box
containing:
• Conlift lifting station with built-in non-return valve
and supply cable with Schuko plug or a free cable
end
• Mounting kit in plastic bag
• Installation and operating instructions.
The mounting kit consists of (see pages 12 and 13):
• 5 metres of hose with internal/external diameter of
10/14 mm (pos. 51)
• 2 angular mounting brackets to counteract buoy-
ancy (pos. 52)
• 4 wood screws (pos. 53) and 4 rawlplugs
®
(pos. 54)
• 1 hose clamp for fastening the discharge hose to
the discharge stub (pos. 55)
• 4 mounting feet to be glued on (pos. 56)
• 1 strain-relief – for the use of external alarm/
potential-free contact (pos. 19)
• 2 sheet metal screws for the strain-relief (pos. 20).
Check that all components are OK.
2. General description
The Grundfos Conlift is a compact lifting station with
built-in non-return valve; it works automatically. The
Conlift is ready for installation.
2.1 Applications
The Conlift is designed for the pumping of conden-
sate from
• boilers
• air-conditioning systems
• cooling and refrigeration systems
• air dehumidifiers
• evaporators.
The Conlift is suitable for the pumping of condensate
which is collected below sewer level or which cannot
flow to the sewage system or drain of the building by
natural gravitation.
The Conlift can pump condensate with a pH value
equal to or above 2.7 from boilers with a heat output
of up to 200 kW.
This applies to boilers fired with
• gas
• liquid gas
• low-sulphur fuel oil according to DIN 51 603-1.
Note:
Where boilers are fired with the above fuels, but
• have a heat output above 200 kW,
• produce condensate with a pH value below 2.7,
and where boilers
• are fired with oils other than
low-sulphur fuel oil
,
the condensate from the boiler
must
be neutralised
before entering the sewage system/lifting station.
In case of deviations from the application conditions
stated above, local electricity regulations and stand-
ards must be observed.
In case of doubt, contact a qualified electrician.
Prior to installation, read these installation
and operating instructions. Installation and
operation must comply with local regula-
tions and accepted codes of good prac-
tice.
Condensates from boilers are aggressive.
They contain acid.
The Conlift must not be used for the trans-
fer of inflammable liquids.
The Conlift must not be installed in poten-
tially explosive environments.