background image

5

Eng

lish (

U

S)

7. Thread the tank/transducer manifold assembly to discharge 

tee as shown in fig. 7. Tighten wrench tight.

8. Tighten the cross fitting such that the transducer, plug and 

bushing(s) are positioned horizontally. Tighten wrench tight.

Fig. 7

Threading tank/transducer manifold assembly to
discharge tee

5.3 Attach the tank

1. Remove the plastic protective cover from over the tank 

threads. Confirm the O-ring is in place and thread the tank into 
the final port in the 1/2” NPT cross fitting opposite the
pressure transducer. Tank should now also be horizontal. 
Tighten until hand tight.

2. The tank is pre-charged from the factory to 50 psi (+/- 7 psi) 

and may need to be adjusted for optimum pump performance. 
Tank pre-charge pressure must be 0.7 x actual setpoint.
49 psi is the correct pre-charge setting for a 70 psi setpoint
(70 x 0.7 = 49).

6. Install the pump

1. Install the pump according to the CM and CME Installation and 

Operating Instructions with these additional steps:

– Wrap 3 to 4 turns of Teflon tape on the male threads of the 

suction size pipe nipple.

– Thread the suction sized pipe nipple directly in the pump 

inlet fitting.

– Thread the check valve onto the pipe nipple; tighten until 

wrench tight.

2. Connect the main power cable and pressure transducer cable 

to the motor terminal box according to the CME Installation 
and Operating Instructions supplied with the pump.

6.1 Set the pump parameters

Using an R100 remote programmer, set the following parameters:
• SENSOR TYPE: As per the label on the transducer (typically 

4-20 mA and range 0-87 psi (0-6 bar) or 0-145 psi (0-10 bar))

• STOP FUNCTION:Active
• CONTROL MODE:Controlled

6.2 Perform functional test

Start the pump and perform the following functional test including 

monitoring for leaks and watching for any obvious problems:

1. Reduce the setpoint to the second LED light from the bottom 

on the motor control panel by pressing the DOWN arrow as 
many times as necessary.

2. Slowly close the discharge line valve and observe that the 

motor reduces speed to compensate for the lower flow rate.

3. Fully close the discharge line valve to test the motor stop

function. (The motor should stop within approximately
2 minutes if there are no leaks).

Note: The stop function may not operate properly, if the
setpoint requires 90% to 100% of the motor maximum speed 
or if the diaphragm tank pre-pressure is not in the desired 
range

.

4. Fully open the discharge line valve and observe that the pump 

starts again.

5. The pump is ready for its normal operation now. Please see 

the CME Installation and Operating Instructions supplied with 
the pump for further instructions.

Fig. 8

Completed kit assembly

T

M

05 06

52 13

11

Note

Note

 If you purchased a complete CME-Plus from
the factory, the pressure transducer and R100 
settings are already installed

.

Thread tank/transducer
manifold assembly here

Note

Note

 Pump must be primed before functional test.

Warning

After setting your pump setpoint, be sure that 
you have not inadvertently set the pump to run on 

Max Curve

Min Curve

 or 

Stop

. See the CRE, 

CRIE...CME Installation and Operating
Instructions for more information.

T

M

05 0

659 1

41

1

Tank with O-ring

1/2" NPT cross fitting

1/2" to discharge
size bushing

Discharge
tee

1/2" NPT
plug

1/4" to 1/2"
NPT bushing

Transducer

1/2" NPT
pipe nipple

Discharge
nipple

Discharge
union

Discharge
pipe

CME Plus Kit Assembly I&O.book  Page 5  Thursday, April 7, 2011  4:41 PM

Содержание CME-Plus

Страница 1: ...GRUNDFOS INSTRUCTIONS CME Plus Kit assembly Installation and operating instructions ...

Страница 2: ...2 ...

Страница 3: ...ages and some jurisdictions do not allow limit actions on how long implied warranties may last Therefore the above limitations or exclusions may not apply to you This warranty gives you specific legal rights and you may also have other rights which vary from jurisdiction to jurisdiction 2 Symbols used in this document 3 General The Grundfos CME Plus system is for the pumping of clean thin and non ...

Страница 4: ... four ports of the cross fitting See fig 3 Fig 3 Threading plug into cross fitting 3 Thread the 1 4 to 1 2 NPT bushing into one of the ports next to the plug from Step 2 in the cross fitting This will be opposite of where the tank will be positioned See fig 4 Tighten until wrench tight Fig 4 Threading bushing into cross fitting next to plug 4 Thread the pressure transducer into the 1 4 NPT port of...

Страница 5: ...bar or 0 145 psi 0 10 bar STOP FUNCTION Active CONTROL MODE Controlled 6 2 Perform functional test Start the pump and perform the following functional test including monitoring for leaks and watching for any obvious problems 1 Reduce the setpoint to the second LED light from the bottom on the motor control panel by pressing the DOWN arrow as many times as necessary 2 Slowly close the discharge lin...

Страница 6: ...6 ...

Страница 7: ...27 3400 Telefax 1 913 227 3500 Canada GRUNDFOS Canada Inc 2941 Brighton Road Oakville Ontario L6H 6C9 Phone 1 905 829 9533 Telefax 1 905 829 9512 México Bombas GRUNDFOS de México S A de C V Boulevard TLC No 15 Parque Industrial Stiva Aeropuerto Apodaca N L C P 66600 Phone 52 81 8144 4000 Telefax 52 81 8144 4010 ...

Страница 8: ...akes it possible Innovation is the essence The name Grundfos the Grundfos logo and the payoff Be Think Innovate are registrated trademarks owned by Grundfos Management A S or Grundfos A S Denmark All rights reserved worldwide L CM TL 004 0411 US 2011 Grundfos Pumps Corp ...

Отзывы: