6.4 The motor-protective circuit breaker has not tripped out, but the pump is inadvertently out of operation.
Cause
Remedy
Supply failure.
•
Switch on the switch.
•
Check cables and cable connections for defects and loose
connections.
Fuses are blown.
•
Check cables and cable connections for defects, and replace the
fuses.
Control-current circuit defective.
•
Repair or replace the control-current circuit.
The pump is mechanically blocked.
•
Switch off the electricity supply, and clean or repair the pump.
6.5 The pump performance is unstable.
Cause
Remedy
Pump inlet pressure too low.
•
Check the inlet conditions of the pump.
Inlet pipe is partly blocked by impurities.
•
Remove and clean the inlet pipe.
Leakage in inlet pipe.
•
Remove and repair the inlet pipe.
Air in inlet pipe or pump.
•
Vent the inlet pipe/pump.
•
Check the inlet conditions of the pump.
6.6 The pump runs, but gives no water.
Cause
Remedy
Pump inlet pressure too low.
•
Check the inlet conditions of the pump.
Inlet pipe partly blocked by impurities.
•
Remove and clean the inlet pipe.
The foot or non-return valve is stuck in its closed position.
•
Remove and clean, repair or replace the valve.
Leakage in inlet pipe.
•
Remove and repair the inlet pipe.
Air in inlet pipe or pump.
•
Vent the inlet pipe/pump.
•
Check the inlet conditions of the pump.
6.7 The pump runs backwards when switched off.
Cause
Remedy
Leakage in inlet pipe.
•
Remove and repair the inlet pipe.
Foot or non-return valve defective.
•
Remove and clean, repair or replace the valve.
The foot valve is stuck in completely or partly open position.
•
Remove and clean, repair or replace the valve.
6.8 The pump runs with reduced performance.
Cause
Remedy
Wrong direction of rotation.
•
Three-phase pumps only:
Switch off the electricity supply with the external circuit breaker and
interchange two phases in the pump terminal box.
It is possible to check the direction of rotation by means of the
installation indicator.
Black: The direction of rotation is correct.
White: The direction of rotation is incorrect.
Pump inlet pressure too low.
•
Check the inlet conditions of the pump.
Inlet pipe is partly blocked by impurities.
•
Remove and clean the inlet pipe.
Leakage in inlet pipe.
•
Remove and repair the inlet pipe.
Air in inlet pipe or pump.
•
Vent the inlet pipe/pump.
•
Check the inlet conditions of the pump.
21
English (GB)
Содержание CM series
Страница 1: ...CM CME Service instructions GRUNDFOS INSTRUCTIONS ...
Страница 2: ......
Страница 3: ...CM CME English GB Service instructions 4 3 Table of contents ...
Страница 22: ...7 Drawings 7 1 CM 1 3 5 TM043588 CM 1 3 5 stainless steel 22 English GB ...
Страница 23: ...TM043591 CM 1 3 5 cast iron 23 English GB ...
Страница 24: ...7 2 CM 10 15 25 TM043828 CM 10 15 25 stainless steel 24 English GB ...
Страница 25: ...TM043829 CM 10 15 25 cast iron 25 English GB ...