Object
Description
Custom device
instance enable
If ticked, CIM 500 is configured to use a BACnet custom device instance number.
Foreign Device
If ticked, CIM 500 is configured as a foreign device.
IP Address
Enter the foreign IP address.
UDP Port
Enter the foreign UDP port number. The default number is 47808.
Re-Register Time
Enter the time period in seconds during which the foreign device must re-register on the
BACnet network.
Network Watchdog
Timer
If enabled and BACnet communication stops, the watchdog timer restarts the internal network
module if it times out.
You can configure the time-out from 2 minutes to 1440 minutes in steps of 1 minute.
A value of 1 is illegal and a value of 0 disables the watchdog.
288