14.4 ALPHA SOLAR 25-145 180 (N)

0.0

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

2.2

2.4

2.6

2.8

Q [m³/h]

0

2

4

6

8

10

12

14

[m]

H

0

20

40

60

80

100

120

[kPa]

p

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

Q [l/s]

0.0

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

2.2

2.4

2.6

2.8

Q [m³/h]

0

10

20

30

40

50

60

[W]

P1

TM063652

ALPHA SOLAR XX-XX: EEI ≤ 0.20 Part 3
ALPHA SOLAR XX-XX N:  EEI ≤ 0.23 Part 3
P

L,avg

 ≤ 25 W

Setting

Max. head 

nom

Max. P

1nom

Curve 1

8.5 m

45 W

Curve 2

10.5 m

52 W

Curve 3

14.5 m

60 W

Settings

PWM C

CC

1

3

Electrical data, 1 x 230 V, +10/-15 %, 50/60 Hz

Speed

P

1

 [W]

1/1

 [A]

Min.

2

*

0.04

Max.

60

0.58

*

Only in minimum PWM speed operation

 

Dimensions

B1

B2

H3

H2

H1

L1

L3

TM066493

TM065636

Pump type

Dimensions [mm]

Connections

Weight

[kg]

L1

L3

B1

B2

H1

H2

H3

ALPHA SOLAR 25-145
180

180

90

64

46

25

102

127

G 1 1/2

2.0

ALPHA SOLAR 25-145
180 N

180

90

64

45

27

102

129

G 1 1/2

2.5

22

English (GB)

Содержание ALPHA SOLAR B

Страница 1: ...ALPHA SOLAR Model B Installation and operating instructions GRUNDFOS INSTRUCTIONS ...

Страница 2: ......

Страница 3: ...rvatski HR Montažne i pogonske upute 200 Magyar HU Telepítési és üzemeltetési utasítás 219 Italiano IT Istruzioni di installazione e funzionamento 238 Lietuviškai LT Įrengimo ir naudojimo instrukcija 258 Latviešu LV Uzstādīšanas un ekspluatācijas instrukcija 277 Nederlands NL Installatie en bedieningsinstructies 296 Polski PL Instrukcja montażu i eksploatacji 316 Português PT Instruções de instala...

Страница 4: ...раїнська UA Інструкції з монтажу та експлуатації 470 Macedonian MK Упатства за монтирање и ракување 490 Norsk NO Installasjons og driftsinstruksjoner 510 Íslenska Uppsetningar og notkunarleiðbeiningar 529 4 ALPHA SOLAR Table of contents ...

Страница 5: ...y or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved Children shall not play with the appliance Cleaning and user maintenance shall not be made by children without supervision Read this document before you install the product Installation and operation must c...

Страница 6: ...such as acids and seawater The product is suitable for the following Clean thin non aggressive and non explosive liquids not containing solid particles or fibres In heating systems the water must meet the requirements of accepted standards on water quality in heating systems for example the German standard VDI 2035 The pH must be between 8 2 and 9 5 The minimum value depends on the water hardness ...

Страница 7: ...PHA SOLAR Pump type 15 Nominal diameter DN of inlet and outlet ports mm 75 Maximum head MPa Cast iron pump housing N Stainless steel pump housing 130 Port to port length mm 3 Receiving the product 3 1 Inspecting the product CAUTION Crushing of feet Minor or moderate personal injury Wear safety shoes when opening the box and handling the product On receipt of the product do the following 1 Check th...

Страница 8: ...sitions 5 3 Control box positions DANGER Electric shock Death or serious personal injury Switch off the power supply before you start any work on the product Make sure that the power supply cannot be switched on accidentally CAUTION Hot surface Minor or moderate personal injury The pump housing may be hot due to the pumped liquid being scalding hot Close the isolating valves on both sides of the p...

Страница 9: ...d position TM076961 4 Refit the screws on the pump head TM076962 5 4 Insulation of the pump housing TM076978 Insulating the pump housing You can reduce the heat loss from the pump by insulating the pump housing with insulating shells which can be ordered as an accessory Do not insulate the control box or cover the operating panel Related information 13 2 Insulating shells 9 English GB ...

Страница 10: ...rseal power connector L PE N IN REF OUT TM069076 Mini superseal plug 6 1 Control signal connection If you do not need the signal connection cover it with a blanking plug You can control the pump with a low voltage PWM pulse width modulation signal The PWM signal is a method for generating an analog signal using a digital source To enable the external control mode PWM profile C you need a signal ca...

Страница 11: ...as been switched on and the pump is running TM076965 7 3 Venting the pump TM077002 Venting the pump Small air pockets trapped inside the pump may cause noise when starting up the pump However because the pump is self venting through the system the noise ceases over a period of time To speed up the venting process do as follows 1 Set the pump to speed III using the button on the operating panel 2 L...

Страница 12: ...erformance follows the selected performance curve I II or III See the figure below where curve II has been selected Q H TM068822 Constant curve speed curve The selection of the constant curve setting depends on the characteristics of the solar system in question 8 3 Control signal The pump can be controlled via a digital low voltage pulse width modulation PWM signal The square wave PWM signal is d...

Страница 13: ... overheating of the solar thermal system Max 10 20 30 40 50 60 70 80 90 100 TM051575 PWM input profile C solar Axis Value X PWM input signal Y Speed PWM input signal Pump status 5 Standby mode off 5 8 Hysteresis area on off 8 15 Minimum speed 15 90 Variable speed from minimum to maximum speed 90 100 Maximum speed 8 3 3 PWM feedback signal The PWM feedback signal offers pump information like in bus...

Страница 14: ...he LEDs will indicate the chosen control mode See the table below A cycle is four button presses Display Control mode Constant curve 1 Constant curve 2 Constant curve 3 PWM profile C Signal off 1 green flash per second Signal on 12 green flashes per second The pump has been factory set to constant curve 3 9 1 Connection of the PWM input signal To enable the external control mode PWM profile C you ...

Страница 15: ...smantling the product 1 Switch off the power supply 2 Pull out the superseal power cable 3 Close the two isolating valves on both sides of the pump 4 Loosen the fittings 5 Remove the pump from the system 10 2 Deblocking the shaft If the pump is blocked it is necessary to deblock the shaft The pump deblocking device is accessible from the front of the pump without having to demount the control box ...

Страница 16: ...green to red When an alarm is active the LEDs indicate the alarm type as defined below When there is no active alarm anymore the operating panel switches back to operating status and the first LED switches from red to green If multiple alarms are active at the same time the LEDs only show the error with the highest priority The priority is defined by the sequence of the table Display Status Soluti...

Страница 17: ...upply voltage 1 x 230 V 15 10 50 60 Hz PE Insulation class F EN 60335 1 Standby power consumption 1 W Inrush current 4 A Minimum switching time power on off No specific requirements Miscellaneous data Motor protection The pump requires no external motor protection Enclosure class IPX4D with drain holes Temperature class TF TF110 at 70 C ambient temperature Specific EEI values ALPHA Solar 25 145 18...

Страница 18: ...x N 529977 529978 529979 32 xx G 2 G threads have a cylindrical form in accordance with the EN ISO 228 1 standard and are not sealing the thread It requires a flat gasket You can only screw male G threads cylindrical into female G threads The G threads are standard thread on the pump housing R threads are tapered external threads in accordance with the EN 10226 2 standard Rc or Rp threads are inte...

Страница 19: ...ut and the signal reference Connect the cable to the control box by a mini superseal plug The optional signal cable is available as an accessory The cable length must not exceed 3 metres TM064414 Mini superseal plug Conductor Colour Signal input Brown Signal reference Blue Signal output Black TM067298 Product description Length mm Product number Installer plug 99439948 TM076722 Product description...

Страница 20: ...ow average values and must not be used as guarantee curves If a specific minimum performance is required individual measurements must be made The curves apply to a kinematic viscosity of 0 474 mm2 s 0 474 cSt The conversion between head H m and pressure p kPa has been made for water with a density of 1000 kg m3 For liquids with other densities for example hot water the outlet pressure is proportio...

Страница 21: ...vg 20 W Setting Max head nom Max P1nom Curve 1 5 5 m 28 W Curve 2 6 5 m 35 W Curve 3 7 5 m 45 W Settings PWM C CC 1 3 Electrical data 1 x 230 V 10 15 50 60 Hz Speed P1 W I 1 1 A Min 2 0 04 Max 45 0 48 Only in minimum PWM speed operation Dimensions B1 B2 H3 H2 H1 L1 L3 TM066493 TM065636 Pump type Dimensions mm Connections Weight kg L1 L3 B1 B2 H1 H2 H3 ALPHA SOLAR 15 75 130 130 90 64 45 36 92 128 G...

Страница 22: ...PHA SOLAR XX XX N EEI 0 23 Part 3 PL avg 25 W Setting Max head nom Max P1nom Curve 1 8 5 m 45 W Curve 2 10 5 m 52 W Curve 3 14 5 m 60 W Settings PWM C CC 1 3 Electrical data 1 x 230 V 10 15 50 60 Hz Speed P1 W I 1 1 A Min 2 0 04 Max 60 0 58 Only in minimum PWM speed operation Dimensions B1 B2 H3 H2 H1 L1 L3 TM066493 TM065636 Pump type Dimensions mm Connections Weight kg L1 L3 B1 B2 H1 H2 H3 ALPHA ...

Страница 23: ...he crossed out wheelie bin symbol on a product means that it must be disposed of separately from household waste When a product marked with this symbol reaches its end of life take it to a collection point designated by the local waste disposal authorities The separate collection and recycling of such products will help protect the environment and human health See also end of life information at w...

Страница 24: ...a Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam ku 135 916 Seoul Korea Tel 82 2 5317 600 Fax 82 2 5633 725 Latvia SIA GRUNDFOS Pumps Latvia Deglava biznesa centrs Augusta Deglava ielā 60 LV 1035 Rīga Tel 371 714 9640 7 149 641 Fax 371 914 9646 Lithuania GRUNDFOS Pumps UAB Smolensko g 6 LT 03201 Vilnius Tel 370 52 395 430 Fax 370 52 395 431 Malaysia GRUNDFOS Pumps Sdn Bhd 7 Jalan Peguam U1 ...

Страница 25: ...ademarks displayed in this material including but not limited to Grundfos the Grundfos logo and be think innovate are registered trademarks owned by The Grundfos Group All rights reserved 2020 Grundfos Holding A S all rights reserved ...

Отзывы: