WARNING

Make all electrical connections (e.g. conductor termination, fuses, 
PE connection, etc.) in accordance with prevailing regulations. 
When working with the inverter powered on, adhere to all 
prevailing safety regulations to minimize risk of accidents.
The inverter may only be operated with PV generators (modules and 
cabling) with protective insulation. Do not connect any source other 
than PV modules to the inverter.
Systems with inverters typically require additional control (e.g., 
switches, disconnects) or protective devices (e.g., fuse, circuit 
breaker) depending upon the prevailing safety rules.

CAUTION

House

grid:

Public 
grid:

Energy flows into the house grid. The consumers connected, 
for example, household devices or lighting, consume the 
energy. The energy left over is fed into the public grid. When 
the UE series inverters do not generate any energy, e.g., at 
night, the consumers which are connected are supplied by the 
public grid. The energy displayed on the LCD of inverter is for 
reference only. When energy is fed into the public grid, the 
energy meter spins backwards.

Energy is fed directly into the public grid. The  UE series 
inverters need install a separate energy meter. The energy 
produced is compensated at a rate depending on the electric 
power company.

2.5 Operation Warnings

WARNING

Ensure all covers and doors are closed and secure during operation.
Although designed to meet all safety requirements, some parts and 
surfaces of Inverter are still hot during operation. To reduce the risk 
of injury, do not touch the heat sink at the back of the PV-Inverter or 
nearby surfaces while Inverter is operating.

Incorrect sizing of the PV plant may result in voltages being present 
which could destroy the inverter. 

     

       Turn the rotary switch of the DC Disconnect to the Off position ;    
        immediately.
       Contact installer.

The Growatt  inverter is to be used solely to feed solar energy 
converted photovoltaically into the public grid. The inverter is 
suitable for mounting indoors and outdoors.
You can use the AC current generated as follows:

5

6

2.2 Safety Precautions

The TL3-S series Inverter is designed and tested according to Internalational safety 
requirements; however, certain safety precautions must be observed when installing 
and operating this inverter. Read and follow all instructions, cautions and warnings 
in this installation manual. If questions arise, please contact our technical services at 
+86 (0)755 2747 1942.

2.3 Assembly Warnings

CAUTION

WARNING

The inverter may only be operated with a permanent connection to 
the public power grid. The inverter is not intended for mobile use. 
Any other or additional use is not considered the intended use. The 
manufacturer/supplier is not liable for damage caused by such 
unintended use. Damage caused by such unintended use is at the 
sole risk of the operator.
Prior to installation, inspect the unit to ensure absence of any 
transport or handling damage, which could affect insulation 
integrity or safety clearances; failure to do so could result in safety 
hazards.
Unauthorized removal of necessary protections, improper use, 
incorrect installation and operation may lead to serious safety, 
shock hazards or equipment damage.
In order to minimize the potential of a shock hazard due to 
hazardous voltages, cover the entire solar array with dark material 
prior to connecting the array to any equipment.

Grounding the PV modules: Comply with the local requirements for 
grounding the PV modules and the PV generator.

We recommend connecting the generator frame and other 
electrically conductive surfaces in a manner which ensures 
continuous conduction and ground these in order to have optimal 
protection of the system and personnel.

2.4 Electrical Connection Warnings

DANGER

Some components in the inverter are live. Touching live components 
can result in serious injury or death.

Danger to life due to high voltages in the inverter
      All work on the inverter may be carried out by qualified 
personnel only.

     The appliance is not to be used by children or persons with         
reduced physical, sensory or mental capabilities, or lack of 
experience and knowledge, unless they have been given supervision 
or instruction.
Children are forbidden to play around the  inverter. 

Содержание 10000TL3-S

Страница 1: ...L3 S Growatt 5000TL3 S Growatt 4000TL3 S Growatt 3000TL3 S Growatt 11000TL3 S Growatt 13000TL3 S Growatt 15000TL3 S Installation Operation Manual Shenzhen Growatt New Energy Technology CO LTD No 28 Gu...

Страница 2: ...3 4 Transportation Unpacking Index 1 2 3 4 2 2 Safety Precautions Installation 5 5 1 Safety instruction 5 2 Selecting the Installation Location 2 3 Assembly Warnings 2 4 Electrical Connection Warning...

Страница 3: ...the Inverter 8 2 Checking the DC Disconnect Trouble shooting 9 10 1 Dismantling the Inverter 10 2 Packing the Inverter Decommissioning 10 10 3 Disposing of the Inverter Specification 11 Certificates...

Страница 4: ...ch if not avoided could result in death or serious injury WARNING indicates a hazardous situation which if not avoided could result in death or serious injury NOTICE indicates a situation which if not...

Страница 5: ...r coupling capacity does not exceed 2 2uF During feed in operation a leakage current flows from the cells to earth the size of which depends on the manner in which the PV modules are installed e g foi...

Страница 6: ...AC current generated as follows 5 6 2 2 Safety Precautions The TL3 S series Inverter is designed and tested according to Internalational safety requirements however certain safety precautions must be...

Страница 7: ...ions comply with all corresponding safety symbols and markings present on the unit and in this manual In special cases there may still be interference for the specified application area despite mainta...

Страница 8: ...f there are lots of inverters need to be stored the maximum layers for original carton is four After long term storage local installer or service department of manufacturer should perform a comprehens...

Страница 9: ...it values e g when sensitive equipment is located at the setup location or when the setup location is near radio or television receivers In this case the operator is obliged to take proper action to r...

Страница 10: ...c panel is exposed to light it generates a DC voltage When connected to this equipment a photovoltaic panel will charge the DC link capacitors Energy stored in this equipment s DC link capacitors pres...

Страница 11: ...me installation countries a second protective conductor is required to prevent a touch current in the event of a malfunction in the original protective conductor For installation countries falling wit...

Страница 12: ...re to the sunlight may cause additional internal heating which will cause power derating More than one inverter need to be installed the dimensions below should be considered Fig5 6 Fig5 7 Fig 5 8 Rec...

Страница 13: ...grid voltage and frequency Voltage 400Vac Frequency 50Hz 60Hz 3 Phase Open the breaker between the PV inverter and utility Specification of AC breaker Cable requirements 1 The AC side terminals of th...

Страница 14: ...he inverter To reduce the risk of electric shock avoid touching the live components and treat the terminals carefully Information Please use the same brand male and female PV connectors Under any cond...

Страница 15: ...e maximum string currents are varying from different inverter types Model Max current 7000TL3 S 3000 6000TL3 S 8000 9000TL3 S 10000 11000TL3 S 12000TL3 12000 15000TL3 S 11 5A 11 5A 11A 11A 11 5A 11 5A...

Страница 16: ...es The inverter starts up automatically when DC power from the PV panel is sufficient Fault Mode The internal intelligent controller can continuously monitor and adjust the system status If inverter f...

Страница 17: ...afety standard must be selected by the DIP switch The DIP switch is composed of four digit binary number PINS The different combination of the four PINS can represent different inverter s model which...

Страница 18: ...4 2 3 1 ON 5 4 2 3 1 ON 5 4 2 3 1 ON 5 4 2 3 1 ON 5 4 2 3 1 ON 5 AS4777_Newzealand GT1XXXXXX0 Reserved GT1XXXXXX1 India GT1XXXXXX2 EN50438_Demark GT1XXXXXX3 EN50438_Sweden GT1XXXXXX4 EN50438_Norway G...

Страница 19: ...l 2000 Kwh AC Volt A B C 230V 230V 230V Set Language Set Language English Once Once Once Double Fig6 3 Overall display interface Power on display After inverter restarts the background light will last...

Страница 20: ...Com Address 001 Set Language Set Date Time AC V Control Disable Enable Once Once Once Setting Three Set Language English Double AC V Control Disable Double Double Date 2012 04 05 Time 14 20 38 Settin...

Страница 21: ...ime Date 2013 05 06 Time 14 20 38 Date 2013 05 06 Time 14 20 38 Date 2013 05 06 Time 15 20 38 Date 2013 05 06 Time 15 20 38 Date 2013 05 06 Time 15 21 38 Set OK Double Once Double Once Double Once Dou...

Страница 22: ...ication systems You can update firmware via RS232 or Rs485 The connecting diagram as follow Active power control with a ripple control signal receiver Through RS485 interface RS485 232 RS232 converter...

Страница 23: ...t be more than 32 6 5 3 RS485 cable connection Rs485 cable connection Pin1 TR B Pin2 Shielding layer or no connection Definitions of RS485 PLUG standard as follows Pin1 TR B Pin2 Shielding layer or no...

Страница 24: ...recommended as STP FTP ASTP 4 Plug in two terminals Cover the fix board Information Tighten 4 pcs screws first then tighten cable gland 5 Tighten 4pcs screws and cable gland Note 1 As to the connecti...

Страница 25: ...off the DC switch of the inverter 3 Check the inverter operating status 4 Until the display of LCD goes out the inverter is shut down Once the output power is derating because of too high warming some...

Страница 26: ...acing inverter Error message Description Suggestion Error 124 No AC connection Check AC wiring Check the status of AC breaker PV Isolation Low Insulation problem 1 Check if panel enclosure ground prop...

Страница 27: ...oblem still exist Contact Growatt Warning 109 Warning 108 PV 1 or PV2 Circuit short PV 1 or PV2 boost broken Check the PV panel polarity Restart the inverter If the warning still exist please contact...

Страница 28: ...unit and where applicable any accessories are disposed of in a proper manner 11 Specification 11 1 Specification of TL3 S Model 3000TL3 S 4000TL3 S 6000TL3 S 5000TL3 S Specification Input data Max DC...

Страница 29: ...wer factor at rated power 1 1 1 1 Adjustable displacement power factor THDi Full load THDv 1 0 8leading 0 8laging AC grid connection type 3 3 3 3 3W N PE 3W N PE 3W N PE 3W N PE Protection devices DC...

Страница 30: ...current 11 7A 13 3A 15A Rated AC output power 7kW 8kW 9kW Max AC apparent power 7 7kVA 8 8kVA 9 9kVA 33A 33A 33A 16A 20A 25A 310 476V 310 476V 310 476V 2 1 1 2 1 1 Efficiency Max efficiency 98 3 98 3...

Страница 31: ...age 160V 160V 160V PV voltage range 160V 1000V 160V 1000V 160V 1000V MPP voltage range DC nominal voltage 200V 1000V 600V Max PV Isc 16A 16A 16A 16A 16A 16A Number of independent MPP trackers strings...

Страница 32: ...monitoring unit yes yes yes General Data Dimensions W H D in mm Weight Operating temperature range 25 C 60 C 13 F 140 F With derating above 45 C 113 F Noise emission typical 35 dB A 480 448 200 22kg 2...

Страница 33: ...current 19A 20 6A 23 8A Rated AC output power 12kW 13kW 15kW Max AC apparent power 13 2kVA 14 3kVA 16 5kVA 44A 44A 44A 25A 32A 32A 310 476V 310 476V 310 476V 2 2 1 2 2 1 Efficiency Max efficiency 98 3...

Страница 34: ...tion night 0 5 W 11 2 DC connector info DC connector Specification 11 3 Torque Values Enclosure lid screws 0 7Nm 6 2 1bf in Shell and RS232 screws 0 7Nm 6 2 1bf in AC terminal 0 6Nm 5 2 1bf in M6 sock...

Страница 35: ...or your dealer Name Description Communication interface Wi Fi Communication interface Shine WebBox Communication data logger Shine Vision receiver Communication data logger receiver Shine Vision emitt...

Страница 36: ...14 Contact If you have technical problems concerning our products contact your installer or manufacturer During inquiring please provide below information 1 Inverter type 2 Modules information 3 Commu...

Страница 37: ...TL3 S Growatt 7000TL3 S Growatt 11000TL3 S Growatt 13000TL3 S Growatt 15000TL3 S Installation Operation Manual Shenzhen Growatt New Energy Technology CO LTD No 28 Guangming Road Longteng Community Shi...

Страница 38: ...3 4 Transportation Unpacking Index 1 2 3 4 2 2 Safety Precautions Installation 5 5 1 Safety instruction 5 2 Selecting the Installation Location 2 3 Assembly Warnings 2 4 Electrical Connection Warning...

Страница 39: ...the Inverter 8 2 Checking the DC Disconnect Trouble shooting 9 10 1 Dismantling the Inverter 10 2 Packing the Inverter Decommissioning 10 10 3 Disposing of the Inverter Specification 11 Certificates...

Страница 40: ...indicates a hazardous situation which if not avoided could result in death or serious injury WARNING indicates a hazardous situation which if not avoided could result in death or serious injury NOTIC...

Страница 41: ...r coupling capacity does not exceed 2 2uF During feed in operation a leakage current flows from the cells to earth the size of which depends on the manner in which the PV modules are installed e g foi...

Страница 42: ...AC current generated as follows 5 6 2 2 Safety Precautions The TL3 S series Inverter is designed and tested according to Internalational safety requirements however certain safety precautions must be...

Страница 43: ...ply with all corresponding safety symbols and markings present on the unit and in this manual In special cases there may still be interference for the specified application area despite maintaining st...

Страница 44: ...ty should be always between 0 and 95 If there are lots of inverters need to be stored the maximum layers for original carton is four After long term storage local installer or service department of ma...

Страница 45: ...imit values e g when sensitive equipment is located at the setup location or when the setup location is near radio or television receivers In this case the operator is obliged to take proper action to...

Страница 46: ...c panel is exposed to light it generates a DC voltage When connected to this equipment a photovoltaic panel will charge the DC link capacitors Energy stored in this equipment s DC link capacitors pres...

Страница 47: ...you need to hang on the inverter During the process please maintain the balance of the TL3 S Hang the inverter on the expansion bolt After confirming the inverter is stuck on expansion bolt fasten fo...

Страница 48: ...re to the sunlight may cause additional internal heating which will cause power derating More than one inverter need to be installed the dimensions below should be considered Fig5 6 Fig5 7 Fig 5 8 Rec...

Страница 49: ...ly disconnected under load Measure the public grid voltage and frequency Voltage 400Vac Frequency 50Hz 60Hz 3 Phase Open the breaker between the PV inverter and utility Specification of AC breaker Cab...

Страница 50: ...he inverter To reduce the risk of electric shock avoid touching the live components and treat the terminals carefully Information Please use the same brand male and female PV connectors Under any cond...

Страница 51: ...nverter 4 The maximum string currents are varying from different inverter types Model Max current 7000TL3 S 8000 9000TL3 S 10000 11000TL3 S 12000TL3 12000 15000TL3 S 11 5A 11 5A 11 5A 11 5A 13A 13A 11...

Страница 52: ...nal system Notes The inverter starts up automatically when DC power from the PV panel is sufficient Fault Mode The internal intelligent controller can continuously monitor and adjust the system status...

Страница 53: ...afety standard must be selected by the DIP switch The DIP switch is composed of four digit binary number PINS The different combination of the four PINS can represent different inverter s model which...

Страница 54: ...4 2 3 1 ON 5 4 2 3 1 ON 5 4 2 3 1 ON 5 4 2 3 1 ON 5 4 2 3 1 ON 5 AS4777_Newzealand GT1XXXXXX0 Reserved GT1XXXXXX1 India GT1XXXXXX2 EN50438_Demark GT1XXXXXX3 EN50438_Sweden GT1XXXXXX4 EN50438_Norway G...

Страница 55: ...l 2000 Kwh AC Volt A B C 230V 230V 230V Set Language Set Language English Once Once Once Double Fig6 3 Overall display interface Power on display After inverter restarts the background light will last...

Страница 56: ...Com Address 001 Set Language Set Date Time AC V Control Disable Enable Once Once Once Setting Three Set Language English Double AC V Control Disable Double Double Date 2012 04 05 Time 14 20 38 Settin...

Страница 57: ...ime Date 2013 05 06 Time 14 20 38 Date 2013 05 06 Time 14 20 38 Date 2013 05 06 Time 15 20 38 Date 2013 05 06 Time 15 20 38 Date 2013 05 06 Time 15 21 38 Set OK Double Once Double Once Double Once Dou...

Страница 58: ...ication systems You can update firmware via RS232 or Rs485 The connecting diagram as follow Active power control with a ripple control signal receiver Through RS485 interface RS485 232 RS232 converter...

Страница 59: ...RS485 cable connection Rs485 cable connection Pin1 TR B Pin2 Shielding layer or no connection Definitions of RS485 PLUG standard as follows Pin1 TR B Pin2 Shielding layer or no connection Pin3 TR A P...

Страница 60: ...recommended as STP FTP ASTP 4 Plug in two terminals Cover the fix board Information Tighten 4 pcs screws first then tighten cable gland 5 Tighten 4pcs screws and cable gland Note 1 As to the connecti...

Страница 61: ...off the DC switch of the inverter 3 Check the inverter operating status 4 Until the display of LCD goes out the inverter is shut down Once the output power is derating because of too high warming some...

Страница 62: ...acing inverter Error message Description Suggestion Error 124 No AC connection Check AC wiring Check the status of AC breaker PV Isolation Low Insulation problem 1 Check if panel enclosure ground prop...

Страница 63: ...oblem still exist Contact Growatt Warning 109 Warning 108 PV 1 or PV2 Circuit short PV 1 or PV2 boost broken Check the PV panel polarity Restart the inverter If the warning still exist please contact...

Страница 64: ...he installation site at that time Ensure that the old unit and where applicable any accessories are disposed of in a proper manner 11 Specification 11 1 Specification of TL3 S Model 7000TL3 S 8000TL3...

Страница 65: ...ency 99 5 99 5 Power factor at rated power 1 1 1 Adjustable displacement power factor THDi Full load THDv 1 0 8leading 0 8laging AC grid connection type 3 3 3 3W N PE 3W N PE 3W N PE Protection device...

Страница 66: ...x output current 16 7A 18 3A 19A Rated AC output power 10kW 11kW 12kW Max AC apparent power 11kVA 12 1kVA 13 2kVA 33A 33A 44A 25A 25A 25A 184 300V 184 300V 184 275V Efficiency Max efficiency 98 3 98 3...

Страница 67: ...Voltage 160V 160V 160V PV voltage range 160V 1000V 160V 1000V 160V 1000V MPP voltage range DC nominal voltage 200V 1000V 600V Max PV Isc 16A 16A 16A 16A 16A 16A Number of independent MPP trackers str...

Страница 68: ...ated all pole sensitive leakage current monitoring unit yes yes yes General Data Dimensions W H D in mm Weight Operating temperature range 25 C 60 C 13 F 140 F With derating above 45 C 113 F Noise emi...

Страница 69: ...ture range 40 to 90 Strip length 7 0mm 9 32 Cable jacket diameter 4 5 to 7 8mm 3 16 to 5 16 Rated current at 90 Additional ground screws 2Nm 181bf in 11 4 Spare Parts and Accessories In the following...

Страница 70: ...0438 G83 G59 CE IEC62109 NB T32004 2013 G59 14 Contact If you have technical problems concerning our products contact your installer or manufacturer During inquiring please provide below information 1...

Отзывы: