Page 28 / 146
00BNO9061-L
VARMAX -
Installation, Use and Maintenance
Height of
fl
ue-gas duct H
in linear metres (lm)
(operating at 50/30°C)
ø
connection
150 mm
180 mm
200 mm
ø
duct
180 mm
200 mm
250 mm
250 mm
300 mm
Type of gas
G20
G31
G20 G31
G20
G31
G20 G31
G20 G31
MODELS
120
2
to
52
--
--
3
to
39
--
--
--
--
--
--
140
7
to
39
--
3
to
94 4
to
38
--
--
--
--
--
--
180
--
--
10
to
29
--
1
to
100 4
to
73
--
--
--
--
225
--
--
--
--
1
to
100 3
to
65
--
--
--
--
275
--
--
--
--
--
--
4
to
99 4
to
61
--
--
320
--
--
--
--
--
--
5
to
81 6
to
53
--
--
390
--
--
--
--
--
--
--
--
2
to
100
--
450
--
--
--
--
--
--
--
--
2
to
100
--
!
IMPORTANT:
The above values are provided for information purposes only. It is
important to check them with a calculation.
!
IMPORTANT:
The weight of
fl
ue-gas ducts must not be supported by the part
connecting to the boiler.
4.10.2. Connection to a B23P chimney
Type B23P connection:
Air coming from the boiler premises, extraction of gases through the roof via
a pressurised duct.
!
IMPORTANT:
For the B23P type connection, it is MANDATORY to use ducts which
have pressurised duct certi
fi
cation, such as CONDENSOR (Poujoulat)
or rigid or
fl
exible CHEMILUX CONDENSATION (Ubbink).
!
IMPORTANT:
The duct extracting combustion products must be sized using the
parameters provided in the table in paragraph 3.3.
Depending on the duct's actual con
fi
guration, a calculation is
necessary to check that the pressures at the boiler outlet do not
exceed the maximum normative values authorised (200 Pa).
Values corresponding to the 50/30°C regime are to be used for this
calculation.
!
WARNING:
Check that there are top and bottom ventilations in the boiler premises,
that they comply with applicable regulations and that they are not
obstructed.