U0594061-C
Page 20 / 82
CORFIRST / CORSUN 2 / CORFLOW
EN
5.3.2. Safety valves:
The safety valves are fitted to the tank inlet using a T (see diagram below).
SAFETY UNIT
SAFETY VALVE
On cold water inlet only
On tank inlet
1 single G 1¨ unit
1¼¨ kit with 2 G 1¨ units
Valve diameter ≥
tank connector diameter
Safety valve/non-return flap/valve
A non-return flap preceded by a valve must be fitted to the cold water inlet if the tank is
equipped with a safety valve. To avoid scaling of these components, operate the safety unit
at least once a month by moving its controls to various positions.
No non-return valve or flap should ever be fitted between the safety valve or safety unit
and the tank.
5.4. Hydraulic connection diagram
See Appendix A page 63.
6. ELECTRIC ELEMENTS
Tank heating time
with resistor(s):
These estimated heating times are given for storage at 60°C and cold water at 10°C
.
On CORFIRST and CORFLOW Shielded option
It is possible to add 5 to 30 kW shielded resistors, according to the following recommended
combinations
.
500
750
900
1000
1500
2000
CORFIRST
Heated volume
248
378
441
463
630
755
5 kW
3:00
4:30
5:15
5:15
7:15
8:45
10 kW
1:30
2:15
2:30
2:30
3:45
4:30
15 kW
-
1:30
1:45
1:45
2:30
3:00
25 kW
-
0:45
1:00
1:00
1:30
1:45
Heated volume
199
301
364
385
506
562
30 kW
0:25
0:35
0:45
0:45
1:00
1:05
Содержание CORFIRST
Страница 2: ......
Страница 63: ...01 02 2019 CORFIRST CORSUN 2 CORFLOW 63 82 ANNEXE A APPENDIX A ANEXO A ALLEGATO A ANHANG A BIJLAGE A ...
Страница 73: ...01 02 2019 CORFIRST CORSUN 2 CORFLOW 73 82 ANNEXE B APPENDIX B ANEXO B ALLEGATO B ANHANG B BIJLAGE B ...
Страница 75: ...01 02 2019 CORFIRST CORSUN 2 CORFLOW 75 82 ANNEXE C APPENDIX C ANEXO C ALLEGATO C ANHANG C BIJLAGE C ...
Страница 80: ... U0594061 C 80 82 CORFIRST CORSUN 2 CORFLOW ANNEXE D APPENDIX D ANEXO D ALLEGATO D ANHANG D BIJLAGE D ...