Smoke Control System
EV-HMI7B User Manual
SW Version: 1C
SCS-OM-03-V1_06-2022
Page | 11 of 14
5.
System Setup
Quick system setup procedure. Refer to the following sections for each activity.
Step Navigation actions
Setup procedure
1
CONFIG
Select the panel addresses connected
2
LABELS
Edit the address location labels and building name
3
SERVICE
Set system clock
4
RESET SERVICE
Reset service due alarm
Addresses
Each interface panel has a predefined address for the zone or function. Interface panel addresses 1 to 28
determine the fire zones. Address 60 is allocated to the head of stairs ventilator and address 62 is allocated
to the head of shaft ventilator. Refer to the interface panel instruction manual for further information.
Select YES to each address that is installed and connected to the HMI.
Labels
The label for each address can be changed to identify the correct fire zone location and the building or
system name. Each label can have up to 12 characters.