reference
manual, rev 1, Feb 22, 2022
Ground
Fault
Systems
B.V.
The Numerical LCD window displays actual ground fault current in A. When a 5000:5 ratio interposing CT
is used, all displayed values are to be interpreted as kA rather than A.
Two blank boxes to the right of the LCD display window are marked ‘A’ and ‘kA’. Use a permanent marker
to check the appropriate box as follows:
‘A’ - when using the built-in CS, an external CS, or a 500:5 ratio interposing CT.
‘kA’ - when using a 5000:5 ratio interposing CT.