Ground
Fault
Systems
B.V.
8.3
Tables 3 - Trip Time Accuracy
Trip Time accuracy has a current dependent behaviour. See the tables below.
8.3.1
Table 3a
- Current level 0,030 – 2,5 A
Trip Current Level set between 0,030 - 2,5 A
Trip Delay
setpoint
Delay when current exceeds trip current setting by a factor of:
1,2
2
4
6
20 ms
57 -
90 ms 34 -
53 ms 23 -
40 ms 17 -
34 ms
50 ms
87 - 120 ms 64 -
83 ms 53 -
70 ms 47 -
64 ms
100 ms
137 - 170 ms 114 - 133 ms 103 - 120 ms 97 - 114 ms
200 ms
237 - 270 ms 214 - 233 ms 203 - 220 ms 197 - 214 ms
500 ms
531 - 581 ms 507 - 544 ms 497 - 531 ms 491 - 525 ms
1000 ms
1031 - 1081 ms 1007 - 1044 ms 997 - 1031 ms 991 - 1025 ms
2000 ms
2031 - 2081 ms 2007 - 2044 ms 1997 - 2031 ms 1991 - 2025 ms
5000 ms
4890 - 5081 ms 4867 - 5044 ms 4856 - 5031 ms 4850 - 5025 ms
8.3.2
Table 3b
- Current level 4 A
Trip Current Level set at 4 A
Trip Delay
setpoint
Delay when current exceeds trip current setting by a
factor of:
1,2
2
≥ 3,7
20 ms
57 -
90 ms 34 -
53 ms 20 -
37 ms
50 ms
87 - 120 ms 64 -
83 ms 50 -
67 ms
100 ms
137 - 170 ms 114 - 133 ms 100 - 117 ms
200 ms
237 - 270 ms 214 - 233 ms 200 - 217 ms
500 ms
531 - 581 ms 507 - 544 ms 494 - 528 ms
1000 ms
1031 - 1081 ms 1007 - 1044 ms 994 - 1028 ms
2000 ms
2031 - 2081 ms 2007 - 2044 ms 1994 - 2028 ms
5000 ms
4890 - 5081 ms 4867 - 5044 ms 4853 - 5028 ms