Grosvenor Sateon Advance 2 Door Blade Скачать руководство пользователя страница 4

Page 4

Lock Connections

Auxiliary Input connections

+
_

Fit mechanical 

override for 

emergency release

Lock

Lock +

GND

BGU

A Fail Secure lock requires power to release 

the lock. The door would remain locked in the 

case of a power failure.

Fail Secure Lock

+
_

Lock

Normal

Broken

Broken

Normal

Break Glass 

2- Pole Changeover

Fail Safe Lock with Break Glass
A Fail Safe lock requires power to lock the 

door. The door would be unlocked in the case 

of a power failure.

If an external power source is detected on 

power up/reset, it is used to power the locks, 

otherwise internal power supply is used. Do 

not connect an external power supply while the 

controller is running.

+

External Lock

Power Supply

12-24 V dc

GND   

In +

0V

+12-24V

IN

IN

IN

External Power Supply

Input switch

Aux In +

Out ±

Return ±

GND

Contact Only (no fault detection)

Supervised (short/open circuit detect)

Supervised (short/open circuit fault detect) with 

additional tamper state.

Auxiliary Output connections

ISO

Max Voltage 30V

Max Current 300mA

Fuse 0.3A

4

3

Aux Out

The Aux input is pulled to 5V by the Blade using the 

equivalent circuit shown below:

GND

GND

TVS

14k4

2k2

+5V

Lock and I/O Connections

Email:  

[email protected]

Telephone: 

+44 (0)1279 838000

Web:  

 

www.grosvenortechnology.com

For more information about Sateon, visit the website or contact Technical Support:

Input switch

Aux In +

Out ±

Return ±

GND

1K

1K

Input switch

Aux In +

Out ±

Return ±

GND

1K

1K

2K2

Tamper switch

Отзывы: