Grosvenor Sateon Advance 2 Door Blade Скачать руководство пользователя страница 2

Current & Voltage

Measure

Overload Protection

Sounder 12V

Reader 12V

Reader 5V

12V => 5V

Current & Voltage

Measure

Overload Protection

Current & Voltage

Measure

Overload Protection

12V Lock 1

(4 Amp max)

12V Lock 2

(4 Amp max)

Up to 8 Amp

12V IN

(from Controller)

12V/24V

External Lock 

Supply

Input Power

The Advance 2-Door Blade draws 12V power from the 

controller. The 2-Door Blade power draw is summed 

as follows:

 

2-Door Blade Quiescent Current = 83 mA max @12V 

(1.0W)

 

External Reader Current (200mA max @ 5V and/or 

500mA max @ 12V)

 

External Door Lock Current (= 4A max per Lock @ 

12V)

Status LED

The main Blade LED Indicator is used to indicate 

activity and state (see also the status LED on the 

controller).
If the LED is continuously red, the 2-Door Blade is not 

communicating with the controller.

Blade State is reported by fl ashing a code on the LED 

every 15 seconds as follows:

5 blue fl ashes

Board is not being monitored. 

Probably no download to 

controller from Sateon

5 red fl ashes

Wrong device type confi gured, e.g. 

a door is defi ned on an I/O Blade

3 red fl ashes

Out of range device confi gured, 

e.g. Input 3 defi ned when it only 

supports 2

5 green fl ashes

No devices confi gured for board

5 yellow fl ashes

Reports electrical issues, such 

as current tripped, over voltage, 

under voltage, over current, under 

current

Blade LED indicators 

Blade Activity is reported as follows:

Yellow fl icker (lasts 

about 30 seconds)

Firmware download in 

progress

Green blink (every 5 

seconds)

Board running OK

Blue blink

Read

Yellow blink

Input state change

Red blink

Output state change

Other LED Indicators

There are three diagnostic red LEDs on a 2-Door 

Blade. Note that these LEDs cannot be seen when the 

controller and Blade are in the enclosure.

 

LED2 – Lock 1 Power. This will be on if Door 1 on the 

Blade has not been defi ned or if the Lock 1 power 

current limit has been tripped

 

LED3 – Lock 2 Power. This will be on if Door 2 on the 

Blade has not been defi ned or if the Lock 2 power 

current limit has been tripped

 

LED4 – Reader Power (includes other connections, 

such as sounders). This will be on if the Blade has 

not been defi ned or the current limit has been 

tripped

External Lock Supply

For systems with 24V door locks, or locks requiring 

more power than the controller can provide, the 

2-Door Blade supports an external lock power supply. 

This operates automatically if available, where the 

Blade will fi nd the external lock power supply for the 

locks, otherwise, it uses internal power. This cannot be 

changed without powering off .

External lock power is separate from the controller 

power. It will need an independent back-up if required: 

it is not supported by the controller battery.

Power Options