Equipment Description 

The Groen NGB and NGB/E steam generators are designed to generate Low pressure steam tor use in GOLDLINE 
cabinet mounted steamers and steam jacketed kettles. 
The generator is housed in a stainless steel cabinet on top of which can be mounted various combinations of 
steamers and kettles requiring a steam supply. It is small enough to fit in a 24 inch wide cabinet. 
The NGB and NGB/E feature an easily accessible control box, which may be pulled out through the cabinet door for 
servicing. (See Troubleshooting section of this manual.) 
The generator itself is constructed or 

1/

4

 inch-boiler plate according to ASME code (all welds are hydrostatically 

tested) and is equipped with all required instruments, fittings, and controls. 
Heat transfer fins inside the combustion chamber add to the high efficiency of this unit. The NGB and NGB/E are 
both rated as 60% efficient or better, with a firing rate of 200,000 BTU/hr using propane or natural gas. The energy 
output is 120,000 BTU/hr and effective boiler horsepower is 3.6. 
The two models are distinguished by different ignition systems. to ignite the burners. Model NGB utilizes a standing 
pilot but Model NGB/E employs a Corborundum glow coil. 

Installation 

WARNING:       

 INSTALLATION OF THE STEAM GENERATOR MUST BE DONE BY PERSONNEL QUALIFIED TO WORK 

WITH ELECTRICITY AND PLUMBING. IMPROPER INSTALLATION CAN CAUSE INJURY TO PERSONNEL 
AND/OR DAMAGE TO THE EQUIPMENT. ANY MECHANICAL, ELECTRICAL, OR GAS TYPE CHANGE 
MUST BE APPROVED BY THE GROEN DIVISION FOOD SERVICE ENGINEERING DEPARTMENT.

 

The unit should be installed in a ventilated room for efficient performance. All items which may obstruct or restrict 
the flow of air for combustion and ventilation must be removed. The area directly around the appliance must be 
cleared of all combustible materials. 

1.   Installation on both combustible and noncombustible floors is allowed, with a minimum clearance to 

combustible construction of six (6) inches at the rear and six (6) inches at each side. 

2.   Installation of the Gas Steam Generator under a ventilating hood is required. Installation of the ventilating 

hood should comply with local codes and/or ANSl/NFPA-96 Latest Edition. Also, the Gas Steam Generator 
should be electrically interlocked to shut off the gas supply and prevent the operation or the unit if the exhaust 
fan is not operating or if the fire suppression system is activated. Failure to follow these instructions can 
cause bodily injury and/or property damage. 

3.   Level the unit by adjusting the legs. and check for levelness with a spirit level on top of the cabinet. 
4.   Complete the piping to the gas service main using 

1/

2

 inch NPT pipe or approved equivalent. Connection to 

the gas valve is at the right front corner of the generator. 

5.    Provide 115 VAC, 60 HZ, 1 PH, 15 AMP electrical service. Observe local codes and/or The National 

Electrical Code in accordance with ANSI/NFPA 70 — latest edition. AN ELECTRICAL GROUND IS 
REQUIRED. The electrical schematic is located on the inside of the cabinet door. 

6.    Installation must conform with the American National Standard Z223.1 — latest edition and the National Fuel 

Gas Code. The unit should be installed in an adequately ventilated room with a provision for adequate air 
supply to the unit. The best ventilation will utilize a vent hood and exhaust fan. DO NOT obstruct the flue or 
vent duct after installation. 

7.    Adequate space for proper servicing and operation is required. DO NOT block any air intake spacing to the 

combustion chamber or obstruct the air flow. 

8.    After the steam generator has been connected to the gas supply, all gas line joints must be checked for 

leaks.

 NO FLAME SHOULD BE USED WHEN CHECKING FOR LEAKS. A

 thick soap solution or other 

suitable leak detector should be employed. 

9.    The appliance and its individual shutoff valve must be

 disconnected

 from the gas supply piping system 

during any pressure testing of the system at test pressures

 in excess of

 1/2 psig (3.48 kPa). The appliance 

must be

 isolated

 from the gas supply piping system by closing its individual manual shutoff valve during any 

pressure testing of the gas supply piping system at test pressures

 equal to or less than

 1/2 psig (3.48 kPa). 

2

 

Содержание NGB

Страница 1: ...R SMELLS GAS THIS INFORMATION SHALL BE OBTAINED BY CONSULTING YOUR LOCAL GAS SUPPLIER AS A MINIMUM TURN OFF THE GAS AND CALL YOUR LOCAL GAS COMPANY AND YOUR AUTHORIZED SERVICE AGENT EVACUATE ALL PERSO...

Страница 2: ...his unit does not extend to 1 Installation and start up 2 Simple adjustments such as tightening fittings and electrical connections 3 Malfunction as a result of improper maintenance 4 Repairs made by...

Страница 3: ...2 3 4 INITIAL START UP 4 5 OPERATION 5 6 SEQUENCE OF OPERATION 7 WATER CONDITIONING 8 REFERENCES 8 MAINTENANCE CLEANING 9 10 TROUBLESHOOTING 11 12 13 14 PARTS LISTS 5 16 17 18 19 DIAGRAMS SCHEMATICS 2...

Страница 4: ...de 2 Installation of the Gas Steam Generator under a ventilating hood is required Installation of the ventilating hood should comply with local codes and or ANSl NFPA 96 Latest Edition Also the Gas St...

Страница 5: ...less elbows and a length of no more than 6 feet A 2 IPS header is recommended for a drain line with more than 2 elbows or a length greater than 6 feet The header drain must have a gravity flow and ven...

Страница 6: ...d the knob in for 60 seconds allowing the thermocouple to heat up so it will keep the gas valve open d For NGB 2 E Turn the knob on the gas valve to the ON position 5 For NGB or NGB E Push the ON OFF...

Страница 7: ...use If it does not contact your Groen Authorized Service Agent The operating controls for NGB and NGB E are 1 The ON OFF switch on the cabinet front panel This control is used to call for electrical...

Страница 8: ...The red light in the switch will come on and the unit will automatically fill with water When the water level in the gauge glass reaches the full mark the green READY light will come on Push the STAR...

Страница 9: ...pressure rise to 12 PSI the mid range pressure switch will open both the condenser water valve and the blow down valve to decrease the pressure rapidly As steam pressure decreases below 10 1 2 PSI th...

Страница 10: ...d water through a properly maintained softener Exchangeable softener cartridges or a regeneratable softener can be used In either case establish a regular program of exchanging the cartridges or regen...

Страница 11: ...ter level in the steam generator should be between the lines on the level gauge glass 3 The strainers in the drain and feed lines should be cleared 4 Check the burner gas jet primary air inlets They s...

Страница 12: ...lief valve 4 Remove the brass plug from the front of the generator 5 Open the manual drain valve 6 Wash out the inside of the boiler with a water hose The rinse water along with the accumulated solids...

Страница 13: ...Water switch to confirm it is on c That electric power is on Check main circuit breaker or fuse and power supply to the building d Strainer for build up of solids e For a defective water level control...

Страница 14: ...e If not correct inspect wiring f Pressure switch If set too low reset If con tinuity check reveals a defect replace Ref 23 Main burner will not light g Gas valve and replace if defective Ref 10 a Pos...

Страница 15: ...Time delay relay If defective replace Ref 28 c Connections for time delay relay Air vent leaks a Clean or replace vent Ref 4 a Water supply to confirm that it is on and the pressure is 25 to 30 PSI Co...

Страница 16: ...from the receptacle of the control module and reading voltage across the pins of the igniter receptacle Ref 25 If 115 V is not present replace the control module Ref 25 C Model NGB Eonly Glow coil do...

Страница 17: ...3442 RELAY CONTROL 10 49274 VALVE GAS NAT PILOT IGNITION 28 49980 RELAY DELAY 50727 VALVE GAS NAT COIL IGNITION 29 54281 TERMINAL BLOCK 18 TABS 50838 VALVE GAS PROPANE PILOT IGNITION 30 51716 TERMINA...

Страница 18: ......

Страница 19: ...1 4 NPT X 1 1 2 LONG 66 049277B BAFFLE BURNER 22 012747 SYPHON PRESS GA TBE 1 4 NPT 67 050490 BRACKET BURNER SUPPORT 23 013207 TEE 1 4 NPT 68 047267 BURNER ASSY W JETS NATURAL 24 026514 TUBE 3 8 O D x...

Страница 20: ......

Страница 21: ...ALVE GAS 1 2 X 1 2 PROPANE 23 090694 SIPHON PRESSURE SWITCH 71 076423 THERMOCOUPLE 36 LONG 24 090695 SIPHON PRESSURE SWITCH 72 076421 PILOT BURNER NATURAL GAS 25 090692 FITTING MALE RUN TEE NPT MALE 0...

Страница 22: ...For NGB 2 NGB 2 E Made After August 7 1991...

Страница 23: ...Electrical Schematics For NGB 2 made between January 1 1988 and August 7 1991...

Страница 24: ...Electrical Schematics For NGB NGB E made before January 1 1988...

Страница 25: ...Wiring Ladder Diagrams...

Отзывы: