background image

OM-NGB/3

10

The manual drain valve is located under the
boiler

.

Cleaning

Whenever the boiler is turned off and allowed to
cool to about 170 

o

F, it drains automatically.  This

should be done every day to minimize scale build-
up inside the boiler.

In addition to this draining, however, the following
cleaning procedure should be followed using a
regular schedule.  This will prevent the
accumulation of lime on the water level probes and
interior surfaces of the boiler. The actual time
between these scheduled cleanings depends on the
water quality and hours of operation.  Minimally,
Groen recommends cleaning the boiler at least once
each month.

A.  Suggested Tools

1. 1/2" hardened square wrench extension
2. Pipe Joint compound 
3 32 oz. 

Groen

 Delimer Descaler (PN 114800),

Lime-A-Way or equivalent 

4.

Groen

 Spray Degreaser (PN 114801, or

equivalent

5.  Nylon pad(s)

B.  Procedure

WARNING

WATER AND VALVES MAY BE VERY HOT,
AND MAY CAUSE BURNS.  PROTECT HANDS
FROM HOT SURFACES AND WATER.

1.

Turn the boiler on/off switch to the OFF position.

2.

Slowly open the manual drain valve to empty
the boiler. The valve is located under the boiler.

3.

Close the manual drain valve.

4.

Turn off water supply to the boiler.

5.

Allow the boiler to cool.  This takes several
hours, so it is recommended that you cool the
boiler overnight.

6.

Turn on/off switch to “ON” to close the
automatic drain valve.

7.

Using a 1/2" hardened square wrench extension,
remove one of the 1" NPT pipe plugs from the
front of the boiler.

Содержание NGB/3 Series

Страница 1: ...ING THIS EQUIPMENT POST IN A PROMINENT LOCATION INSTRUCTIONS TO BE FOLLOWED IN THE EVENT USER SMELLS GAS THIS INFORMATION SHALL BE OBTAINED BY CONSULTING YOUR LOCAL GAS SUPPLIER AS A MINIMUM IMMEDIATE...

Страница 2: ...THE WARNINGS AND FOLLOW THE DIRECTIONS ON THE LABEL OF EACH CLEANING AGENT USE SAFETY GLASSES AND RUBBER GLOVES AS RECOMMENDED BY DELIMING AGENT MANUFACTURER WARNING DO NOT MIX DE LIMING AGENTS ACID A...

Страница 3: ...IONING REQUIREMENTS 4 INSTALLATION INSTRUCTIONS 5 INITIAL START UP 6 OPERATING INSTRUCTIONS 7 SEQUENCE OF OPERATION 8 CLEANING AND MAINTENANCE PROCEDURES CLEANING 9 MAINTENANCE 11 TROUBLESHOOTING 12 D...

Страница 4: ...utput and possibly cause premature component failure Your water utility can tell you about the minerals in your water The water going to the steam generator should have between 1 and 30 parts per mill...

Страница 5: ...ected from the gas supply piping system during any pressure testing of that system at test pressures in excess of PSI 3 45 kPA The unit must be isolated from the gas piping system by closing its indiv...

Страница 6: ...it with 1 1 4 NPT pipe DO NOT USE PLASTIC PIPE DRAIN PIPING MUST WITHSTAND STEAM AND BOILING WATER Extend the drain piping to a nearby floor drain Piping of 1 1 4 NPT or 1 1 2 NPT is acceptable for di...

Страница 7: ...tem will automatically stop gas flow to the pilot burner and terminate the ignition trial If this happens turn the switch to OFF and then ON again to repeat the trial for ignition 5 Turn the on off sw...

Страница 8: ...ob is released the pilot burner will remain lit Turn the control to the ON position 2 For the NGB 3 E Turn the control knob on the gas valve to the ON position NOTE On the NGB 3 E the ignition trial p...

Страница 9: ...nt before it is fully closed at approximately 200o F Once the pressure has reached 9 1 2 PSI the main burner will be shut off by an operating pressure switch Residual heat stored in the boiler s heat...

Страница 10: ...h month A Suggested Tools 1 1 2 hardened square wrench extension 2 Pipe Joint compound 3 32 oz Groen Delimer Descaler PN 114800 Lime A Way or equivalent 4 Groen Spray Degreaser PN 114801 or equivalent...

Страница 11: ...for 10 minutes 14 When steamer timers sound turn them to OFF and open the doors 15 When the fans have stopped remove fan baffle partitions using protective gloves and rinse with clean water 16 Comple...

Страница 12: ...Service Log Each time maintenance is performed on the unit enter the date on which it was done what was done and who did it Keep this log with the warranty In addition to yearly inspections by a qual...

Страница 13: ...with water User can check a Is the boiler level Check levelness of unit with a spirit level b Is the water pressure too high Greater than 60 PSI Auth Service Rep Only c Is the Water Level Control Boa...

Страница 14: ...essure gauge defective Auth Service Rep Only c Is the air vent leaking steam X d Is the solenoid or manual drain valve open or leaking NOTE Excessive make up water added to the boiler reduces steam pr...

Страница 15: ...e rep 15 Boiler blows down immediately when turned off Auth Service Rep Only a Is the thermostatic switch defective Check for loose electrical connections on switch X Boiler does not drain User can ch...

Страница 16: ...Jets w 55 Drill Dia Hole 065949 7b Main Burner Assy 2501 5500 Ft Elev Incl 29 Gas Jets w 69 Drill Dia Hole 065019 7c Main Burner Assy 5501 8500 Ft Elev Incl 29 Gas Jets w 55 Drill Dia Hole 091938 7c M...

Страница 17: ...097099 12 Globe Valve 1 2 NPT 099255 4 Flue 099217 13 Operating Pressure Switch 9 PSI 099222 5 Safety Valve 15PSI 102297 14 Hi limit Pressure Switch 14 PSI 099223 6 Pressure Relief Valve 12PSI 099228...

Страница 18: ...074842 3 Indicator Light Reset 099289 12 Transformer 120 208 240V Pri 24V Sec 094164 4 Circuit Board Supports 1 2 High 099292 13 Fuse 7 AMP 096798 5 Liquid Level Control Board 099246 14 Terminal Block...

Страница 19: ...OM NGB 3 19 Electrical Schematic NGB 3 Standing Pilot...

Страница 20: ...OM NGB 3 20 Electrical Schematic NGB 3 E Spark Ignition...

Страница 21: ...TITUTE 1403 Broadway New York New York 10018 Z21 30 Installation of Gas Appliances and Gas Piping Z223 1 latest edition National Flue Gas Code NATIONAL FIRE PROTECTION ASSOCIATION 60 Battery March par...

Страница 22: ...OM NGB 3 22 Service Log Model No Serial No Date Purchased Purchase Order No Purchased From Location Date Installed For Service Call Date Maintenance Performed Performed by...

Страница 23: ...tal to portal transportation costs time and mileage for the first twelve 12 months from date of installation or fifteen 15 months from date of shipment from Groen This warranty does not cover boiler m...

Страница 24: ...1055 Mendell Davis Drice Jackson MS 39272 Telephone 888 994 7636 OM NGB 3 Revised 12 97 Part Number 121003...

Отзывы: