OM-AH

6

WARNING

THIS PRODUCT MUST BE INSTALLED BY A LICENSED PLUMBER OR GAS FITTER WHEN

INSTALLED  WITHIN THE COMMON WEALTH OF MASSACHUSETTS.  IMPROPER INSTALLATION CAN   

CAUSE INJURY TO PERSONNEL AND/OR DAMAGE TO THE EQUIPMENT.

THIS UNIT IS FOR COMMERCIAL USE. NEVER USE HOME OR RESIDENTIAL GRADE GAS CONNECTIONS.

THEY DO NOT MEET GAS CODES AND COULD BE HAZARDOUS.

Installation and Initial Start-Up

A. Installation

The unit should be installed in a ventilated room for

efficient performance. items which may obstruct or

restrict the flow of air for combustion and ventilation

must be removed. The area directly around the

appliance must be cleared of all combustible materials.
1. Installation requires connection with gas and

electrical services. See items 8 to 14 for details.

2. To protect the unit from damage, leave it on the

shipping pallet until the time of installation. When

installation is to begin, cut the straps holding the

kettle, and hoist the kettle straight up off the skid.

NOTICE 

To avoid damaging parts of the burner system

underneath the kettle, LIFT THE UNIT ONLY BY THE

RING beneath the outer portion of the body.

3. Install the unit with a minimum clearance to

combustible and non-combustible construction of six

inches at the sides and six inches between the draft

diverter and the wall. Also leave enough room for

cleaning, maintenance, and service.

4. The draft diverter shipped with the kettle is the

correct height and shape to give maximum

performance. Install the draft diverter as shown on

Figures 1 and 2 above.  Securely fasten the screw
to attach draft directly.  Do  not change the diverter
in any way.

WARNING  

DO NOT ATTACH THE UNIT TO A TYPE “B” VENT.

FAILURE COULD RESULT IN FIRE OR PROPERTY

DAMAGE.

Install the unit under a ventilation hood, or vent the

flue directly to a masonry chimney. Put a hood at

least several inches above the upper end of the draft

diverter. Do 

not

 rest hood supports on the diverter.

Installation of a ventilating hood should comply with

local codes and/or ANSI/NFPA-96 Latest Edition.

Also, local codes may require that the kettle be

electrically interlocked to shut off the gas supply

and prevent the operation of the unit if the

exhaust fan is not operating or if the fire

suppression system is activated. Failure to

follow these instructions can cause bodily injury

and/or property damage. 

5. To level the unit, adjust leg length by turning the

bullet feet

6. Make sure the water level is correct in the

jacket, by confirming that the level is between

the marks on the gauge glass. If the water level

is low, follow the instructions under “Jacket

Filling” in the “Maintenance” Section of this

manual.

CAUTION

DO NOT CONNECT ANY PIPING TO THE 
PRESSURE RELIEF SAFETY VALVE. IT MUST

BE FREE TO VENT STEAM AS NEEDED.

ELBOW SHOULD POINT DOWN TOWARD

FLOOR. IMPROPER INSTALLATION

WILL VOID WARRANTY!

7. To protect personnel from steam coming out of

the safety valve, the open end of the elbow at

the outlet must be directed down. If it is not, turn

the elbow to the correct position.

DANGER ELECTRICALLY GROUND THE UNIT

AT THE TERMINAL PROVIDED. FAILURE TO

GROUND UNIT COULD RESULT IN

ELECTROCUTION AND DEATH.

Fig. 1

Fig. 2

PDF compression, OCR, web optimization using a watermarked evaluation copy of CVISION PDFCompressor

Содержание AH/1

Страница 1: ...CINITY OF THIS OR ANY OTHER APPLIANCE POST IN A PROMINENT LOCATION INSTRUCTIONS TO BE FOLLOWED IN THE EVENT USER SMELLS GAS THIS INFORMATION SHALL BE OBTAINED BY CONSULTING YOUR LOCAL GAS SUPPLIER AS...

Страница 2: ...BRANES AND CLOTHING TAKE PRECAUTIONS WEAR RUBBER GLOVES GOGGLES OR FACE SHIELD AND PROTECTIVE CLOTHING CAREFULLY READ WARNINGS AND FOLLOW DIRECTIONS ON CLEANER LABELS NOTICE NEVER LEAVE A SANITIZER IN...

Страница 3: ...hio 44131 ANSI Z83 11 NATIONAL SANITATION FOUNDATION 3475 Plymouth Rd Ann Arbor Michigan 48106 NSF ANSI 4 AMERICAN NAT L STANDARDS INST INC 1430 Broadway New York New York 10018 Z223 1 1984 National F...

Страница 4: ...what is happening inside the unit These are a Water level sight glass Indicates whether there is enough water in the steam jacket b Pressure vacuum gauge Shows steam pressure and whether too much air...

Страница 5: ...damage Open the container and check the unit for hidden damage Report shipping damage or shipment errors to the delivery agent Write down the model number serial number and installation date for your...

Страница 6: ...above Securely fasten the screw to attach draft directly Do not change the diverter in any way WARNING DO NOT ATTACH THE UNIT TO A TYPE B VENT FAILURE COULD RESULT IN FIRE OR PROPERTY DAMAGE Install...

Страница 7: ...ng system at test pressures equal to or less than 1 2 PSIG 3 48 kPa 16 Check the following points to confirm that your AH kettle has been installed properly electrical or gas type change must be appro...

Страница 8: ...TO LIGHT ANY BURNER WITH A FLAME CAUTION HEATING AN EMPTY KETTLE MAY CAUSE THE RELEASE OF STEAM FROM THE SAFETY VALVE 1 To Start Kettle a CHECK THE WATER LEVEL IN THE JACKET EVERY DAY The level shoul...

Страница 9: ...TIRRING OR TRANSFERRING PRODUCT TO ANOTHER CONTAINER CAUTION DO NOT OVERFILL THE KETTLE WHEN COOKING HOLDING OR CLEANING KEEP LIQUIDS 2 3 5 8 cm BELOW THE KETTLE RIM TO ALLOW CLEARANCE FOR STIRRING BO...

Страница 10: ...urn off the power switch Check the gas supply valves and wait five minutes before trying again by switching power on If you cannot establish a pilot flame in four tries close all valves turn off the p...

Страница 11: ...CONTACT CAN CAUSE CORROSION c Prepare a solution of the detergent cleaning compound as instructed by the supplier Clean the unit thoroughly A cloth moistened with cleaning solution can be used to cle...

Страница 12: ...as Groen De limer De Scaler Part Number 114800 Rinse and drain the unit thoroughly before further use m If especially difficult cleaning problems persist contact your cleaning product supplier for as...

Страница 13: ...ng a will screwdriver or other implement to pull the ring help you avoid contact with the steam 3 Jacket Filling Every day before you turn on the unit make sure the water level is approximately in the...

Страница 14: ...s and compound are used in the future However it is best to check the pH each time treated water is prepared Troubleshooting Your Groen kettle is designed to operate smoothly and efficiently if proper...

Страница 15: ...is not flowing 1 Check the pilot gas line for kinks and obstructions 2 Clean orifice if necessary 3 Check magnetic operator for pilot valve on gas valve Repair or replace as necessary d That the pilo...

Страница 16: ...OM AH 16 Parts List AH 1E PDF compression OCR web optimization using a watermarked evaluation copy of CVISION PDFCompressor...

Страница 17: ...T x Close 008877 Screw Sheet Metal pan hd 12 x 1 2 lg 008769 Valve Gate 1 2 NPT 004180 Bracket faucet Mounting 16 Ga x 4 3 4 009054 Label Warning 098171 Diverter Draft 6 AH 1E 20 40 012474 Wiring Diag...

Страница 18: ...OM AH 18 Parts List AH 1E 40 PDF compression OCR web optimization using a watermarked evaluation copy of CVISION PDFCompressor...

Страница 19: ...281 Orifice Prop Higher Elev 000403 9 Bracket Pilot Burner Mounting 123824 11 Bracket Pilot Burner Mounting 123824 10 Screw 10 24 x 3 8 lg Round Head 006009 12 Screw 10 24 x 3 8 lg Round Head 006009 1...

Страница 20: ...mbly Front Panel Components Assembly Parts List To order parts contact your Groen Certified Service Agency Supply the model designation part description and number quantity and where applicable voltag...

Страница 21: ...Screw 10 32 x 3 8 long 069773 12 Sight Tube 5 8 Dia x 4 3 4 long 008742 Electrical Panel Assembly 123823 13 Fittings Sight Glass Assembly 002845 1 Water Level Control 24V 122192 Front Panel Component...

Страница 22: ...OM AH 22 Electrical Schematic PDF compression OCR web optimization using a watermarked evaluation copy of CVISION PDFCompressor...

Страница 23: ...tion ___________________________________ Date Purchased _____________________________ Date Installed _______________________________ Purchase Order No __________________________ For Service Call _____...

Страница 24: ...from date of shipment from Groen IV This warranty does not cover boiler maintenance calibration periodic adjustments as specified in operating instructions or manuals and consumable parts such as scra...

Отзывы: