Verifications/ Calibration 

The transmitter features a simple snap-mount sensor pcb that is pre-calibrated. This means that the entire sensor pcb can 
simply be replaced with a new calibrated pcb if desired without having to remove the enclosure. This sensor swap requires no 
tools and can be completed in seconds. Simply disconnect the device wiring, remove the old sensor pcb, snap in the new pcb 
and reconnect the device power. There is no need to make any adjustments or apply gas to the transmitter using the sensor 
swap method. 

 

The device may also be calibrated or verified with CO gas if required. This requires a field calibration kit consisting of a 
bottle of gas (250 ppm CO in air for example), a tank pressure regulator with flow restrictor and the necessary tubing with a 
calibration cap to cover to the sensor. Calibration can be done at 20-27 

C. 

 

Verification 

Verification with gas can be done without removing the device cover. Simply apply gas using the calibration cap attached 
directly to the port on the cover and monitor the output signal. 

 

Verify With Cover In Place

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Calibration 

The device cover must be removed to perform an actual calibration. In this case, the gas calibration cap attaches to the sensor 
fixture inside the enclosure.  

Calibrate With Cover Removed

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание CMD5B1 Series

Страница 1: ...tion In normal operation the sensor will measure the CO level in the surrounding air and output a proportional value on the 4 20 mA output The CO measurement range is 0 to 300 ppm An optional relay can be used to indicate an alarm condition The trip point for the relay can be programmed to three different settings with an on board jumper If the CO level exceeds the trip point then the relay is act...

Страница 2: ...ll not operate if connected backwards For 3 wire operation of the relay model connect either an AC or DC power supply to POWER and COMMON and the 4 20 mA signal is available on the OUTPUT terminal with respect to COMMON The current output operates in the Active mode and does not require a loop power supply This means the signal current is generated by the transmitter and must not be connected to a...

Страница 3: ...tter using the sensor swap method The device may also be calibrated or verified with CO gas if required This requires a field calibration kit consisting of a bottle of gas 250 ppm CO in air for example a tank pressure regulator with flow restrictor and the necessary tubing with a calibration cap to cover to the sensor Calibration can be done at 20 27 C Verification Verification with gas can be don...

Страница 4: ... and attach it to the 250 ppm gas bottle and firmly tighten it by hand Moisten the sponge and squeeze out any excess water Place the sponge in the cap so that it will not touch the sensor but does not plug the hole in the side of the cap Attach the cap to the fixture over the sensor Slowly turn the valve knob on the regulator to let the gas begin flowing The regulator will restrict the flow rate t...

Страница 5: ...overage 700 m2 7500 ft2 or 15 m 50 ft radius Wiring Connections Screw terminal block 14 to 22 AWG Enclosure 2 8 w x 4 1 h x 1 9 d 71 x 104 x 48 mm 2 Wire Loop Powered Model Power Supply 24 Vdc 20 or 24 Vac 10 non isolated half wave rectified Consumption 20 mA max Output Signal 4 20 mA loop powered Output Drive Capability 550 ohms max 24 Vac dc 3 Wire Relay Model Power Supply 24 Vdc 20 or 24 Vac 10...

Отзывы: