background image

MODEL 

AFS-222/AFS-222-112 

AFS-262/AFS-262-112 

AFS-460 

SAMPLE MEDIA 

Air 

Air 

Air 

MOUNTING POSITION 

Diaphragm in any vertical plane 

Diaphragm in any vertical plane 

Diaphragm in any vertical plane 

FIELD ADJUSTABLE RANGE 

.05, ±.02” w.c. to 12” w.c. 

.05, ±.02” w.c. to 2” w.c. 

.40, ±.06” w.c. to 12” w.c. 

SWITCH DIFFERENTIAL 

Progressive, increasing from      
approximately .02± .01” w.c. at 
minimum set point to approximately 
0.8” w.c. at maximum set point.  

Progressive, increasing from      
approximately 0.02± 0.01” w.c. at 
minimum set point to approximately 
0.1” w.c. at maximum set point. 

Progressive, increasing from      
approximately .06± .01” w.c. at 
minimum set point, to                
approximately .8”w.c. at maximum 
set point. 

MAXIMUM PRESSURE 

.5” (0.03 bar) 

.5” (0.03 bar) 

.5” (0.03 bar) 

OPERATING TEMPERATURE RANGE 

-40°C – 82.2°C (-40°F–180°F) 

-40°C – 82.2°C (-40°F–180°F) 

-40°C – 82.2°C (-40°F–180°F) 

LIFE 

100,000 cycles/min. at 5psi max 
pressure each cycle and  at max  
electrical load. 

100,000 cycles/min. at 5psi max 
pressure each cycle and  at max 
electrical load. 

600 cycles/min. at 5psi max pres-
sure each cycle and at max electrical 
load. 

ELECTRICAL RATING 

300 va pilot duty at 115-277vac, 10 
amp, non-inductive, 277 vac, 60Hz. 

300 va pilot duty at 115-277vac, 10 
amp, non-inductive, 277 vac, 60Hz. 

300 va pilot duty at 115-277vac, 10 
amp, non-inductive, 277 vac, 60Hz. 

CONTACT ARRANGEMENT 

SPDT 

SPDT 

SPDT 

ELECTRICAL CONNECTIONS 

Screw top terminals with cup   wash-
ers 

Screw top terminals with cup   
washers 

Screw top terminals with cup   
washers 

SAMPLE LINE CONNECTIONS 

Ferrule and nut compression type 
connectors that accept 6.35 mm
(.25”) OD rigid tubing or 1/4“ 
barbed fittings (-112) that accept 
flexible tubing. 

Ferrule and nut compression type 
connectors that accept 6.35 mm
(.25”) OD rigid tubing or 1/4“ 
barbed fittings (-112) that accept 
flexible tubing. 

Ferrule and nut compression type 
connectors that accept 6.35 mm 
(.25”) OD rigid tubing. 

AUTOMATIC/MANUAL RESET 

Automatic 

Automatic 

Manual 

APPROVALS 

UL and CSA 

UL and CSA 

UL and CSA 

Specifications 

Dimensions  

Alarm or Control 

 

NO 

NC 

NC 

NO 

Alarm 

Control 

Control 

Alarm 

To prove excessive airflow or pressure 

To prove insufficient airflow or pressure 

01/07/09 