The pressure scale defaults to "wc. Use <UP> or <DOWN> to toggle it to Pa.
<MENU>
Press to advance to next menu item
The pressure range defaults to HI. Pressure ranges per model are shown below:
RP01 = HI (±1"wc or ±250 Pa), LO (±0.5"wc or ±125 Pa)
RP02 = HI (±0.25"wc or ±60 Pa), LO (±0.125"wc or ±30 Pa)
This can be changed to LO using <UP> or <DOWN>.
<MENU>
Press to advance to next menu item
1. PRESSURE SCALE
2. PRESSURE RANGE
<MENU>
Press and release to enter the Setup Menu.
"WC
MENU
The pressure averaging time defaults to 5 seconds. This can be changed from
1-60 seconds using <UP> or <DOWN>.
<MENU>
Press to advance to next menu item
3. PRESSURE AVERAGING
"WC
MENU
MENU
The local alarm buzzer volume can be set or muted via the menu and an alarm test can be initiated via
the menu. The alarm test will force an alarm condition to be set. Since the menu has a 5 minute time-out,
if the alarm is left on it will reset after 5 minutes back to a normal condition.
AUTO ZERO OPERATION
A sensor auto zero can be initiated by pressing and holding the internal ZERO switch for at least 3
seconds. If booth pressure ports are close to zero pressure (open to ambient), then the device will
calibrate with a new zero point.
SETUP MENU OPERATION
The setup menu can be accessed by pressing the internal <MENU> key at any time after the start-up
mode.
The system suspends operation when in the menu and holds the last pressure value on the output. If an
alarm condition was present then it will be reset to enter the menu and alarm operation is disabled while
in the menu (except for alarm test). If the setup menu is not active for 5 minutes (no key press), then the
menu will exit and the device returns to normal operation.
The high pressure alarm limit defaults to (+ range max x 50%). This equals
+ 0.5 "wc for the ± 1 "wc range, + 125 for the ± 250 Pa range, etc. It can be
changed using <UP> or <DOWN> throughout the range. Resolution for each
range is: ± 1 "wc (0.05), ± 0.5 "wc (0.02), ± 0.25 "wc (0.01), ± 0.125 "wc (0.01),
± 250 Pa (10), ± 125 Pa (5), ± 60 Pa (2) and ± 30 Pa (1). Note that the ± 250 Pa
range must be displayed as /10 such that it is - 25H to 25H.
<MENU>
Press to advance to next menu item
4. HIGH PRESSURE ALARM
MENU
The low pressure alarm limit defaults to (- range max x 50%). This equals - 0.5
for the ± 1 "wc range, - 125 for the ± 250 Pa range, etc. It can be changed using
<UP> or <DOWN> throughout the range. Note the restrictions as described in
Alarm Operation section.
<MENU>
Press to advance to next menu item
5. LOW PRESSURE ALARM
MENU
"WC