The pressure scale defaults to "wc. Use <UP> or <DOWN> to toggle it to Pa.

<MENU> 

Press to advance to next menu item

The pressure range defaults to HI. Pressure ranges per model are shown below:

RP01 = HI (±1"wc or ±250 Pa), LO (±0.5"wc or ±125 Pa)

RP02 = HI (±0.25"wc or ±60 Pa), LO (±0.125"wc or ±30 Pa)

This can be changed to LO using <UP> or <DOWN>.

<MENU> 

Press to advance to next menu item

1. PRESSURE SCALE

2. PRESSURE RANGE

<MENU> 

Press and release to enter the Setup Menu.

"WC

MENU

The pressure averaging time defaults to 5 seconds. This can be changed from

1-60 seconds using <UP> or <DOWN>.

<MENU> 

Press to advance to next menu item

3. PRESSURE AVERAGING

"WC

MENU

MENU

The local alarm buzzer volume can be set or muted via the menu and an alarm test can be initiated via 

the menu. The alarm test will force an alarm condition to be set. Since the menu has a 5 minute time-out, 

if the alarm is left on it will reset after 5 minutes back to a normal condition.

AUTO ZERO OPERATION

A sensor auto zero can be initiated by pressing and holding the internal ZERO switch for at least 3 

seconds. If booth pressure ports are close to zero pressure (open to ambient), then the device will 

calibrate with a new zero point.

SETUP MENU OPERATION

The setup menu can be accessed by pressing the internal <MENU> key at any time after the start-up 

mode.

The system suspends operation when in the menu and holds the last pressure value on the output. If an 

alarm condition was present then it will be reset to enter the menu and alarm operation is disabled while 

in the menu (except for alarm test). If the setup menu is not active for 5 minutes (no key press), then the 

menu will exit and the device returns to normal operation.

The high pressure alarm limit defaults to (+ range max x 50%). This equals

+ 0.5 "wc for the ± 1 "wc range, + 125 for the ± 250 Pa range, etc. It can be

changed using <UP> or <DOWN> throughout the range. Resolution for each

range is: ± 1 "wc (0.05), ± 0.5 "wc (0.02), ± 0.25 "wc (0.01), ± 0.125 "wc (0.01),

± 250 Pa (10), ± 125 Pa (5), ± 60 Pa (2) and ± 30 Pa (1). Note that the ± 250 Pa

range must be displayed as /10 such that it is - 25H to 25H.

<MENU> 

Press to advance to next menu item

4. HIGH PRESSURE ALARM

MENU

The low pressure alarm limit defaults to (- range max x 50%). This equals - 0.5

for the ± 1 "wc range, - 125 for the ± 250 Pa range, etc. It can be changed using

<UP> or <DOWN> throughout the range. Note the restrictions as described in

Alarm Operation section.

<MENU> 

Press to advance to next menu item

5. LOW PRESSURE ALARM

MENU

"WC

"WC

Содержание RPC Series

Страница 1: ...sed to vibrations or rapid temperature changes To prevent erroneous readings due to air disturbances within the wall cavity seal the conduit leading to the junction box The cover is hooked to the base at the top edge and must be removed from the bottom edge first Use a small Phillips screwdriver to loosen the security screw as shown in Figure 1 Complete removal is not required Use a screw driver t...

Страница 2: ...evices with RS 485 network connections Connect the RS 485 network with twisted shielded pair to the terminals marked A B and SHIELD The positive wire connects to B and the negative wire connects to A and the cable shield must be connected to the SHIELD terminal on each device If the device is installed at either end of an RS 485 network an end of line EOL termination resistor 121 ohm should be ins...

Страница 3: ... signal type is correctly selected on the PCB Also review the specifications to ensure the power supply is correct and that the pressure is within the correct range The product should be allowed to warm up for several minutes before attempting to verify accuracy Operation can be verified by measuring the output signal For voltage output configuration measure the voltage between the PRES OUT and CO...

Страница 4: ...um span is reached while adjusting one of the alarm limits then the other alarm limit will be pushed In this example for the 1 wc range these are some possible alarm settings 1 0 to 0 5 wc 0 75 to 0 25 wc 0 5 to 0 wc 0 25 to 0 25 wc 0 to 0 5 wc 0 5 to 1 0 wc The alarm also has settings for on delay and off delay which can be set via the menu Both of these default to 5 seconds but may be changed fr...

Страница 5: ... 3 seconds If booth pressure ports are close to zero pressure open to ambient then the device will calibrate with a new zero point SETUP MENU OPERATION The setup menu can be accessed by pressing the internal MENU key at any time after the start up mode The system suspends operation when in the menu and holds the last pressure value on the output If an alarm condition was present then it will be re...

Страница 6: ...IGHT MENU The LCD backlight defaults to 1 on It can be toggled to 0 off using UP or DOWN MENU Press to advance to next menu item 11 ALARM TEST MENU The alarm off delay defaults to 5 seconds It can be changed from 1 59 seconds and 1 10 minutes using UP or DOWN MENU Press to advance to next menu item 7 ALARM OFF DELAY MENU OFF The default BACnet MAC address is 3 This can be changed from 0 to 127 usi...

Страница 7: ... LCD 0 45 digit height unit symbols and backlight Wiring Connections Screw terminal block 14 to 22 AWG Pressure Connections Ports for 1 16 ID tubing 1 8 ID adapters included Enclosure White ABS IP30 NEMA 1 84mm W x 119mm x 29mm H 3 3 x 4 7 x 1 15 Weight 115g 4oz Country of Origin Canada POWER SUPPLY Power Supply 24 Vac dc 10 Power Consumption 70 mA max with alarms on INTERFACE Communication 2 wire...

Отзывы: