background image

IN-GE-RPCXXXBAC-01-02             03/19

Page  2

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

SETUP

The device parameters must be set before connection to the network and will ensure each device will have 

a unique MAC address and Device Instance for startup. On startup, the MAC address is appended to the 

Device Object : Vendor Identifier to create the unique Device Instance (Device Object : Object Identifier). 

Once connected to a network, the Device Object : Object Identifier can be written to any unique value via 

BACnet and then the MAC address will no longer be appended to the value. Once set, all parameters are 

saved in non-volatile memory. The local menu and LCD are used to set the BACnet MAC device address (0-

127) and the baud rate. The factory defaults are address 3 and 9600 baud. The menu and setup procedure is 

described later.

WIRING

The transmitter has standard screw block connectors. Use shielded twisted pair wiring of at least 22 AWG for 

all connections and do not run device wires in the same conduit with wiring used to supply inductive loads 

such as motors. Disconnect the power supply before making any connections to prevent electrical shock or 

equipment damage. Make all connections in accordance with national and local electrical codes.

This is a 3-wire sourcing device. Connect the positive dc or the ac voltage hot side (24 Vac/dc ± 10%) to the 

POWER terminal. The supply common is connected to the COMMON terminal. The device is reverse voltage 

protected and will not operate if connected backwards. Use caution if 24 Vac 

power is used and one side of the transformer is earth-grounded. In general, 

the transformer should NOT be connected to earth ground when using 

devices with RS-485 network connections.

Connect the RS-485 network with twisted shielded pair to the terminals 

marked A(-), B(+) and SHIELD. The positive wire connects to B(+) and the 

negative wire connects to A(-) and the cable shield must be connected to the 

SHIELD terminal on each device. If the device is installed at either end of an 

RS-485 network, an end-of-line (EOL) termination resistor (121 ohm) should 

be installed in parallel to the A(-) and B(+) terminals. This device includes a 

network termination jumper and will connect the 121 ohm resistor correctly 

on the PCB. Simply move the jumper to the EOL position and no external 

resistor is required. The ground wire of the shielded pair should be connected 

to earth ground at the end of the network and the device is not grounded. 

Do not run bus wiring in the same conduit 

as line voltage wiring or other wiring that 

switches power to highly inductive loads 

such as contactors, coils or motors.

A network segment is a single shielded wire loop run between several devices (nodes) in a daisy chain 

configuration. The total segment length should be less than 4000 feet (1220 meters) and the maximum 

number of nodes on one segment is 127. Nodes are any device connected to the loop and include controllers, 

repeaters and sensors such as the RP but do not include the EOL terminators. To install more than 127 devices, 

or to increase the network length, repeaters will be required for proper communication. The maximum 

daisy chain length (segment) depends on transmission speed (baud rate), wire size and number of nodes. 

If communication is slow or unreliable, it may be necessary to wire two daisy chains to the controller with a 

repeater for each segment.

Figure 5

Figure 6

Digital Input

RELAY

Controller

Building Controller

24 Vac/dc

Common

BACnet® Master

A (-)

B (+)

Shield

Device 01

POWER

COMMON

A (-)

B(+)

SHLD

POWER

COMMON

A (-)

B(+)

SHLD

A (-)

B(+)

SHLD

POWER

COMMON

Device 02

Device 03

Set EOL Jumper

Connect Shield

One End Only

EOL

EOL

ON

OFF

Figure 8

Buzzer -

Содержание RPC Series

Страница 1: ...sed to vibrations or rapid temperature changes To prevent erroneous readings due to air disturbances within the wall cavity seal the conduit leading to the junction box The cover is hooked to the base at the top edge and must be removed from the bottom edge first Use a small Phillips screwdriver to loosen the security screw as shown in Figure 1 Complete removal is not required Use a screw driver t...

Страница 2: ...evices with RS 485 network connections Connect the RS 485 network with twisted shielded pair to the terminals marked A B and SHIELD The positive wire connects to B and the negative wire connects to A and the cable shield must be connected to the SHIELD terminal on each device If the device is installed at either end of an RS 485 network an end of line EOL termination resistor 121 ohm should be ins...

Страница 3: ... signal type is correctly selected on the PCB Also review the specifications to ensure the power supply is correct and that the pressure is within the correct range The product should be allowed to warm up for several minutes before attempting to verify accuracy Operation can be verified by measuring the output signal For voltage output configuration measure the voltage between the PRES OUT and CO...

Страница 4: ...um span is reached while adjusting one of the alarm limits then the other alarm limit will be pushed In this example for the 1 wc range these are some possible alarm settings 1 0 to 0 5 wc 0 75 to 0 25 wc 0 5 to 0 wc 0 25 to 0 25 wc 0 to 0 5 wc 0 5 to 1 0 wc The alarm also has settings for on delay and off delay which can be set via the menu Both of these default to 5 seconds but may be changed fr...

Страница 5: ... 3 seconds If booth pressure ports are close to zero pressure open to ambient then the device will calibrate with a new zero point SETUP MENU OPERATION The setup menu can be accessed by pressing the internal MENU key at any time after the start up mode The system suspends operation when in the menu and holds the last pressure value on the output If an alarm condition was present then it will be re...

Страница 6: ...IGHT MENU The LCD backlight defaults to 1 on It can be toggled to 0 off using UP or DOWN MENU Press to advance to next menu item 11 ALARM TEST MENU The alarm off delay defaults to 5 seconds It can be changed from 1 59 seconds and 1 10 minutes using UP or DOWN MENU Press to advance to next menu item 7 ALARM OFF DELAY MENU OFF The default BACnet MAC address is 3 This can be changed from 0 to 127 usi...

Страница 7: ... LCD 0 45 digit height unit symbols and backlight Wiring Connections Screw terminal block 14 to 22 AWG Pressure Connections Ports for 1 16 ID tubing 1 8 ID adapters included Enclosure White ABS IP30 NEMA 1 84mm W x 119mm x 29mm H 3 3 x 4 7 x 1 15 Weight 115g 4oz Country of Origin Canada POWER SUPPLY Power Supply 24 Vac dc 10 Power Consumption 70 mA max with alarms on INTERFACE Communication 2 wire...

Отзывы: