CALIBRATION

All pressure ranges are factory calibrated and no calibration is necessary. The user may adjust the zero 

point if desired when changing ranges for example. Make sure the unit is warmed up for at least 10 

minutes (1 hour is best) before making a zero adjustment. With both ports open to the ambient pressure, 

press and hold the ZERO button for at least 3 seconds.  Release the button after at least 3 seconds and 

the device will calculate and store the new zero point.

Generally, it is not recommended that the span calibration be performed in the field unless a high quality 

calibrator with low differential pressure ranges is available and the temperature of the sensor can be 

maintained. Contact the factory for information on this type of calibration.

SPECIFICATIONS

Pressure Ranges .............................±4", ±2", ±1", 0-4", 0-2", 0-1" WC
 

±8", ±5", 0-8", 0-5", 0-3" WC

 

±12", ±10", ±6", 0-12", 0-10", 0-6" WC

 

±20", ±15", ±10", 0-20", 0-15", 0-10" WC

 

±1000 Pa, ±500 Pa, ±250 Pa, 0-1000 Pa, 0-5000 Pa, 0-250 Pa

 

±2000 Pa, ±1000 Pa, ±500 Pa, 0-2000 Pa, 0-1000 Pa, 0-500 Pa

 

(6 per model, switch selectable)

Accuracy ...........................................±1% F.S. of selected range (minimum range is ±1.5 %F.S.)
 

@ 22°C (72°F) including hysteresis, non-linearity and repeatability

Measurement Type .......................Differential (single port), Static, Velocity, & Total Pressure
Response Time ...............................250 ms
Stability .............................................<±0.5% F.S./year typical
Thermal Effects ...............................<±3% over compensated range
Compensated Range....................0 to 50°C (32 to 122°F)
Proof Pressure .................................40" W.C. (100" for 10" & 20" models)
Burst Pressure .................................60" W.C. (200" for 10" & 20" models)
Operating Conditions ..................0 to 50°C (32 to 122°F), 5 to 95 %RH, non-condensing
Power Supply ..................................20-28 Vac/dc (non-isolated half-wave rectified)
Supply Current ...............................<4 mA for voltage output, 20 mA max for current output
Input Voltage Effect ......................Negligible over specified operating range
Protection Circuitry .......................Reverse voltage protected and output limited
Output Signal ..................................4-20 mA (2-wire), 0-5 or 0-10 Vdc (3-wire), field selectable
Output Drive @ 24 Vdc ................

Current:

 400Ω max

 

Voltage:

 10KΩ min

Zero Adjustments ..........................Push-button auto-zero
Wiring Connections ......................Screw terminal block (14 to 22 AWG)
Pressure Connection ....................Barbed ports for 5 mm (0.170" ID) flexible tubing
Conduit Connection .....................1/2" NPT conduit or cable gland
Display ...............................................31/2" digit LCD, 0.4" digit height
Enclosure ..........................................Polycarbonate UL94-V0, IP65 (NEMA 4X)
 

F style includes thread adapter (1/2" NPT to M16) and cable gland fitting

Approvals .........................................CE, RoHS
Country of Origin ...........................Canada

follows: 

 

4-20 mA 

Pressure = [(Output current - 4 mA) / 16 mA] x 2 x Range - Offset

 

0-5 Vdc 

Pressure = (Output voltage / 5 V) x 2 x Range - Offset

 

0-10 Vdc 

Pressure = (Output voltage / 10 V) x 2 x Range - Offset

In the case of ± 2” wc, 4 mA or 0 V = -2” wc and 20 mA or 5 V or 10 V = +2” wc. Since the transmitter is 

linear, 0” wc would be 12 mA or 2.5 V or 5 V.

IN-GE-LPXXXS-02

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

Содержание LP-S

Страница 1: ...ace around the unit to connect the pressure tubing without kinking and to make the electrical connections avoid locations with severe vibrations or excessive moisture Drill a hole in the duct and insert so the probe point is facing into the air flow The enclosure has a standard opening for a 1 2 conduit and may be installed with either conduit and a conduit coupler or a cable gland type fitting Se...

Страница 2: ...signal is available on the OUT terminal This signal is switch selectable for either a voltage output or a standard loop powered 4 20 mA output signal type When voltage mode is selected either 0 5 Vdc or 0 10 Vdc can also be selected These options are clearly indicated on the device circuit board The analog output signal is typically connected directly to the Building Automation System B A S and us...

Страница 3: ...ng it off but be careful not to cut the fitting or an air leak may occur POWER UP INSTRUCTION Before turning on the power verify all wiring to ensure that it complies with one of the included wiring diagrams and verify that the output signal type is correctly selected with the switches Also review the specifications to ensure the power supply is correct and that the pressure is within the correct ...

Страница 4: ... Thermal Effects 3 over compensated range Compensated Range 0 to 50 C 32 to 122 F Proof Pressure 40 W C 100 for 10 20 models Burst Pressure 60 W C 200 for 10 20 models Operating Conditions 0 to 50 C 32 to 122 F 5 to 95 RH non condensing Power Supply 20 28 Vac dc non isolated half wave rectified Supply Current 4 mA for voltage output 20 mA max for current output Input Voltage Effect Negligible over...

Страница 5: ...D IN CANADA 116 5 mm 4 58 99 7 mm 3 93 0 5 NPT 96 27 mm 3 79 49 27 mm 1 94 112 5 mm 4 43 53 7 mm 2 11 IN GE LPXXXS 02 Copyright Greystone Energy Systems Inc All Rights Reserved Phone 1 506 853 3057 Web www greystoneenergy com ...

Отзывы: