E32.0.05.6C-06
Manual for connection and operation of the GIR 2000 Pt
page 6 of 12
5. Configuration of the output functions
General description and notes to the operating of the menu
By means of
button 1
you can go to the next parameter.
Additionally a given changing in the parameter setting can be confirmed by this button and the new value
will be saved. Afterwards it will be changed to the parameter view again.
By means of
button 2
or
button 3
you can go from the parameter view to the parameter setting and adjust
its value there.
Hint:
The buttons 2 and 3 are featured with a „roll-function„. When pressing the button once the value will be raised
(button 2) by one or lowered (button 3) by one. When holding the button pressed for longer than 1 sec. the value
starts counting up or down, the counting speed will be raised after a short period of time.
The device also features a „overflow-function„, when reaching the upper limit of the range, the device switches to
the lower limit, vice versa.
By means of
button 4
a
given changing will be cancelled in the parameter setting. The changing will be
discarded and the former parameter value will be preserved.
In the parameter view button 4 closes the menu.
Please note:
If you don‟t press any button for more than 10 sec. in the parameter setting, the adjustment will
be cancelled, the changing discarded and it will be changed to the parameter view. If you don‟t
press any button for more than 60 sec. in the menu, the menu will be automatically closed.
5.1. Selection of the output function
- Turn the device on and wait until it completed its built-in seg-
ment test.
- At the same time press the pushbutton on the rear side (but-
ton 5) and button 1 for >2 seconds.
The device displays “
outP
“ ('output').
- Use button 2 or button 3 to select the output function.
According your selection the outlets will be allocated as the following table shows:
Description
To select
as output
Output 1
(change-over
contact)
See chapter
No output, device is
used as display unit
no
off
--
2-point-controller
2P
Switching function 1
5.2
Min-/Max-alarm
AL.F1
Min-/Max-alarm
,
inverse
5.3
- Press button 1
to validate the selected output function. The display shows “
outP
“ again.
Note: Alarm inverse means, that the output will be active when there is no alarm!
Hint:
The settings for the switching and alarm points can be made later in an extra menu (see chapter 5)
5.2. 2-point-controller
This chapter describes how to configure the device as a 2-point-controller and how to adjust the switching
values. This instruction demands that
you selected “
2P
“ as your desired output function like it is explained in
chapter 5.1.
- Press button 1
.
The device will be displaying “
1.on
“ (turn-on-point of switching function 1).
- Use button 2 or button 3
to set the desired value, the device‟s switching function 1 should be turning on.
- Press button 1
to validate your selection. The display shows “
1.on
“ again.
ON/SP
SET
min.
OFF/Hy.
1
2
max.
ALARM
Scale
Analog
CAL
Scale
Analog
CAL
ON/SP
SET
min.
OFF/Hy.
1
2
max.
GIR/GIA
ALARM
SET
1
2