background image

E35.0.01.6C-03                     Manual for connection and operation of the EB 3000                        page 18 of 19

10.2.2. Tab:  control outputs

Here is once again a listing of the measurement channels with allocation to the control outputs. A modifica-
tion or reselection of the channels results via „drag and drop“ or through manually input of the respective
channel number.

  - 

channel-nr.

allocated measurement channel for this output.
( The regulation function is assigned to this

 

measuring value )

  -

switch.-on-point,

switching points of the outputs (can also be modified via EB3000-device keys)

switch.-off-point:

  -

delay

minimum switching delay in seconds after a turn-off until output turns on again

  -

function

switching function of the outputs (in case of error, see chapter 6 – error codes).
The following switching functions are defined:
0 – preference in case of error: switching output off
1 – preference in case of error: switching output on

10.2.3. Tab:  alarm

Here you can examine and redefine the adjusted alarm limits for each measurement channel. By pushing the
„edit“ button next to the respective measurement channel you reached a second dialogue window.
Adjustable are following values:

minimum alarm limit (alarm min)

maximum alarm limit (alarm max)

alarm delay (declaration in minutes)

Содержание EB 3000

Страница 1: ...B 3000 page 1 of 19 Manual for connection and operation of EASYBus control display and supervisory device EB 3000 as of Version 1 7 GREISINGER electronic GmbH D 93128 Regenstauf Hans Sachs Stra e 26 T...

Страница 2: ...sioning of the EB3000 8 6 OPERATION OF THE EB3000 8 6 1 How to display the current measurement values 8 6 2 How to display or reset the min max values 9 6 3 Setting of switching points 9 6 4 Setting o...

Страница 3: ...evice must be switched off and must be marked against using again in case of obvious malfunc tions of the device which are e g visible damage no prescripted working of the device storing the device un...

Страница 4: ...terfaces EASYBUS output connection for the EASYBUS sensor modules EASYBUS input permits via level converter e g EBW1 EBW64 communication with a superior computer master The EB3000 cyclically enquires...

Страница 5: ...setting setting mode selection 3 Key 4 interruption recognition of the last setting acknowledgement of an error message 4 Main display indication of current measurement value resp min max value 5 Aux...

Страница 6: ...1 Switching output 3 normally open 10 Switching output 4 normally open 9 Alarm output normally closed 8 Alarm output normally open 7 Alarm output common connector 6 Supply voltage 230VAC 5 Supply volt...

Страница 7: ...y 2 EASYBUS standard loads EBN 2 EASYBUS standard loads EBHT EBT EBH 1 5 EASYBUS standard loads GIA20EB GIR2002 1 EASYBUS standard load W hen connecting the modules keep in mind that the sum of all bu...

Страница 8: ...calculation functions choose register tab virtual channels for programming the desired func tion for virtual channel 1 or 2 For details see chapter 9 EB3000 Configuration 6 Operation of the EB3000 Hin...

Страница 9: ...off point In the auxiliary display the text of the allocated channel appears Use key 1 to select the adjustable switching parameter Push key 2 or 3 In the main display the currently adjusted switching...

Страница 10: ...the main display AL Lo appears again With key 4 you can cancel the setting at any time the made modification is resetted and in the main display AL Lo appears again Press key 1 again and the adjusted...

Страница 11: ...ossible causes Incorrect scale Counter overflow Remedies The error message will be reset if the display value is below 9999 Reset the counter When happening frequently check the scale setting maybe it...

Страница 12: ...ion error CRC Code wrong Indicates that the enquiry of an attached EASYBUS measurement channel has generated an CRC error Possible causes multiple attached EASYBUS measurement channels have the same a...

Страница 13: ...rformed incorrect configuration bus is blocked in fact of a master requiry Remedies remove alarm by pushing key 4 or by using EASYBUS Configurator software perform new configuration of the EB3000 The...

Страница 14: ...lly adjustable Alarm output 1 relay output changeover Switching capacity 230VAC 5A ohmic load Alarm functions Collective alarm for all sensors alarm settings for all sensors changeable Displays Main d...

Страница 15: ...d system configuration In this case the following described EB3000 configuration must be performed again Afterwards you reached the EB3000 configuration window displayed on next page with all availabl...

Страница 16: ...19 10 2 EB3000 Configuration By double click on the EB3000 symbol on the device overview a configuration window for the EB3000 opens Now 5 register tabs are available monitoring display control outpu...

Страница 17: ...not too low to avoid error messages of the measurement system 2 Predetermination of the display of individual channels auxiliary display channel description for the respective channel shown in the aux...

Страница 18: ...e modified via EB3000 device keys switch off point delay minimum switching delay in seconds after a turn off until output turns on again function switching function of the outputs in case of error see...

Страница 19: ...l functions for download are available After download copy transferred datafiles easily into directory EB3CV inside of the configurator installation directory By the next start of register tab virtual...

Отзывы: