Link-Belt MG-534 Calibration
16
W450160 10/07
When prompted, press the key adjacent to
Yes! Calibrate!
to
zero the sensor, otherwise press the key adjacent to
No, Exit/
Abort
to cancel.
When it has finished, the display should show “Zero No. 3 0”
Press the key adjacent to
Exit
to return to the main menu.
LOAD
0.8
ANGLE
41.8
RADIUS
76.2 FT
LENGTH
106.0
Yes! Calibrate!
Zero Sensor
No, Exit / Abort
Exit
LOAD
0.8
ANGLE
41.8
RADIUS
76.2 FT
LENGTH
106.0
Zero No.3 0
Zero Sensor
Menu Up
Menu Down
Exit