  2.0  Installation Instructions

 

2.1 

General Preparation

 

2.1.1

 

The Vireo HR155WM / HR155CM unit is supplied with 4 x 125mmØ spigots.

125mm ducting with connectors can be used 

(see Ancillary Section page 3)

 to provide performance 

levels required for compliance with Building Regulations. 

 

2.1.2

 

The Vireo HR185WM unit is supplied with 4 x 150mmØ spigots.

150mm ducting with connectors can be used 

(see Ancillary Section page 3)

 to provide performance 

levels required for compliance with Building Regulations. 

 

2.1.3

 

Installation of the unit should be in accordance with the current editions of Building Regulations, NHBC 

Compliance Guide and BS7671: IEE Wiring Regulations.

 

2.1.4

 

The design, material specification and installation must only be carried out by "competent persons". Electrical 

installation must be carried out by a qualified Electrician.

 

2.1.5

 

IMPORTANT NOTE: Gases from fuel-burning equipment must not be drawn 
into any living areas. If any room, where air is extracted, contains a fuel-
burning appliance such as a central heating boiler, then either of the following 
should be undertaken:

The flue must be of the room sealed or balanced flue type or; 

Allowance must be made for an adequate supply of air into the room.

 

2.2 Positioning

 

2.2.1

 

The Vireo HR155WM / HR185WM unit must be installed vertically and can be either wall or floor mounted to 

enable effective condensate drainage in either a kitchen/service cupboard or secured to a vertical structure 

in the loft space. If located within a cold space, it is recommended that the bottom of the unit is insulated to 

prevent freezing around the condensate connection. Duct spigots must be upright at top of unit.

 

2.2.2

 

The Vireo HR155CM unit must be installed horizontally with the fixing brackets provided. The unit is not 

intended for installation within a utility room.

5

 

 

1.2.3

 

Vireo HR185WM

839

60

550

Vireo HR185WM front

899

555

150

Vireo HR185WM side

Front View

Side View

Содержание Vireo HR155CM

Страница 1: ...185WM Mechanical Ventilation with Heat Recovery Installation Instructions Commissioning Data To be completed by the Commissioning Engineer Refer to User Homeowner Guide also supplied Vireo HR155WM Vir...

Страница 2: ...aration 5 Positioning 5 Configuration 6 Mounting 7 Access Dimension for Maintenance 9 Condensate Drain 10 Ducting Guidelines 11 Electrical 12 Wiring The Unit 13 Connecting to the BMS 13 3 0 On Site Co...

Страница 3: ...used where appropriate 150mm Ducting rectangular ducting can be used where appropriate GS2 Hardwired switch providing switching between low and high option GS2 Hardwired switch providing switching be...

Страница 4: ...This product may not be treated as household waste Instead it should be handed to an appropriate collection point for the recycling of electrical and electronic equipment For more detailed informatio...

Страница 5: ...s from fuel burning equipment must not be drawn into any living areas If any room where air is extracted contains a fuel burning appliance such as a central heating boiler then either of the following...

Страница 6: ...equire any internal changes See Figures overleaf for ducting configuration 2 3 Configuration Note To change the handing of the unit follow the simple steps within the Commissioning Wizard See Section...

Страница 7: ...n kitchen cupboard There should be no movement once correctly located and the filters should be accessible from easily removing the panels on the front of the unit See Section 4 1 8 and 4 2 0 Homeowne...

Страница 8: ...bracket on the back of the unit See Figure 3 Securely locate brackets together Figure 2 Figure 3 2 4 8 Tighten loose screws until the unit is securely fitted See Figure 4 add an additional two screws...

Страница 9: ...Maintenance 2 5 1 Footprint of Vireo HR155WM Wall Mounted 500mm HR155WM Top View 2 5 2 Footprint of Vireo HR155CM Ceiling Mounted 500mm HR155CM Side View 2 5 3 Footprint of Vireo HR185WM Wall Mounted...

Страница 10: ...steps are taken to minimise the risk of mechanical damage to the drainage pipe work IMPORTANT NOTE The condensate drain must incorporate a U bend to create an air block and avoid leakage of smells ba...

Страница 11: ...be insulated with at least 25mm of insulation 2 7 4 If applicable Fire Dampers MUST BE FITTED in accordance with Part B of the Building Regulations 2 7 5 Rigid Ducting Install using the least number...

Страница 12: ...tch having a minimum contact separation of 3 0mm must be used to provide isolation for the unit 2 8 5 The recommended switches for use with this product are the Greenwood Airvac GS2 Optional 2 positio...

Страница 13: ...ol Options via the Building Management System BMS 2 9 2 To wire into to the BMS connector within the Vireo unit first remove the electrical wiring cover as per Fig 15 17 below then locate the BMS conn...

Страница 14: ...Free normally closed contact 5 N O Volt Free normally open contact 6 Common Relay common Figure 18 Close up of PCB with BMS connection points Figure 19 GRC1 Controller Figure 20 BMS Wiring Diagram No...

Страница 15: ...clamp down with screw fixings 1 2 3 4 5 1 2 3 4 5 Figure 21 Securing BMS Wiring Cable not supplied 2 9 5 Refit electrical cover taking care gasket seal underneath is seated correctly and cable is not...

Страница 16: ...TUP COMMISSIONING WIZARD Below are examples explanations of what you would see through the Commissioning Wizard P SETUP COMMISSIONING WIZARD O R T C O N F I G R H Example 1 Function selection screen T...

Страница 17: ...p a Factory airflow set at 66 rotate button to required airflow b Press button to select c Rotate button and choose FWD to move to next section or BACK to return to set up d Press button to select E X...

Страница 18: ...low and high speed settings Performance levels can be verified at both extract and supply air valves using an appropriate method such as a rotating vane anemometer and air cone kit Record airflow rate...

Страница 19: ...on to Exit press button to confirm 3 1 10 To Modify Summer ByPass Activation Temperature When the internal and external temperature conditions are met the unit will try to maintain an indoor comfort t...

Страница 20: ...vac Central Demand Control with 1 sensor 77 3 38 4 13 5 A A E Bidirectional Variable Speed Recuperative 90 279 77 154 50 191 53 50 0 33 0 85 Internal 2 7 External 2 9 Details within Homeowner Guide ww...

Страница 21: ...2 Greenwood Airvac Central Demand Control with 1 sensor 77 2 38 3 13 3 A A E Bidirectional Variable Speed Recuperative 90 245 68 133 48 173 48 50 0 34 0 85 Internal 2 7 External 2 9 Details within Ho...

Страница 22: ...Greenwood Airvac Central Demand Control with 1 sensor 78 8 39 6 14 6 A A E Bidirectional Variable Speed Recuperative 91 313 87 156 52 220 61 50 0 29 0 85 Internal 2 4 External 2 3 Details within Home...

Страница 23: ...his Greenwood product Vireo HR155WM HR155CM HR185WM has a 2 Year Guarantee 5 1 2 This does not affect your statutory rights 5 1 3 Full details available on request from 44 0 1276 408404 or www greenwo...

Страница 24: ...n is believed correct at time of going to press E OE All goods are sold according to Zehnder Group UK Ltd s Standard Conditions of Sale which are available on request All dimensions referred to are in...

Отзывы: