 3.1.4

 

Commissioning Wizard

   

To progress through the commissioning wizard, rotate the controls central button to required configuration 

and press the button to select (at each section the text will flash until it has been selected, whereby it will then 

go solid).  You can move backwards and forwards throughout the process until all settings are correct.

When first turning the power onto the unit, the "Setup Wizard" prompt will be shown.

Press the central button to start the commissioning wizard. 

Refer to design drawings for setting up the required rates. 

   

The steps of the wizard are as follows:

P O R T

C O N F I G :

< R H >

Step 1

Port Configuration Set-up

a

Rotate button to choose either RH (Right Hand Configuration) or 

 

LH (Left Hand Configuration)

b

Press button to select

c

Rotate button and choose FWD to move to next section or BACK to 

return to set-up

d

Press button to select

E X T R A C T

H I G H

< 6 6 % >

Step 2

Extract High Set-up

a

Factory airflow set at 66%, rotate button to required airflow %

b

Press button to select

c

Rotate button and choose FWD to move to next section or BACK to 

return to set-up

d

Press button to select

S U P P L Y

H I G H

< 6 6 % >

Step 3

Supply High Set-up

a

Factory airflow set at 66%, rotate button to required airflow %

b

Press button to select

c

Rotate button and choose FWD to move to next section or BACK to 

return to set-up

d

Press button to select

E X T R A C T

L O W

< 3 3 % >

Step 4

Extract Low Set-up

a

Factory airflow set at 33%, rotate button to required airflow %

b

Press button to select

c

Rotate button and choose FWD to move to next section or BACK to 

return to set-up

d

Press button to select

S U P P L Y

L O W

< 3 3 % >

Step 5

Supply Low Set-up

a

Factory airflow set at 33%, rotate button to required airflow %

b

Press button to select

c

Rotate button and choose FWD to move to next section or BACK to 

return to set-up

d

Press button to select

H U M I D I S M A R T

< O N

>

Step 6

Greenwood HumidiSMART

TM

 Set-up

a

Rotate button to choose either ON or OFF

b

Press button to select

c

Rotate button and choose FWD to move to next section or BACK to 

return to set-up

d

Press button to select

T I M E R S M A R T

< O N

>

Step 7

Greenwood TimerSMART

TM

 Set-up

a

Rotate button to choose either ON or OFF

b

Press button to select

c

Rotate button and choose FWD to move to next section or BACK to 

return to set-up

d

Press button to select

S E T U P

C O M P L E T E

< b a c k

e x i t >

Step 8

Commissioning Set-up Wizard Completion

a

Rotate button to choose either EXIT to complete commissioning or 

BACK to return to set-up 

b

Press button to select

Содержание Vireo HR155CM

Страница 1: ...185WM Mechanical Ventilation with Heat Recovery Installation Instructions Commissioning Data To be completed by the Commissioning Engineer Refer to User Homeowner Guide also supplied Vireo HR155WM Vir...

Страница 2: ...aration 5 Positioning 5 Configuration 6 Mounting 7 Access Dimension for Maintenance 9 Condensate Drain 10 Ducting Guidelines 11 Electrical 12 Wiring The Unit 13 Connecting to the BMS 13 3 0 On Site Co...

Страница 3: ...used where appropriate 150mm Ducting rectangular ducting can be used where appropriate GS2 Hardwired switch providing switching between low and high option GS2 Hardwired switch providing switching be...

Страница 4: ...This product may not be treated as household waste Instead it should be handed to an appropriate collection point for the recycling of electrical and electronic equipment For more detailed informatio...

Страница 5: ...s from fuel burning equipment must not be drawn into any living areas If any room where air is extracted contains a fuel burning appliance such as a central heating boiler then either of the following...

Страница 6: ...equire any internal changes See Figures overleaf for ducting configuration 2 3 Configuration Note To change the handing of the unit follow the simple steps within the Commissioning Wizard See Section...

Страница 7: ...n kitchen cupboard There should be no movement once correctly located and the filters should be accessible from easily removing the panels on the front of the unit See Section 4 1 8 and 4 2 0 Homeowne...

Страница 8: ...bracket on the back of the unit See Figure 3 Securely locate brackets together Figure 2 Figure 3 2 4 8 Tighten loose screws until the unit is securely fitted See Figure 4 add an additional two screws...

Страница 9: ...Maintenance 2 5 1 Footprint of Vireo HR155WM Wall Mounted 500mm HR155WM Top View 2 5 2 Footprint of Vireo HR155CM Ceiling Mounted 500mm HR155CM Side View 2 5 3 Footprint of Vireo HR185WM Wall Mounted...

Страница 10: ...steps are taken to minimise the risk of mechanical damage to the drainage pipe work IMPORTANT NOTE The condensate drain must incorporate a U bend to create an air block and avoid leakage of smells ba...

Страница 11: ...be insulated with at least 25mm of insulation 2 7 4 If applicable Fire Dampers MUST BE FITTED in accordance with Part B of the Building Regulations 2 7 5 Rigid Ducting Install using the least number...

Страница 12: ...tch having a minimum contact separation of 3 0mm must be used to provide isolation for the unit 2 8 5 The recommended switches for use with this product are the Greenwood Airvac GS2 Optional 2 positio...

Страница 13: ...ol Options via the Building Management System BMS 2 9 2 To wire into to the BMS connector within the Vireo unit first remove the electrical wiring cover as per Fig 15 17 below then locate the BMS conn...

Страница 14: ...Free normally closed contact 5 N O Volt Free normally open contact 6 Common Relay common Figure 18 Close up of PCB with BMS connection points Figure 19 GRC1 Controller Figure 20 BMS Wiring Diagram No...

Страница 15: ...clamp down with screw fixings 1 2 3 4 5 1 2 3 4 5 Figure 21 Securing BMS Wiring Cable not supplied 2 9 5 Refit electrical cover taking care gasket seal underneath is seated correctly and cable is not...

Страница 16: ...TUP COMMISSIONING WIZARD Below are examples explanations of what you would see through the Commissioning Wizard P SETUP COMMISSIONING WIZARD O R T C O N F I G R H Example 1 Function selection screen T...

Страница 17: ...p a Factory airflow set at 66 rotate button to required airflow b Press button to select c Rotate button and choose FWD to move to next section or BACK to return to set up d Press button to select E X...

Страница 18: ...low and high speed settings Performance levels can be verified at both extract and supply air valves using an appropriate method such as a rotating vane anemometer and air cone kit Record airflow rate...

Страница 19: ...on to Exit press button to confirm 3 1 10 To Modify Summer ByPass Activation Temperature When the internal and external temperature conditions are met the unit will try to maintain an indoor comfort t...

Страница 20: ...vac Central Demand Control with 1 sensor 77 3 38 4 13 5 A A E Bidirectional Variable Speed Recuperative 90 279 77 154 50 191 53 50 0 33 0 85 Internal 2 7 External 2 9 Details within Homeowner Guide ww...

Страница 21: ...2 Greenwood Airvac Central Demand Control with 1 sensor 77 2 38 3 13 3 A A E Bidirectional Variable Speed Recuperative 90 245 68 133 48 173 48 50 0 34 0 85 Internal 2 7 External 2 9 Details within Ho...

Страница 22: ...Greenwood Airvac Central Demand Control with 1 sensor 78 8 39 6 14 6 A A E Bidirectional Variable Speed Recuperative 91 313 87 156 52 220 61 50 0 29 0 85 Internal 2 4 External 2 3 Details within Home...

Страница 23: ...his Greenwood product Vireo HR155WM HR155CM HR185WM has a 2 Year Guarantee 5 1 2 This does not affect your statutory rights 5 1 3 Full details available on request from 44 0 1276 408404 or www greenwo...

Страница 24: ...n is believed correct at time of going to press E OE All goods are sold according to Zehnder Group UK Ltd s Standard Conditions of Sale which are available on request All dimensions referred to are in...

Отзывы: