STATIC AND STATIC WITH MOTORIZED DAMPERS MODELS 

Sloped Drain

Pan

drainage system

Greentek

TM

HRV units are

equipped with an easy-access

sloped drain pan. Excess 

condensation that might 

accumulate inside the unit migrate to 
the centre of the drain pan to be 
evacuated.

9.Condensation Drain Line

Insert the threaded drain adapter thru the bottom of the HRV  and hand tighten the plastic nut sup-
plied with the drain kit.

Install the condensate line (10 feet included in drain kit). Insert condensate tubing by pushing clear
plastic line over drain adapter. Make condensate trap by looping the clear plastic tubing. This proce-
dure is to avoid foul odor to enter the HRV .

figure 9.1

Hand screw the drain adapter

figure 9.2  Insert condensate line

figure 9.3

Make a loop in 
condensate line

figure 9.4

Use a condensate 
pump if you don’t 
have access to the 
floor drain

Содержание SH 0.12

Страница 1: ...ST A TIC AND ST A TIC WITH MOT ORIZED DAMPERS MODELS INST ALLA TION GUIDE Horizontalseries MODEL SHTM MODEL SHMTM MODEL SHMTM MODEL SHTM...

Страница 2: ...ance 15 Accessories 16 Wiring Diagram Model SHM only 17 Specification and Technical Information P AGE 2 GreentekTM Peace of Mind Limited WARRANTY All GreentekTM products are backed by the best limited...

Страница 3: ...intake A Room Count Calculation B Air Change per Hour Method 2 Typical Installation 1 Ventilation Needs LIVING SPACE Master Bedroom With Basement Without Basement Single Bedroom Living Room Dinning R...

Страница 4: ...airflow is not as indicated flip the core to the appropriate side Note To install the core unit accordigly to with the airflow locate the four arrows on the core decal and read the directions Side A...

Страница 5: ...for HRV Figure 3 2 Installation kit is shipped inside the unit Figure 3 3 Installation kit The HRV unit should be installed in a mechanical room or as close to an outside wall as possible This would a...

Страница 6: ...installer If unit is not level improper drainage will occur and could lead to moisture and leakage problems GreentekTM TIPS to installer Always use rigid ducting between HRV and the forced air system...

Страница 7: ...nstallation to the unit Take four collars out of the unit Insert the flex over the interior flange of the collar Make sure that flex is pushed all the way so the four tabs on the collar hooks on to th...

Страница 8: ...2 Align the damper in the fully closed position figure 8 3 Using a 1 8 Allen key tool inserted in the locking screw rotate the coupling slightly clockwise just enough to exert a slight torque on the d...

Страница 9: ...apter thru the bottom of the HRV and hand tighten the plastic nut sup plied with the drain kit Install the condensate line 10 feet included in drain kit Insert condensate tubing by pushing clear plast...

Страница 10: ...TIPS to installer Extend the sheet metal sleeve 1 5 inside the home Attach GreentekTM specialty ISFTM collar to sheet metal sleeve 10 Outside Hoods figure 10 1 Locating Outside Hoods 72 18 figure 10 4...

Страница 11: ...proper readings mount the air flow grid inside a rigid ducting at a minimum of 18 inches from the unit This will avoid getting unstable airflow witch could offset the readings Figure 11 2 Step 2 Star...

Страница 12: ...ll toll free 1 888 724 5211 or visit us at www greentek ca P AGE 12 12 Controls Model SHMTM Only 13 Troubleshooting Control The GreenThinkerTM model control is offered with features making your ventil...

Страница 13: ...ation accessories and products by Imperial Air Technologies Inc 15 Accessories figure 15 1 VentilationAccessories When should I Service my HRV service and accessories HEA T RECOVERY CORE UNIT Once a y...

Страница 14: ...der thermostats energizing the R and G terminals at the forced air system has the effect of energizing the Y termi nal at the thermostat and therby activat ing the coolong system If you identify this...

Страница 15: ...tified technician or electrician 211 2 237 8 17 Specification and Technical Information SPECIFICA TIONS Size Heat exchanger L x H x W CFM Type of heat exchanger SH 0 8 SH 0 12 237 8 x211 2 x113 8 237...

Страница 16: ...icmaterialswheneverpossible Imperial Air Technologies inc 500 Ferdinand Blvd Dieppe NB Canada E1A 6B9 Toll free 1 888 724 5211 Visit us at www greentek ca ITEM 100320 REF 0503 004 Protectthenaturalwor...

Отзывы: