background image

PAGE 3

STATIC AND STATIC WITH MOTORIZED DAMPERS MODELS 

Determine Your

Ventilation Needs

installation

How much fresh air do I need?  Good air
quality is based  in part on the capacity of
the home’s ventilation system.  

Usually, the HRV’s capacity is measured in
CFM (Cubic Feet per Minutes) or L/s
(Liters per Seconds) of fresh air being 
distributed in the living space.  The Room
Count Calculation or the Air Change per
Hour Method shows you how to 
determine your ventilation needs.

Air Volume

Needed

installation

In a typical installation there must be an
adequate air volume passing through the
unit in proportion of the pressure from
the heating system.  

Exemple: On the warm side*, the air vol-
ume needed is based on a 26’ rigid duct.
On the cold side*, the proportional eqiva-
lent is 18’ of rigid duct.

*  Between the model SH and the 

forced air system.

**Between the model SH and the 

outside intake.

A. Room Count Calculation

B. Air Change per Hour Method

2. Typical Installation  

1.Ventilation Needs

LIVING SPACE

Master Bedroom
With Basement
Without Basement
Single Bedroom
Living Room
Dinning Room
Family Room
Recreation Room
Other

Kitchen
Bathroom
Laundry Room
Utility Room

TOTAL cu ft X 0.3 per hr = total

Take total and divide by 60 to get CFM

Number of Rooms

CFM (L/s)

CFM Required

x 20 cfm (10 L/s)

=  

x 20 cfm (10 L/s)

=  

x 10 cfm (5 L/s)

=  

x 10 cfm (5 L/s)

=  

x 10 cfm (5 L/s)

=  

x 10 cfm (5 L/s)

x 10 cfm (5 L/s)

x 10 cfm (5 L/s)

x 10 cfm (5 L/s)

=   

x 10 cfm (5 L/s)

=  

x 10 cfm (5 L/s)

x 10 cfm (5 L/s)

TOTAL ventilation requirement 

(add last column)     =

25’ x 40’ house with basement
1,000 sq. ft. x 8’ high x 2 

(1

st

floor = basement)= 

16,000 cu. ft.

16,000 sq. ft. x 0.3 ACH 

4,800 cu. ft.

4,800 sq. ft. / 60 Minutes 

80 CFM

1 CFM = 0.47189 L/s

1 L/s = 3.6 m

3

/hr

80 CFM is your ventilation needs

Example: 

VENTILATION PERFORMANCE - MODEL SH

0.25

0.20

0.15

0.10

0.05

0.00

Supply

Return

60        70         80        90       100

Ft

3

/min. of HRV (Exhaust)

Supply    

SUPPL

Y (“W

.C.)

0.25

0.20

0.15

0.10

0.05

0.00

60        70         80        90       100

Ft

3

/min. of HRV (Fresh Air Intake)

Return

RETURN (“W

.C.)

Содержание SH 0.12

Страница 1: ...ST A TIC AND ST A TIC WITH MOT ORIZED DAMPERS MODELS INST ALLA TION GUIDE Horizontalseries MODEL SHTM MODEL SHMTM MODEL SHMTM MODEL SHTM...

Страница 2: ...ance 15 Accessories 16 Wiring Diagram Model SHM only 17 Specification and Technical Information P AGE 2 GreentekTM Peace of Mind Limited WARRANTY All GreentekTM products are backed by the best limited...

Страница 3: ...intake A Room Count Calculation B Air Change per Hour Method 2 Typical Installation 1 Ventilation Needs LIVING SPACE Master Bedroom With Basement Without Basement Single Bedroom Living Room Dinning R...

Страница 4: ...airflow is not as indicated flip the core to the appropriate side Note To install the core unit accordigly to with the airflow locate the four arrows on the core decal and read the directions Side A...

Страница 5: ...for HRV Figure 3 2 Installation kit is shipped inside the unit Figure 3 3 Installation kit The HRV unit should be installed in a mechanical room or as close to an outside wall as possible This would a...

Страница 6: ...installer If unit is not level improper drainage will occur and could lead to moisture and leakage problems GreentekTM TIPS to installer Always use rigid ducting between HRV and the forced air system...

Страница 7: ...nstallation to the unit Take four collars out of the unit Insert the flex over the interior flange of the collar Make sure that flex is pushed all the way so the four tabs on the collar hooks on to th...

Страница 8: ...2 Align the damper in the fully closed position figure 8 3 Using a 1 8 Allen key tool inserted in the locking screw rotate the coupling slightly clockwise just enough to exert a slight torque on the d...

Страница 9: ...apter thru the bottom of the HRV and hand tighten the plastic nut sup plied with the drain kit Install the condensate line 10 feet included in drain kit Insert condensate tubing by pushing clear plast...

Страница 10: ...TIPS to installer Extend the sheet metal sleeve 1 5 inside the home Attach GreentekTM specialty ISFTM collar to sheet metal sleeve 10 Outside Hoods figure 10 1 Locating Outside Hoods 72 18 figure 10 4...

Страница 11: ...proper readings mount the air flow grid inside a rigid ducting at a minimum of 18 inches from the unit This will avoid getting unstable airflow witch could offset the readings Figure 11 2 Step 2 Star...

Страница 12: ...ll toll free 1 888 724 5211 or visit us at www greentek ca P AGE 12 12 Controls Model SHMTM Only 13 Troubleshooting Control The GreenThinkerTM model control is offered with features making your ventil...

Страница 13: ...ation accessories and products by Imperial Air Technologies Inc 15 Accessories figure 15 1 VentilationAccessories When should I Service my HRV service and accessories HEA T RECOVERY CORE UNIT Once a y...

Страница 14: ...der thermostats energizing the R and G terminals at the forced air system has the effect of energizing the Y termi nal at the thermostat and therby activat ing the coolong system If you identify this...

Страница 15: ...tified technician or electrician 211 2 237 8 17 Specification and Technical Information SPECIFICA TIONS Size Heat exchanger L x H x W CFM Type of heat exchanger SH 0 8 SH 0 12 237 8 x211 2 x113 8 237...

Страница 16: ...icmaterialswheneverpossible Imperial Air Technologies inc 500 Ferdinand Blvd Dieppe NB Canada E1A 6B9 Toll free 1 888 724 5211 Visit us at www greentek ca ITEM 100320 REF 0503 004 Protectthenaturalwor...

Отзывы: