AC Current Measurement
Electrical Shock Hazard.
Contact with live circuits will result in severe injury
or death.
1. Set the slide switch to the “A” position.
2. Press the trigger to open the jaws. Clamp around one conductor only.
Make sure that the jaws are firmly closed around the conductor.
3. Read the value from the digital display.
AC Voltage Measurement
~
~
Electrical Shock Hazard.
Contact with live circuits will result in severe injury
or death.
1. Set the slide switch to the “V” position.
2. Connect the black test lead to the COM terminal and the red test lead to the
V -
Ω
terminal.
3. Connect the test leads across the source load being measured.
4. Read the value from the digital display.