background image

XG-Dual Duct VAV Terminals Rev 2

4

Important

If equipped with pneumatic controls, the orientation of the 

XG-Dual Duct Air Terminal unit is critical. The pneumatic controls 

must be mounted right side up. The XG-Dual Duct Air Terminal 

must be level or – 10 degrees of horizontal, both parallel 

to the air flow and at right angle of air flow. The control side of 

the XG-Dual Duct Air Terminal is labeled with an arrow indicat-

ing up. Unless otherwise noted, most electric, analog electronic 

and digital are not position sensitive and may be installed in any 

orientation. 

Minimum Clearance for Access

XG-Dual Duct Air Terminals require sufficient space to allow 
servicing of the controls. Horizontal clearance requirements are 
dependent upon access panel dimensions which are indicated on 
the appropriate submittal. For control panel access, a minimum 
of 18” is recommended. See the appropriate submittal for control 
panel location.

Note

:

 These clearances recommendations are not meant 

to preclude NEC requirements or local building codes that 

may be applicable, which are the responsibility of the installing 

contractor.

Connecting Duct Work

1.  Slip each inlet duct over the inlet collar of the XG-Dual 

Duct Air Terminal. 

2.  Fasten and seal the connection by method prescribed 

by job specification.

3.  The diameter of the inlet duct in inches, must be equal 

to the listed size of the XG-Dual Duct Air Terminal; e.g. 

a duct that actually measures 8 inches must be fitted to 

a size 8 inch Air Terminal. The inlet tube of the XG-Dual 

Duct Air Terminal is manufactured 1/8” smaller than the 

listed size in order to fit inside the duct.

Note

:

 Do not insert duct work inside the inlet collar of the 

XG-Dual Duct Air Terminal. Inlet duct should be installed in 

accordance with SMACNA guidelines.

4.  If an inlet air flow sensor is installed, it is recom-

mended the installer provide a minimum of 3 duct diam-

eters of straight duct at the XG-Dual Duct Air Terminal 

inlet.

5.  The outlet end of the XG-Dual Duct Air Terminal is de-

signed for use with flanged outlet connections. 

(Slip and 

drive outlet connection is optional.)

6.  A rectangular duct the size of the XG-Dual Duct Air 

Terminal outlet should be attached. 

(Refer to submittal 

for correct size.)

Field Electrical Wiring

 

5

All field wiring must comply with local building codes and 

NEC. (ANSI/NFPA 70-2002)

 

5

When Applicable, electrical control and piping diagrams are 

attached to bottom of XG-Dual Duct Air Terminal. 

 

5

Use copper only conductors.

 

5

Air Terminal must be properly grounded per NEC 424-14  

and 250.

 

5

Always check product label for voltage and current data to 

determine the proper wire size and over current protection.

 

5

The control cabinet contains live electrical parts.

 

5

Contacting these parts with power applied may cause seri-

ous injury or even death.

 

5

The control panel cover must be closed or in place before 

applying electric power to the XG-Dual Duct Air Terminal.

 

5

These recommendations are not meant to precluded NEC 

requirements or applicable local building codes and are the 

sole responsibility of the installing contractor.

Controls

For information on controls provided by other manufactures and 
installed on the Air Terminals, contact the local branch or dealer.

Important

Air Terminals with digital controls, if factory programmed, incor-

porate specific communication addresses. Installing the Air Ter-

minal in a different location than noted on the Air Terminal label 

and building plans, may result in excessive start up labor and is 

the sole responsibility of the contractor.

Inlet Flow Sensor

XG-Dual Duct Air Terminals are shipped with factory installed 
(where applicable) pressure differential inlet flow sensors in the 
primary inlet. 

See figure 4

 for calibration curve and K factors.

Содержание XG-Dual

Страница 1: ...mpting to assemble install operate or maintain the product described Protect yourself and others by observing all safety information Failure to comply with these instructions will result in voiding of the product warranty and may result in personal injury and or property damage Phone 715 359 6171 Fax 715 355 2399 Parts 800 355 5354 E mail gfcinfo greenheck com Website www greenheck com ...

Страница 2: ...e 135ºF Caution Do not use the flow sensor connecting tubing or damper shaft as a lift point Damage to the components may result Hanging Installation Requirements 5 The XG Dual Duct Air Terminal should be supported direct ly with straps screwed into the side of the terminal See figure 1 5 Alternate trapeze hangers or the method prescribed for the rectangular duct on the job specification may be us...

Страница 3: ...XG Dual Duct VAV Terminals Rev 2 3 Figure 2 Trapeze Figure 3 Optional Hanger Brackets and Hanger Rods Hanger brackets and Rod 5 16 minimum Primary air inlet ...

Страница 4: ...elines 4 If an inlet air flow sensor is installed it is recom mended the installer provide a minimum of 3 duct diam eters of straight duct at the XG Dual Duct Air Terminal inlet 5 The outlet end of the XG Dual Duct Air Terminal is de signed for use with flanged outlet connections Slip and drive outlet connection is optional 6 A rectangular duct the size of the XG Dual Duct Air Terminal outlet shou...

Страница 5: ...Air Terminal can be due to a variety of condi tions and can be difficult to eliminate 5 The first step is to isolate the type source and direction 5 Generally noise heard at the air outlet is considered a dis charge type 5 Noise heard through the ceiling is considered radiated noise 5 For detailed information concerning noise transmission in buildings refer to AHRI Standard 885 2008 Procedure for ...

Страница 6: ...XG Dual Duct VAV Terminals Rev 2 6 Figure 4 ...

Отзывы: