background image

XG-Fan Powered Air Terminals Rev 2

5

Troubleshooting

Investigating Noise Complaints

 

5

Noise from a XG-Fan Powered Air Terminal can be due to a 

variety of conditions and can be difficult to eliminate.

 

5

The first step is to isolate the type, source and direction.

 

5

Generally, noise heard at the air outlet is considered a dis-

charge type.

 

5

Noise heard through the ceiling is considered radiated noise.

 

5

For detailed information concerning noise transmission in 

buildings, refer to AHRI Standard 885-2008, “Procedure for 

estimating occupied space sound levels in the application 

of Air Terminals and air outlets”.

Discharge Noise

 

5

This is usually caused by high static or little to no internal duct 

lining downstream of the Air Terminal.

 

5

It can sometimes be caused by air outlet itself.

 

5

Air outlet generated sounds can be reduced by reducing flow 

or increasing an outlet size.

 

5

Reducing static pressure, flow or adding additional down-

stream attenuation materials will reduce discharge sounds 

from the Air Terminal.

Radiated Noise 

 

5

Radiated noise is most commonly associated with XG-Fan 

Powered Terminals

.

 

5

The suspension and the ducting of these XG-Fan Powered 

Air Terminals is crucial to minimize any vibrations from being 

transmitted through structure or ductwork.

 

5

Severe vibrations or any sounds of knocking or rubbing 

should be immediately investigated and the XG-Fan Powered 

Air Terminal shut down.

 

5

Occasionally, shipping, handling or installing can  

unbalance a blower.

Initial Startup/Adjustment of Fan Flow Rate

1.  Check the discharge ductwork is connected.

2.  Verify all the electrical connections are properly installed and 

that all safety covers and access panels are in place.

3.  Inspect the XG-Fan Powered Air Terminal and duct work 

for the presence of any packaging or foreign materials and 

remove if found.

4.  Fan motor is shipped from the factory set at full speed.

5.  Allow the motor to warm up for a period of 10 minutes prior 

to adjusting the SCR motor speed control.

6.  During the warm up period, inspect the ductwork for leaks 

and make necessary repairs.

Caution: 

Do not operate the XG-Fan Powered Air Terminal if 

the downstream ductwork is not present.

7.  Flow adjustment: Turn the SCR motor speed control counter-

clockwise to reduce the fan speed.

8.  Turn the SCR motor speed control clockwise to increase fan 

speed.

9.  Set the XG-Fan Powered Air Terminal to full heating (maxi-

mum induction).

10.  Adjust the downstream dampers (if present).

11.  Adjust the SCR motor speed control to deliver the desired 

air flow rate by measuring the air delivered to the room outlets 

using a flow hood or other instruments.

12.  Set the XG-Fan Powered Air Terminal to full cooling (maxi-

mum primary air).

13.  The fan speed may need to be readjusted with the primary 

air and ventilation at maximum set point to ensure that no 

supply air is discharged at the plenum air intake port.

14.  Recheck full heating.

Warning: 

SCR motor speed control will cause all electric 

motors to run hotter. Speed reduction should never fall 

below 700 RPM for proper lubrication of the bearings/

sleeves.

Fan Motor Maintenance

The fan motor is equipped with permanently lubricated bearings. 
Inspect the fan motor, fan and XG-Fan Powered Air Terminal unit 
for a buildup of dust or foreign material.Clean as required based 
on the operating environment and type of insulation installed.

Fan Startup for Series Constant Volume XG-Fan Powered Air 

Terminals

• 

It is standard operating procedure for Series (Constant 

Volume) XG-Fan Powered Air Terminal units to close pri-

mary air damper if the fan is shut off during unoccupied 

times.

• 

Upon morning warm up, the primary air damper should be 

closed before the fan is re-energized or restarted to prevent 

the fan blower wheel from running backwards.

• 

Once the fan is running in the proper direction, the primary 

damper can be re-opened.

• 

The reason for this coordination between the primary damper 

and fan is due to the Series Constant Volume fan design.

• 

The fan blower and motor are positioned “in series” with the 

primary inlet and any residual primary air traveling through 

the XG-Fan Powered Air Terminal can cause the fan blower 

wheel to run backwards.

• 

If the fan blower wheel is rotating backwards at fan startup 

and the fan motor is re-energized, this condition results in a 

high torque condition which could lead to premature motor 

failure.

• 

It can also loosen the set screw on the fan blower wheel-to-

motor shaft.

• 

This condition is not a manufacturing defect and thus not 

covered under our standard warranty.

• 

If the control scheme is as described above, the fan blower 

wheel set screw should be periodically checked for tightness 

and verify that LOCKTITE is applied.

Содержание XG-BP

Страница 1: ...empting to assemble install operate or maintain the product described Protect yourself and others by observing all safety information Failure to comply with these instructions will result in voiding o...

Страница 2: ...ts 5 The XG Fan Powered Air Terminal should be suspended from the building structure in a horizontal plane with the bottom access panel facing down 5 Do not obstruct the bottom access panels or side m...

Страница 3: ...These clearances recommendations are not meant to preclude NEC requirements or local building codes that may be applicable which are the responsibility of the installing contractor Connecting Duct Wo...

Страница 4: ...s with Hot Water Coils Always inspect the hot water coils for damage prior to install ing the XG Fan Powered Air Terminal Caution The copper tubing should not be used as lift points The hot water coil...

Страница 5: ...ckwise to reduce the fan speed 8 Turn the SCR motor speed control clockwise to increase fan speed 9 Set the XG Fan Powered Air Terminal to full heating maxi mum induction 10 Adjust the downstream damp...

Страница 6: ...er assembly to hang from the power leads Fan Motor Removal from Blower 1 Loosen the blower wheel hub set screw to fan motor shaft 2 Remove the 3 screws holding motor leg brackets to blower housing 3 S...

Страница 7: ...ower supply wiring voltage are correct contact factory for further assistance Manual reset safety switch has tripped 1 Push the reset safety button on back of safety reset The manual safe ty reset is...

Страница 8: ...ng coil 6 Use an ohmmeter to check continuity of the holding coil on the back up contractor 7 If bad contact factory for replacement backup contractor Insufficient air flow across the electric heat in...

Страница 9: ...XG Fan Powered Air Terminals Rev 2 9 Figure 3...

Отзывы: