Laboratory Exhaust System

8

®

WARNING

In a kitchen exhaust application, do not use a speed 
control or isolation damper.

NOTE

In a kitchen fan and high temperature applications 
exhaust upblast fans must have external wiring.

Kitchen Roof Mounting Installation

UL/cUL 762 installation for restaurant applications

1.  The size of the duct must be equal to the inlet opening.
2.  Secure the fan to curb at all four corners using a 

minimum eight anchor bolts, lag screws or other 
suitable fasteners.

3.  Use optional grease trap and external junction box.
4.  Area codes may require a continuous weld between 

duct and inlet.

5.  To comply with NFPA 96, the discharge is required 

to be a minimum of 40 inches 

(1016 mm)

 above the 

roof deck and a minimum of 10 ft. from any building 
air intake. The minimum velocity in the duct should be 
500 ft/min. or greater.

6.  Ductwork to an upblast discharge exhaust fan is 

constructed of carbon steel not less than 16 MSG 

(1.6 mm)

 and extends a minimum of 18 inches 

(457 mm)

 above the roof surface.

7.  Ensure that a minimum of 500 ft/min. of air velocity 

through the fan is maintained per NFPA 96, clause 
8.2.1.1, 2008 edition and UL 762, Issue #5,  
December 19, 2003, clause 6.2.

Grease Trap

A grease trap is an aluminum trap designed to collect 
grease residue to avoid drainage onto roof surface. It 
contains a built-in water separating baffle.

Instructions

1.  Apply cover to grease trap. Install clip nuts to trap over 

holes provided. Attach cover with two #10 - 24 x 1/2 
fasteners.

2.  Position the container under the grease drain so the 

drain spout enters the cover approximately 1-1/2 to 
2 in. 

(38-51 mm)

.

3.  Locate and mark the container mounting holes on the 

extended base or roof curb. 

4.  Drill 3/16 in. (

5 mm

) diameter holes in marked locations.

5.  Apply container with #10 - 24 x 3/4 fasteners.
6.  For most climates, fill container with water (at 

installation and after each cleaning) until it flows out the 
drain hole. The unit is now ready for use.

Maintenance

Regular inspection of grease trap is recommended. 
Depending on the amount of grease discharged through 
the fan, the grease trap should be changed accordingly to 
ensure proper operation.

Roof Curb

Grease

Trap

Grease

Trap

Welded duct

by others.

Minimum of

18 inches

(457 mm)

above roof

deck per

NFPA.

Roof Deck

Typical Commercial Kitchen Installation

Содержание Vektor-HS

Страница 1: ...instructions and should be aware of general safety precautions Improper installation can result in electric shock possible injury due to coming in contact with moving parts as well as other potential hazards Other considerations may be required if high winds or seismic activity are present If more information is needed contact a licensed professional engineer before moving forward 1 Follow all loc...

Страница 2: ...eratures should be evenly maintained between 30 F and 110 F 1 C and 43 C Wide temperature swings may cause condensation and sweating of metal parts All accessories must be stored indoors in a clean dry atmosphere Remove any accumulations of dirt water ice or snow and wipe dry before moving to indoor storage To avoid sweating of metal parts allow cold parts to reach room temperature To dry parts an...

Страница 3: ...ual components of a system have matching identification tags which should be used to identify and assemble the complete system Assembling systems with different identification tags can cause reductions in the fan s performance Prior to fully assembling and installing the Vektor H or Vektor HS fans inspect bypass air plenums and the fan assembly to make sure they are in working order Pre Installati...

Страница 4: ...re lifting be sure that all shipping materials have been removed from the unit 2 Use standard lifting and rigging practices 3 All lifting brackets on each unit must be utilized at the same time 4 Fan to be kept level during lifting and installation 5 Spreader bars must span the unit to prevent damage to the unit by the lifting cables 6 Always test lift the unit to check for proper balance and rigg...

Страница 5: ...OTHERS SEE NOTE ABOVE Continuous weld or stitch weld Minimum 6 inch 152 4 mm stitch weld by 3 25 inch 82 5 mm spacing minimum Minimum 6 inch 152 4 mm weld on each corner OR Install 5 16 inch 7 9375 mm 24 Dril Flex Self Drilling Tapping Screws 3 16 inch 4 7625 mm minimum thread engagement into A36 steel centered in flange 4 5 inch 114 3 mm spacing 5 8 inch 15 875 mm minimum edge distance ALL HARDWA...

Страница 6: ...r is present in the roof curb the duct is located between the roof curb and the damper adapter tray Duct Connection to Curb Side or End Duct Connection Vektor H or Vektor HS With bypass air plenum NOTE Plenum is provided with removable side or end panels allowing the proper duct connection Duct to Bypass Air Plenum Bypass Air Plenum Weatherhood Duct flange and gasketing by others Roof Curb Option ...

Страница 7: ...ozzle subassemblies as shown in the submittal drawing Align flange bolt holes and fasten sections using the 3 8 inch 316 stainless steel bolts washers and lock washers provided 6 Follow electrical connection and pre start up checks as listed on pages 10 and 11 System Assembly NOTE When installing each section be certain to rig each section separately using the lifting lugs provided Stack Extension...

Страница 8: ... of air velocity through the fan is maintained per NFPA 96 clause 8 2 1 1 2008 edition and UL 762 Issue 5 December 19 2003 clause 6 2 Grease Trap A grease trap is an aluminum trap designed to collect grease residue to avoid drainage onto roof surface It contains a built in water separating baffle Instructions 1 Apply cover to grease trap Install clip nuts to trap over holes provided Attach cover w...

Страница 9: ...y occur Drain connections are 1 2 inch NPT Installed piping to have a downward angle to allow for drainage Fill traps to recommended level before start up Note A conservative method of trap design is to set N total static pressure Fan Drain Connection Plenum Drain Connection H 1 in for each inch of maximum negative static pressure plus 1 in J 1 2 of H L H J Pipe diameter L H J Connect this end to ...

Страница 10: ...ed to fan housing Optional transformer and isolation damper refer to CAPS file selection SINGLE PHASE LAYOUT THREE PHASE LAYOUT THREE PHASE WITH VFD LAYOUT Field Wiring Factory Wiring Field Wiring Factory Wiring Field Wiring Factory Wiring Three Phase with Variable Frequency Drives Layout LINE IN 115 208 230 277 volt single phase MOTOR DISCONNECT 115 208 230 277 volt Single phase TRANSFORMER 208 2...

Страница 11: ... inlet For 3 phase installations fan rotation can be reversed by simply interchanging any two of the three electrical leads For single phase installations follow the wiring diagram located on the motor Radial Gap Overlap A Inlet Cone Wheel Vektor H Applications with Variable Frequency Drive VFD For Vektor systems with single point three phase wiring per blower the isolation damper actuator will be...

Страница 12: ...rive Motor bearings are lubed for life with no maintenance required If motor or wheel needs to be serviced or replaced use the lifting lugs to pull assembly cartridge out Removal of Dust and Dirt Dirt clogs cooling openings on the motor housing contaminates bearing lubricant and collects on the impeller causing severe imbalance if left unchecked The exterior surface of the motor and impeller shoul...

Страница 13: ... a gravity isolation damper remove the panel opposite the weatherhood on the bypass air plenum section and slide the damper straight out toward you When performing maintenance on an isolation damper with an actuator remove the bolted weatherhood and disconnect the actuator from damper Then remove the panel opposite the weatherhood on the bypass air plenum section and slide the isolation damper out...

Страница 14: ...P PAINT REPAIR KIT CONTENTS One Zinc Clad Aerosol Can One pint recoat epoxy primer grey with one pint recoat epoxy primer catalyst One quart H S Polyurethane One Scotch Brite scratch pad Two 1 1 2 inch wide paint brushes Four pint sized empty cans for mixing One quart sized empty can for mixing Zinc repair instructions MSDS sheets NOTE While the manufacturer provides heavy duty quality products fo...

Страница 15: ...RAME BOTTOM BAR 2 5 FRAME TOP BAR 2 6 FRAME WELD 2 7 BLADE WELD 2 8 ACTUATOR MOUNT 2 9 LIFT LUG 4 10 ACTUATOR COVER 2 11 BLADE SEAL RIGHT 2 12 BLADE SEAL LEFT 6 13 FLEX BACKING 4 14 VEKTOR BACKING 2 15 ACTUATOR 2 16 ELECTRICAL BOX 1 17 BEARING 4 18 BLADE SEAL 4 19 FLEX SEAL 2 20 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Quantity 1 for sizes 9 thru 13 Quantity 2 for sizes 16 thru 36 Item Q...

Страница 16: ...AM PM Notes ____________________________________________ _________________________________________________ _________________________________________________ _________________________________________________ _________________________________________________ Date____________________Time______________ AM PM Notes ____________________________________________ ___________________________________________...

Отзывы: